Agreement State Event Number: 53631
Rep Org: COLORADO DEPT OF HEALTH
Licensee: MARIOTT DENVER TECH CENTER
Region: 4
City: DENVER   State: CO
County:
License #: GL000359
Agreement: Y
Docket:
NRC Notified By: PHILLIP PETERSON
HQ OPS Officer: JEFF HERRERA
Notification Date: 10/01/2018
Notification Time: 10:23 [ET]
Event Date: 12/19/2017
Event Time: 00:00 [MDT]
Last Update Date: 10/01/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
AGREEMENT STATE
Person (Organization):
THOMAS FARNHOLTZ (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB (EMAIL)
This material event contains a "Less than Cat 3" level of radioactive material.

Event Text

AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGNS

The following report was received from the Colorado Department of Public Health and Environment via email:

"Marriott Denver Tech Center reported three lost tritium exit signs when conducting the annual reconciliation."

Event Report ID No.: CO180020

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf

To top of page
Agreement State Event Number: 53632
Rep Org: COLORADO DEPT OF HEALTH
Licensee: OLINGER HAMPDEN FUNERAL HOME AND CEMETARY
Region: 4
City: DENVER   State: CO
County:
License #: GL001929
Agreement: Y
Docket:
NRC Notified By: PHILLIP PETERSON
HQ OPS Officer: JEFF HERRERA
Notification Date: 10/01/2018
Notification Time: 10:27 [ET]
Event Date: 12/29/2017
Event Time: 00:00 [MDT]
Last Update Date: 10/01/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
AGREEMENT STATE
Person (Organization):
THOMAS FARNHOLTZ (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB (EMAIL)
This material event contains a "Less than Cat 3" level of radioactive material.

Event Text

AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGNS

The following report was received from the Colorado Department of Public Health and Environment via email:

"Olinger Hampden Funeral Home & Cemetery reported three lost tritium exit signs when conducting the annual reconciliation."

CO Event Report ID No.: CO180021

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf

To top of page
Agreement State Event Number: 53633
Rep Org: COLORADO DEPT OF HEALTH
Licensee: CANYON BAKEHOUSE
Region: 4
City: JOHNSTOWN   State: CO
County:
License #: GL002453
Agreement: Y
Docket:
NRC Notified By: PHILLIP PETERSON
HQ OPS Officer: JEFF HERRERA
Notification Date: 10/01/2018
Notification Time: 10:30 [ET]
Event Date: 12/22/2017
Event Time: 00:00 [MDT]
Last Update Date: 10/01/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
AGREEMENT STATE
Person (Organization):
THOMAS FARNHOLTZ (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB (EMAIL)
This material event contains a "Less than Cat 3" level of radioactive material.

Event Text

AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGNS

The following report was received from the Colorado Department of Public Health and Environment via email:

"Canyon Bakehouse reported that three tritium exit signs were not in the building when the ownership of the building was transferred."

CO Event Report ID No.: CO180023

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf

To top of page
Agreement State Event Number: 53634
Rep Org: COLORADO DEPT OF HEALTH
Licensee: KEYSTONE REPORT-PROPERTY MANAGEMENT
Region: 4
City: KEYSTONE   State: CO
County:
License #: GL000311
Agreement: Y
Docket:
NRC Notified By: PHILLIP PETERSON
HQ OPS Officer: JEFF HERRERA
Notification Date: 10/01/2018
Notification Time: 10:33 [ET]
Event Date: 06/28/2018
Event Time: 00:00 [MDT]
Last Update Date: 10/01/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
AGREEMENT STATE
Person (Organization):
THOMAS FARNHOLTZ (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB (EMAIL)
This material event contains a "Less than Cat 3" level of radioactive material.

Event Text

AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGNS

The following report was received from the Colorado Department of Pubic Heath and Environment via email:

"Keystone Resort-Property Management reported one tritium exit sign was unable to be located during the annual reconciliation."

CO Event Report ID No.: CO180025

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf

To top of page
Agreement State Event Number: 53635
Rep Org: COLORADO DEPT OF HEALTH
Licensee: UNITED PARCEL SERVICE
Region: 4
City: COMMERCE CITY   State: CO
County:
License #: GL000169
Agreement: Y
Docket:
NRC Notified By: PHILLIP PETERSON
HQ OPS Officer: JEFF HERRERA
Notification Date: 10/01/2018
Notification Time: 10:33 [ET]
Event Date: 07/27/2018
Event Time: 00:00 [MDT]
Last Update Date: 10/01/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
AGREEMENT STATE
Person (Organization):
THOMAS FARNHOLTZ (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB (EMAIL)
This material event contains a "Less than Cat 3" level of radioactive material.

