Event Notification Report for April 1, 2015

U.S. Nuclear Regulatory Commission
Operations Center

Event Reports For
03/31/2015 - 04/01/2015

** EVENT NUMBERS **


50351 50807 50919 50920 50943

To top of page
Power Reactor Event Number: 50351
Facility: HATCH
Region: 2 State: GA
Unit: [1] [2] [ ]
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: KENNY HUNTER
HQ OPS Officer: HOWIE CROUCH
Notification Date: 08/07/2014
Notification Time: 20:00 [ET]
Event Date: 08/07/2014
Event Time: 17:07 [EDT]
Last Update Date: 03/31/2015
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
Person (Organization):
REBECCA NEASE (R2DO)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 90 Power Operation 90 Power Operation

Event Text

UNANALYZED CONDITION DUE TO DISCOVERY OF DEGRADED FIRE BARRIER WALLS

"During a fire inspection activity involving inspection of fire walls that serve as Appendix R barriers, degradation of some fire walls was identified that was sufficient to prevent these walls from meeting Appendix R requirements as 3-hour fire barriers. In the event of a postulated fire in the affected areas, both safe shutdown paths on the affected unit could be compromised. Given this information, the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B).

"Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded penetrations in these same fire areas. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded conditions can be corrected.

"Condition Reports: 850802, 850819"

In addition to automatic fire protection features, the licensee has posted fire watches as a compensatory measure.

The licensee has notified the NRC Resident Inspector.


* * * UPDATE FROM STANLEY STONE TO DONALD NORWOOD AT 1814 EST ON 11/24/2014 * * *

"As part of the 'extent of condition' corrective action for the condition identified in EN 50351, an inspection activity is in progress to inspect the remaining fire walls for conditions similar to those reported on 8/7/2014. During this inspection, another condition was identified involving some degradation of the fire wall between Fire Area 1023 - RPS MG Set Room and Fire Area 1015 - Annunciator Room. In the event of a postulated fire in the affected areas both safe shutdown paths on Unit 1 could be compromised. Given this information, the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B).

"Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded penetrations in these same fire areas and will remain in place until the wall is repaired. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition is repaired. The inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS update report and will be documented in a revised LER at the end of the inspection activity.

"Condition Report: 898908."

The licensee will notify the NRC Resident Inspector.

Notified R2DO (Ehrhardt).


* * * UPDATE FROM KENNY HUNTER TO DANIEL MILLS AT 1758 EST ON 11/25/2014 * * *

"As part of the 'extent of condition' corrective action for the condition identified in EN 50351, an inspection activity is in progress to inspect the remaining fire walls for conditions similar to those reported on 8/7/2014. During this inspection, another condition was identified involving some degradation of the fire wall between Fire Area 1016 - 600 Volt Switchgear Room 1C and Fire Area 1017 - 600 Volt Switchgear Room 1D. In the event of a postulated fire in the affected areas, both safe shutdown paths on Unit 1 could be compromised. Given this information the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B).

"Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded penetrations in these same fire areas and will remain in place until the wall is repaired. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition is repaired. The inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS update report and will be documented in a revised LER at the end of the inspection activity."

The licensee notified the NRC Resident Inspector.

Notified R2DO (Ernstes).


* * * UPDATE FROM SCOTT BRITT TO DONALD NORWOOD AT 1706 EST ON 12/4/2014 * * *

"As part of the 'extent of condition' corrective action for the condition identified in EN 50351, an inspection activity is in progress to inspect the remaining fire walls for conditions similar to those reported on 8/7/2014. During this inspection, additional conditions were identified involving multiple fire barriers in the control building that affected both safe shutdown paths on Unit 1 and Unit 2 based on the respective inspection results. In the event of a postulated fire in the affected areas both safe shutdown paths on Unit 1 and 2 could be compromised.

"Given this information the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B). Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded penetrations in these same fire areas and will remain in place until the wall is repaired. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition is repaired. The inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS update report as required and will be documented in a revised LER at the end of the inspection activity."

The licensee will notify the NRC Resident Inspector.

Notified R2DO (Freeman).


