Skip to main content

Alert

Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for October 30, 2015

U.S. Nuclear Regulatory Commission
Operations Center

Event Reports For
10/29/2015 - 10/30/2015

** EVENT NUMBERS **


51486 51502 51506 51507

To top of page
Non-Agreement State Event Number: 51486
Rep Org: EVONIK CORPORATION
Licensee: GENERAL LICENSE
Region: 3
City: LAFAYETTE State: IN
County:
License #: General
Agreement: N
Docket:
NRC Notified By: APRIL RADEMAKER
HQ OPS Officer: DANIEL MILLS
Notification Date: 10/21/2015
Notification Time: 13:08 [ET]
Event Date: 10/11/2015
Event Time: [EDT]
Last Update Date: 10/21/2015
Emergency Class: NON EMERGENCY
10 CFR Section:
20.2201(a)(1)(i) - LOST/STOLEN LNM>1000X
Person (Organization):
ROBERT DALEY (R3DO)
NMSS_EVENTS_NOTIFIC (EMAI)

This material event contains a "Less than Cat 3 " level of radioactive material.

Event Text

LOST TRITIUM EXIT SIGN

A tritium exit sign was mistakenly placed in general waste by an employee who was replacing the sign on 10/11/15. The employee reported the mistake on 10/13/15 and the licensee initiated attempts to locate the sign. The sign was determined to have been placed in a general waste container which had already been collected. The manufacture date of the sign was 2/2009 and at the time of the disposal the source was intact. The lost source material (0.426 TBq of Tritium as of 2/2009) is considered unrecoverable.

THIS MATERIAL EVENT CONTAINS A "LESS THAN CAT 3" LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf

To top of page
Power Reactor Event Number: 51502
Facility: QUAD CITIES
Region: 3 State: IL
Unit: [1] [2] [ ]
RX Type: [1] GE-3,[2] GE-3
NRC Notified By: CRAIG VROMAN
HQ OPS Officer: DONG HWA PARK
Notification Date: 10/27/2015
Notification Time: 17:50 [ET]
Event Date: 10/27/2015
Event Time: 10:30 [CDT]
Last Update Date: 10/29/2015
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
ERIC DUNCAN (R3DO)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation

Event Text

TSC AIR FILTRATION SYSTEM DEGRADED

"A planned surveillance was started on the Quad Cities Station Technical Support Center (TSC) ventilation air filtration system. The surveillance measures the flow rate through the air filtration unit and verifies the TSC is pressurized to ensure habitability requirements. The flow rate obtained was high, outside of acceptance criteria, and the surveillance was stopped pending resolution.

"If an emergency is declared requiring TSC activation during this period, the TSC will be staffed and activated using existing procedures. If TSC evacuation is warranted due to radiological conditions, the facility will be relocated in accordance with existing procedures.

"This event is reportable per 10CFR50.72(b)(3)(xiii) since the air filtration unit affects an emergency response facility.

"The NRC Resident Inspector has been notified."

* * * UPDATE FROM CLIFFORD STEINER TO HOWIE CROUCH AT 1315 EDT ON 10/29/15 * * *

"The TSC Air Filtration system was successfully tested on 10/27/15 at 2100 CDT."

The licensee notified the NRC Resident Inspector.

Notified R3DO (Stoedter).

To top of page
Power Reactor Event Number: 51506
Facility: POINT BEACH
Region: 3 State: WI
Unit: [ ] [2] [ ]
RX Type: [1] W-2-LP,[2] W-2-LP
NRC Notified By: KILE HESS
HQ OPS Officer: DAN LIVERMORE
Notification Date: 10/29/2015
Notification Time: 10:38 [ET]
Event Date: 10/29/2015
Event Time: 03:48 [CDT]
Last Update Date: 10/29/2015
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
KARLA STOEDTER (R3DO)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N N 0 Hot Standby 0 Hot Standby

Event Text

ACTUATION OF THE AUXILIARY FEEDWATER SYSTEM DUE TO MAIN TRANSFORMER LOCKOUT

"At 0348 CDT, while Point Beach Unit 2 was performing outage activities, it experienced a Main Power Transformer lockout and associated loss of busses (2A-01, 2A-02, 2B-01 and 2B-02). The loss of the two non-vital 4160 V buses resulted in actuation of the Unit 2 undervoltage logic which resulted in actuation of the Auxiliary Feedwater System. The Auxiliary Feedwater System functioned normally upon actuation.

"This condition was determined to be reportable per 10CFR50.72(b)(3)(iv)(A)(6), PWR auxiliary or emergency feedwater system actuation.

"This event did not affect the operating Unit 1.

"The NRC Senior Resident Inspector has been notified."

To top of page
Part 21 Event Number: 51507
Rep Org: CB&I
Licensee: CB&I
Region: 1
City: CHARLOTTE State: NC
County:
License #:
Agreement: Y
Docket:
NRC Notified By: CURTIS CASTELL
HQ OPS Officer: HOWIE CROUCH
Notification Date: 10/29/2015
Notification Time: 15:33 [ET]
Event Date: 05/05/2015
Event Time: [EDT]
Last Update Date: 10/29/2015
Emergency Class: NON EMERGENCY
10 CFR Section:
21.21(d)(3)(i) - DEFECTS AND NONCOMPLIANCE
Person (Organization):
BRIAN BONSER (R2DO)
PART 21/50.55 REACT (EMAI)

Event Text

PART 21 REPORT - DEFECT ASSOCIATED WITH PRESSURIZER INSTRUMENTATION PIPING PENETRATION IN MODULE FOR VOGTLE UNIT 3

The following information was excerpted from an email received from CB&I:

"This letter provides a report in accordance with 10 CFR 21.21 pertaining to the identification of a defect associated with a structural module piping penetration for the Vogtle Unit 3 AP1000 project. The defect is associated with a Pressurizer instrumentation piping penetration in structural module CA01 for Vogtle Unit 3.

"This condition was previously identified by interim report letters dated July 1, 2015, and September 2, 2015.

"The discovery date of these deviations is based on the date of the associated CB&I Power Inspection Report (IR). That IR was initiated on May 5, 2015. Interim Part 21 reports dated July 1, 2015, and September 2, 2015, were submitted to the NRC that state the evaluation of this condition was expected to be completed by October 30, 2015. The interim reports were identified as Accession Nos. ML15254A043 and ML15201A130, and Log Nos. 2015-50-01 and 2015-50-00, on the NRC 'Part 21 Reports' website.

"Name and address of the individual or individuals informing the Commission:

Don DePierro
CB&I Power
128 S. Tryon St., Suite 1000
Charlotte, NC 28202"

Page Last Reviewed/Updated Thursday, March 25, 2021

Page Last Reviewed/Updated Thursday, March 25, 2021