Event Notification Report for April 4, 2017

U.S. Nuclear Regulatory Commission
Operations Center

Event Reports For
04/03/2017 - 04/04/2017

** EVENT NUMBERS **


52637 52657 52658 52662

To top of page
Agreement State Event Number: 52637
Rep Org: LOUISIANA RADIATION PROTECTION DIV
Licensee: BLUE CUBE OPERATIONS LLC
Region: 4
City: PLAQUEMINE State: LA
County:
License #: LA-133286-L01
Agreement: Y
Docket:
NRC Notified By: JAMES PATE
HQ OPS Officer: STEVE SANDIN
Notification Date: 03/24/2017
Notification Time: 11:48 [ET]
Event Date: 03/23/2017
Event Time: 11:00 [CDT]
Last Update Date: 03/24/2017
Emergency Class: NON EMERGENCY
10 CFR Section:
AGREEMENT STATE
Person (Organization):
JAMES DRAKE (R4DO)
NMSS_EVENTS_NOTIFIC (EMAI)

Event Text

AGREEMENT STATE REPORT - FIXED GAUGE SHUTTER MALFUNCTION

The following information was received from the State of Louisiana via fax:

"On March 24, 2017, LDEQ [Louisiana Department of Environmental Quality] was notified by Blue Cube Operations LLC, that during an annual equipment inspection, it was determined that a level density gauge shutter was malfunctioning.

"The density gauge was a TN Technologies Inc. Model: 5202, and equipped with a TN Technologies Inc. Model 57157C sealed source - serial number: GK-9492. Initial source activity was 500 mCi [Cs-137], after decay correction, it is 341.78 mCi.

"No release or exposure to personnel. Blue Cube Operations plans to repair the shutter to the level density gauge.

"Event Report ID No.: LA170004"

To top of page
Part 21 Event Number: 52657
Rep Org: AMETEK
Licensee: VISHAY/INTERNATIONAL
Region: 3
City: COLUMBUS State: OH
County:
License #:
Agreement: Y
Docket:
NRC Notified By: ETHAN SALSBURY
HQ OPS Officer: HOWIE CROUCH
Notification Date: 04/03/2017
Notification Time: 09:28 [ET]
Event Date: 06/01/2016
Event Time: [EDT]
Last Update Date: 04/03/2017
Emergency Class: NON EMERGENCY
10 CFR Section:
21.21(d)(3)(i) - DEFECTS AND NONCOMPLIANCE
Person (Organization):
MICHAEL KUNOWSKI (R3DO)
CHRISTOPHER CAHILL (R1DO)
PART 21/50.55 REACT (EMAI)
EUGENE GUTHRIE (R2DO)
MICHAEL VASQUEZ (R4DO)

Event Text

PART 21 NOTIFICATION - FAILURE OF VISHAY DIODES

The following information is the summary letter was received from Ametek via email:

"Product: Vishay/ International Rectifier Clamp, Diodes 600 V, 250A, forward and reverse bias. Ametek part numbers 07-600254-00 and 07-600255-00.

"Ametek Solidstate Controls is submitting the following Report of a Potential Defect in accordance with the requirements of 10CFR21. This notification is applicable to equipment model number 85-VC0250-29 provided to Dominion Nuclear at Millstone Power Station. Serial numbers affected by this potential defect are:

C901880111
C901880211
C901880221
C901880231
C901880244

"AMETEK SOLIDSTATE CONTROLS CORRECTIVE ACTION: If you wish to replace the diodes, Ametek Solidstate Controls will work with you to arrange replacements. Please contact Mr. Mark Shreve of our Client Services group at 1-800-222-9079 or 1-614-846-7500 ext. 6332. mark.shreve@ametek.com"

"Please contact us at telephone: 614-846-7500; 1-800-635-7300 or e-mail: ethan.salsbury@ametek.com, if there are any questions.

To top of page
Power Reactor Event Number: 52658
Facility: SUSQUEHANNA
Region: 1 State: PA
Unit: [1] [2] [ ]
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: DARVIN DUTTRY
HQ OPS Officer: HOWIE CROUCH
Notification Date: 04/03/2017
Notification Time: 11:37 [ET]
Event Date: 04/03/2017
Event Time: 10:45 [EDT]
Last Update Date: 04/03/2017
Emergency Class: NON EMERGENCY
10 CFR Section:
20.1906(d)(2) - EXTERNAL RAD LEVELS > LIMITS
20.1906(d)(1) - SURFACE CONTAM LEVELS > LIMITS
Person (Organization):
CHRISTOPHER CAHILL (R1DO)
NMSS_EVENTS_NOTIFIC (EMAI)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N N 0 Cold Shutdown 0 Cold Shutdown

Event Text

EXCLUSIVE USE TRANSPORT VEHICLE EXCEEDED CONTACT DOSE RATES

"This is being reported under 10CFR20.1906(d)(1,2). At 1045 hours [EDT], the SSES [Susquehanna Steam Electric Station] Radwaste shipper was notified by the RP [Radiation Protection] shipping technician performing a receipt survey of an open transport vehicle shipped exclusive use carrying an empty radwaste liner exceeded the 10CFR71.47(b)(1) vehicle contact dose rates of 200 mR/hr. Per NDAP-QA-0720 [Nuclear Department Administrative Procedure] Attachment E, contaminated /radioactive shipments this is a 1 hour notification for exceeding the radiological receipt survey requirements of 200 mR/hr at any point on the outer surface of the vehicle."

The vehicle was from Energy Solutions. The licensee will be using the vehicle to transport radwaste from the facility.

The licensee has notified the Pennsylvania Emergency Management Agency and the NRC Resident Inspector.

To top of page
Power Reactor Event Number: 52662
Facility: ROBINSON
Region: 2 State: SC
Unit: [2] [ ] [ ]
RX Type: [2] W-3-LP
NRC Notified By: VINCENT LEETH
HQ OPS Officer: JEFF HERRERA
Notification Date: 04/04/2017
Notification Time: 02:33 [ET]
Event Date: 04/03/2017
Event Time: 21:55 [EDT]
Last Update Date: 04/04/2017
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
EUGENE GUTHRIE (R2DO)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N N 0 Hot Standby 0 Hot Standby

Event Text

AUTOMATIC ACTUATION OF AUXILIARY FEEDWATER SYSTEM DURING SURVEILLANCE TESTING

"At 2155 hours EDT on 04/03/2017, with the unit in Mode 3 at 0 [percent] power, an automatic actuation of the Auxiliary Feedwater (AFW) System occurred during surveillance testing. The cause of the AFW system auto-start was an improperly performed procedure step to bypass the auto-start logic of the AFW pumps during performance of the surveillance test. The 'A' and 'B' AFW pumps automatically started as designed when the feedwater isolation signal was received.

"Due to the valid actuation of the AFW system, this event requires an 8-hour non-emergency notification under 10 CFR 50.72(b)(3)(iv)(A)(B)(6). At no time did this occurrence pose undue risk to the health and safety of the public.

"The NRC Resident Inspector has been notified."

Page Last Reviewed/Updated Wednesday, March 24, 2021