* * * UPDATE AT 1842 EST ON 12/12/2014 FROM G.S. GRIFFIS TO MARK ABRAMOVITZ * * *

"As part of the 'extent of condition' corrective action for the condition identified in EN# 50351, an inspection activity is in progress to inspect the remaining fire walls and associated penetrations for conditions similar to those reported on 08/07/2014. During this inspection, nonconformances of multiple fire barriers were identified that bring into question the functionality of the affected fire barriers that can compromise safe shutdown paths on Unit 1 and 2 based on the respective inspection results. Since additional time is required to further evaluate each nonconformance to conclusively determine if the nonconformance is sufficient to consider the barrier nonfunctional, interim conservative fire actions were taken by considering these fire barriers as nonfunctional. Based on this conservative conclusion, in the event of a postulated fire in the affected areas both safe shutdown paths on Unit 1 and 2 could be compromised. Given this information the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B).

"Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded penetrations and fire walls in most of these same fire areas and will remain in place until the barrier(s) are repaired. Additional fire actions were taken as required to address the additional fire areas identified. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition is repaired. The inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report and will be documented in a revised LER at the end of the inspection activity.

"Unit 1 is entering a planned outage due to unrelated activities."

Condition Report: 10000607

The licensee notified the NRC Resident Inspector.

Notified the R2DO (Desai).


* * * UPDATE FROM STANLEY STONE TO DONALD NORWOOD AT 2315 EST ON 1/15/2015 * * *

"As part of the 'extent of condition' corrective action for the conditions identified in EN# 50351, an inspection activity was performed of a fire wall for conditions similar to those reported on 12/12/2014. During this inspection, another condition was identified involving some degradation of the fire wall between Fire Area 1008 - Unit 1 AC Inverter Room and Fire Area 0001 to consider the barrier nonfunctional. In the event of a postulated fire in the affected areas both safe shutdown paths on Unit 1 could be compromised. Given this information the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B).

"Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded fire barriers in these same fire areas and will remain in place until the wall is repaired. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition is repaired. The inspection activity is continuing and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report and will be documented in a revised LER at the end of the inspection activity."

Condition Report: 10013077

The licensee notified the NRC Resident Inspector.

Notified the R2DO (Musser).

* * * UPDATE FROM JOHN MITCHELL TO JEFF HERRERA AT 2025 EST ON 1/21/2015 * * *

"During review and closeout of fire barrier and penetration seals work orders and surveillance procedures performed as part of the 'extent of condition' inspection activity initially described in Event # 50351, the following conditions were identified that in the event of a postulated fire in the respective fire areas listed both safe shutdown paths could be compromised.

"Unit 2 Control Bldg. el. 130', gap in the grout around conduit penetration between fire areas 2013 and 2015
"Unit 1 Reactor Bldg. el. 130', open conduit between fire areas 1203C and 1105

"Given this information the determination was made that this condition meets the reporting criteria of 10 CFR 50.72(b)(3)(ii)(B). Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded fire barriers in the Unit 2 fire area and will remain in place until the affected barrier areas are repaired. Compensatory measures were established for the Unit 1 areas and will remain in place until the affected barriers areas are repaired. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition is repaired. Subsequent similar condition(s) found when performing remaining inspections that meet the reporting requirements will be included in an ENS Update Report and will be documented in a revised LER at the end of the inspection activity.

"Condition Report 10015417
"Condition Report 10015437"

The licensee notified the NRC Resident Inspector.

Notified the R2DO (McCoy).

* * * UPDATE FROM G.S. GRIFFIS TO HOWIE CROUCH AT 1714 EST ON 2/4/15 * * *

"During the review of fire barrier surveillance procedures performed as part of the 'extent of condition' inspection activity for the event initially identified in EN# 50351, some degradation was observed on the east wall of fire area 2006. These nonconforming issues observed on the affected fire wall were identified as affecting both safe shutdown paths for Unit 2. Therefore, in the event of a postulated fire for the affected area, both safe shutdown paths on Unit 2 could be compromised. Given this information, the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B).

"Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire area and will remain in place until the wall is repaired. The presence of the compensatory measures, in addition to portable fire protection equipment located in adjacent areas, ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The extent of condition inspection activity is continuing, and this, and any subsequent similar condition(s) that meets the reporting requirements, will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity."

CR 10021623

Notified R2DO (HAAG).