Event Text

AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGNS

The following report was received from the Colorado Department of Public Health and Environment via email:

"United Parcel Service reported one tritium exit sign was lost when the building was renovated."

CO Event Report ID No.: CO180024

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf

To top of page
Power Reactor Event Number: 53656
Facility: SOUTH TEXAS
Region: 4     State: TX
Unit: [1] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: SILVESTRE ROMERO JR.
HQ OPS Officer: STEVEN VITTO
Notification Date: 10/10/2018
Notification Time: 01:29 [ET]
Event Date: 10/09/2018
Event Time: 00:00 [CDT]
Last Update Date: 10/10/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
HEATHER GEPFORD (R4DO)
CYBER ASSESSMENT (EMAIL)
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Cold Shutdown 0 Cold Shutdown
2 N Y 100 Power Operation 100 Power Operation

Event Text

UNPLANNED LOSS OF EMERGENCY RESPONSE EQUIPMENT

"At 2115 CST on October 9, 2018, South Texas Project Electric Generating Station (STPEGS) experienced an unplanned loss of the Integrated Computer System (ICS) to the Emergency Operations Facility (EOF). The loss of ICS resulted in a major loss of emergency assessment capability to the STPEGS Emergency Operations Facility (EOF) for greater than 75 minutes. Assessment capability has been verified to be available in the Unit 1 and Unit 2 Technical Support Centers (TSC) and the Unit 1 and Unit 2 Control Rooms.

"This report is being made pursuant to 10 CFR 50.72(b)(3)(xiii), any event that results in a major loss of emergency assessment capability, off site response capability, or off site communications ability.

"The NRC Resident Inspector has been informed."

The cause of the unplanned loss is currently being investigated and compensatory measures are in place.


* * * UPDATE ON 10/10/18 AT 0951 EDT FROM RICK NANCE TO PHIL NATIVIDAD * * *

Integrated Computer System was returned to service as of 0810 CDT on October 10, 2018.

Notified R4DO (Gepford) and CAT via email.

To top of page
!!!!! THIS EVENT HAS BEEN RETRACTED.THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor Event Number: 53657
Facility: QUAD CITIES
Region: 3     State: IL
Unit: [1] [2] []
RX Type: [1] GE-3,[2] GE-3
NRC Notified By: JEFFREY EASLEY
HQ OPS Officer: STEVEN VITTO
Notification Date: 10/10/2018
Notification Time: 03:26 [ET]
Event Date: 10/09/2018
Event Time: 00:00 [CDT]
Last Update Date: 11/14/2018
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
AARON McCRAW (R3DO)
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation

Event Text

CONTROL ROOM EMERGENCY VENTILATION AC SYSTEM INOPERABLE

"On October 9, 2018 at 2002 CDT the Control Room Emergency Ventilation Air Condition (CREV AC) system was in the process of being returned to service following maintenance. During the return to service, the end bell on the CREV AC Condenser developed a significant leak requiring isolation. No work was performed on the CREV AC Condenser during the work window.

"The CREV AC system maintains a habitable control room environment and ensures the operability of components in the control room emergency zone during accident conditions.

"This notification is being made in accordance with 10CFR50.72(b)(3)(v)(D), "Event or Condition That Could Have Prevented Fulfillment of a Safety Function " because the CREV system is a single train system required to mitigate the consequences of an accident."

The NRC Resident Inspector has been notified.

* * * RETRACTION AT 1714 EST ON 11/14/2018 FROM JASON SWAIN TO JEFF HERRERA * * *

"The purpose of this notification today (November 14, 2018) is to retract the ENS Report made on October 10, 2018 at 0326 EDT (ENS Report #53657).

"Upon further investigation, it was determined that while the CREV AC system was out of service for planned maintenance and inoperable, the return to service valve sequencing caused an in-rush of residual heat removal service water (RHRSW) at 300 psig dead-heading into the refrigeration condensing unit (RCU). Previous normal sequencing had refilled the RCU with service water which is supplied at 100 psig. This unexpected higher than normal pressure on the RCU end bell gasket (rated at 150 psig) caused the gasket to be pushed from its normally seated position to allow a leak path. The gasket was not previously leaking; upon removal was inspected and no evidence of premature cracks or tears were found.

"The CREV AC system leak was induced by an improper coordination of return to service activities at the time of discovery, and the leak path was not previously present. This was not a latent failure. As such, a pre-exiting condition that could have prevented the fulfillment of a safety function did not exist, and based on this information, ENS Report# 53657 is being retracted.

"Note: On October 11, 2018 at 1330 hours CDT, the CREV RCU System gaskets were replaced and the system was returned to service under the properly sequenced tagout and was returned to Operable status.

"The NRC Resident Inspector has been notified. "

Notified the R3DO (Peterson).