* * * UPDATE FROM JOHN MITCHELL TO DANIEL MILLS AT 1823 EST ON 2/18/15 * * *

"During performance of work package closeouts to support the 'extent of condition' inspection activity for the event initially identified in EN# 50351, the following fire barriers were identified as failing to meet the procedure acceptance criteria:
- Three penetrations separating Unit 1 Fire Areas 1013 and 0040
- A fire wall deficiency in the wall separating Unit 1 Fire Areas 1015 and 1013

"These nonconforming issues observed on the affected penetrations and fire wall were identified as affecting both safe shutdown paths for Unit 1. Therefore, in the event of a postulated fire for the affected area, both safe shutdown paths on Unit 1 could be compromised. Given this information, the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B).

"Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire area and will remain in place until the wall is repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The extent of condition inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity.

"CR 10028364
"CR 10028366"

The NRC Resident Inspector has been notified. Notified R2DO (Rose).

* * * UPDATE AT 2035 EST ON 02/25/15 FROM SCOTT BRITT TO S. SANDIN * * *

"During the review and closeout of a work package performed as part of the 'extent of condition' for the inspection activity initially described in EN #50351, a fire penetration seal was identified as failing to meet the procedure acceptance criteria. This penetration seal is located in the 2C Diesel Generator (DG) room and passes between Fire Area 2407 and 2408.

"The nonconforming issue observed on the affected penetration was identified as affecting both safe shutdown paths for Unit 2. Compensatory measures were established for the Unit 2 Areas and will remain in place until the affected barriers areas are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The extent of condition inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity.

"CR 10032202"

The licensee will inform the NRC Resident Inspector. Notified R2DO (Seymour).

* * * UPDATE FROM SCOTT BRITT TO HOWIE CROUCH AT 2000 EST ON 3/4/15 * * *

"During an expanded scope inspection, two deficiencies in the following areas were observed that caused the affected barriers to be considered nonfunctional:
- Small imperfections and a hole through Penetration 1Z43-H116C that passes between Fire Area 1101G (Unit 1 Reactor Building Closed Cooling Water (RBCCW) Room) and Fire Area 1006 (Unit 1 Water Analysis Room), and
- Gaps in a civil/architectural joint at the top of the south wall leading from Fire Area 1006 (Unit 1 Water Analysis Room) to Fire Area 0007A (East Corridor in the Control Bldg.).

"These nonconforming conditions observed for the affected penetration and fire barrier were identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire area and will remain in place until the wall is repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS update report as required and will be documented in a revised LER at the end of the inspection activity.

"CR 10035730"

The licensee will be notifying the NRC Resident Inspector. Notified R2DO (Sykes).

* * * UPDATE FROM SCOTT BRITT TO DANIEL MILLS AT 2047 EDT ON 3/16/15 * * *

"During an expanded scope inspection, deficiencies in the following areas were observed that caused the affected barriers to be considered nonfunctional:
- Imperfections in three penetration seals (2Z43-H037C, 2Z43-H038C, and 2Z43-H177C) located in the 2A Battery Room separating Unit 2 Fire Areas 2004 and 2005
- Imperfections in fire penetration seal 2Z43-H644C located in the U2 Water Analysis Room separating Fire Area 2006 and 0007A
- Imperfections in the grout between two tiers of concrete masonry wall and at the intersection of the walls in the upper northeast corner of the U2 Water Analysis Room separating Fire Areas 2006 and 0007A

"The nonconforming conditions observed for the affected penetrations and fire barriers were identified as affecting both safe shutdown paths for Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity.

"CR 10041392, CR 10041394, and CR 10041397"

The NRC Resident Inspector will be notified. Notified R2DO (Shaeffer)

* * * UPDATE FROM JOHN MITCHELL TO HOWIE CROUCH AT 1619 EDT ON 3/17/15 * * *

"During an expanded scope inspection, a fire penetration seal was observed to contain imperfections that did not meet acceptance criteria. Penetration seal 1Z43H542C is located between the U1 Corridor, Fire Area 0001, and the Unit 1 AC Inverter Room, Fire Area 1008, in the Unit 1 Control Building.

"The nonconforming issue observed on the affected penetration was identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until all associated non-functional fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The extent of condition inspection activity is continuing and this, and any subsequent similar condition(s) that meets the reporting requirements, will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity.

"CR 10041766"

The licensee notified the NRC Resident Inspector. Notified R2DO (Desai).

* * * UPDATE FROM GUY GRIFFIS TO HOWIE CROUCH AT 1648 EDT ON 3/18/15 * * *

"During an expanded scope inspection, deficiencies in the following areas were observed that caused the affected barriers to be considered nonfunctional:

- Gap in the concrete masonry wall at penetration seal 1Z43-H547C located between the Unit 1 AC Inverter Room (Fire Area 1008) and the Unit 1 Corridor (Fire Area 0001)
- Gap in the annulus around the 2 inch continuous run penetration seal located between the Unit 1 AC Inverter Room (Fire Area 1008) and the Unit 1 Corridor (Fire Area 0001)
- Gap in penetration seal 1Z43-H059C located between the Unit 1 AC Inverter Room (Fire Area 1008) and the Unit 1 Corridor (Fire Area 0001)

"The nonconforming conditions observed for the affected penetrations and barrier were identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity.

"CR 10042532; CR 10042530; CR 10042526"

The licensee has notified the NRC Resident Inspector. Notified R2DO (Desai).

* * * UPDATE FROM JOHN MITCHELL TO DANIEL MILLS AT 1814 EDT ON 3/31/15 * * *

"During an expanded scope inspection, a fire wall was observed to contain a gap behind a 3 inch square plate attached to the thru-bolt anchor that did not meet acceptance criteria and caused the affected barrier to be considered nonfunctional. The affected fire barrier is located between the U2 RPS MG Set Room (Fire Area 2013) and the U2 Annunciator Room (Fire Area 2015).

"The nonconforming issue observed on the affected fire barrier was identified as affecting both safe shutdown paths for Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until all associated non-functional fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The extent of condition inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity.

"CR 10048449"

The licensee will notify the NRC Resident Inspector.

Notified R2DO (Walker).

To top of page
!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor Event Number: 50807
Facility: TURKEY POINT
Region: 2 State: FL
Unit: [ ] [4] [ ]
RX Type: [3] W-3-LP,[4] W-3-LP
NRC Notified By: JAY VAN HULZEN
HQ OPS Officer: JEFF ROTTON
Notification Date: 02/11/2015
Notification Time: 01:03 [ET]
Event Date: 02/10/2015
Event Time: 17:50 [EST]
Last Update Date: 03/31/2015
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
Person (Organization):
REBECCA NEASE (R2DO)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
4 N Y 100 Power Operation 100 Power Operation

Event Text

HIGH HEAD SAFETY INJECTION INOPERABLE DUE TO MISSING PIPING SUPPORT

"This is a non-emergency 8 hour report in accordance with 10 CFR 50.72(b)(3)(ii)(B).

"At 1750 [EST] hours on 2/10/15, Unit 4 entered Technical Specification 3.0.3 due to missing tubing supports identified for two separate high point vent lines. This condition is unanalyzed and potentially rendered the cold leg High Head Safety Injection flow path inoperable. Upon discovery, the vent line root isolation valves were closed and Technical Specification 3.0.3 was exited at 1805. Investigation has been initiated to determine cause."

The licensee has notified the NRC Resident Inspector.

* * * UPDATE AT 1250 EDT ON 03/31/15 FROM ERIC JUERGENS TO S. SANDIN * * *

The licensee is retracting this report based on the following:

"On 2/11/2015 at 0103 EST, Event Notification 50807 reported to the Nuclear Regulatory Commission Operations Center (NRCOC) the potential inoperability of the Unit 4 cold leg High Head Safety Injection (HHSI) piping due to missing tubing supports on two separate high point vent lines.

"Subsequent analysis has determined that the Unit 4 HHSI cold leg injection flow path to the reactor coolant system (RCS) remained operable with the missing vent line tubing supports and its safety related function was not affected.

"The Unit 4 HHSI system discharge flow path to the RCS had been operable with the missing vent line tubing supports, Technical Specification (TS) requirements were met, and entry into TS 3.0.3 was not required. The HHSI system remained capable of fulfilling the safety function to mitigate the consequences of an accident on Unit 4. Therefore, the immediate notification to the NRCOC on 2/11/2015 at 0103 EST in accordance with 10 CFR 50.72(b)(3)(ii)(B) is hereby retracted."

The licensee informed the NRC Resident Inspector. Notified R2DO (Walker).

To top of page
Agreement State Event Number: 50919
Rep Org: LOUISIANA RADIATION PROTECTION DIV
Licensee: BOISE PACKING AND NEWSPRINT LLC
Region: 4
City: DeRIDDER State: LA
County:
License #: LA-2873-L01,
Agreement: Y
Docket:
NRC Notified By: JOE NOBLE
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 03/24/2015
Notification Time: 15:20 [ET]
Event Date: 02/26/2015
Event Time: 13:00 [CDT]
Last Update Date: 03/24/2015
Emergency Class: NON EMERGENCY
10 CFR Section:
AGREEMENT STATE
Person (Organization):
VINCENT GADDY (R4DO)
NMSS_EVENTS_NOTIFIC (EMAI)

Event Text

AGREEMENT STATE REPORT - MISSING FIXED GAUGE SHUTTER

The following report was received via e-mail:

"On 02/26/2015, the RSO for Boise Cascade called in a preliminary report [to the Louisiana Department of Environmental Quality] about a shutter missing on a gauge to be 'locked out' during a 24 hour turn-a-round. The shutter is a manual sliding port cover that has to be removed when the gauge is used on the process. The removed shutter is stored by placing it on an adjacent surface until needed. Vibrations on the process had caused the port cover to fall approximately 50 ft. below the storage locations. However, this time the cover could not be located and the gauge could not be locked out. The gauge remained on the process until it could be repaired.

"On 02/26/2015, a replacement shutter/port cover was ordered from Thermo Measuretech. The shutter was delivered on 02/27/2015 and installed the same day. There was no radiation exposure risk to the public or workers. The gauge is installed on a 50 ft. elevation and the unshielded radiation field is approximately 0.3 mR/hr at 1 ft. from the surface of the device.

"The gauge was a Texas Nuclear Device, TN 5192, s/n B3421 containing approximately 100 mCi of Cs-137 when installed during the mid-1980s.

"The Department [Louisiana Department of Environmental Quality] considers this item closed and the records will be reviewed during the next inspection."

Louisiana Event Report ID No.: LA 15-0005, T162439

To top of page
Agreement State Event Number: 50920
Rep Org: FLORIDA BUREAU OF RADIATION CONTROL
Licensee: CARDINAL HEALTH
Region: 1
City: TAMPA State: FL
County:
License #: 3453-13
Agreement: Y
Docket:
NRC Notified By: KELLIE ANDERSON
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 03/24/2015
Notification Time: 16:53 [ET]
Event Date: 03/01/2015
Event Time: [EDT]
Last Update Date: 03/25/2015
Emergency Class: NON EMERGENCY
10 CFR Section:
AGREEMENT STATE
Person (Organization):
TODD JACKSON (R1DO)
NMSS_EVENTS_NOTIFIC (EMAI)
MARISSA BAILEY (NMSS)

Event Text

AGREEMENT STATE REPORT - RADIATION TECHNICIAN POTENTIAL OVEREXPOSURE

The following information was obtained from the State of Florida via email:

"An employee of Cardinal Health had a dosimeter reading of 140 REM. The employee routinely wears one whole-body badge and two ring dosimeters assigned to him. These findings are for the wear period of 2/16/2015-3/1/2015. The whole body badge had a reported dose of 140884 mRem DDE and 241488 mRem SDE. [Cardinal Health] stated that the individual didn't have any reportable readings from their rings badges for this wear period. The individual is showing no symptoms of overexposure and has been removed from handling radioactive material as a safety precaution. It is believed that the badge may have become contaminated therefore distorting the correct exposure reading. Cardinal Health is reportedly conducting an investigation to find the cause and extent of this incident. Pending the Landauer report and some additional information, an investigator will be assigned to inspect their laboratory for safety and confirm Cardinal Health's investigative conclusions."

Florida Incident Number: FL15-023

To top of page
Power Reactor Event Number: 50943
Facility: DUANE ARNOLD
Region: 3 State: IA
Unit: [1] [ ] [ ]
RX Type: [1] GE-4
NRC Notified By: HANS OLSON
HQ OPS Officer: JEFF HERRERA
Notification Date: 03/31/2015
Notification Time: 18:29 [ET]
Event Date: 03/31/2015
Event Time: 15:09 [CDT]
Last Update Date: 03/31/2015
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
Person (Organization):
ROBERT DALEY (R3DO)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation

Event Text

UNANALYZED CONDITION DUE TO DEGRADED TORUS COATING

"The issue described in this report was addressed during the station's most recent refueling and maintenance outage in October of 2014 and no longer exists.

"During an inspection of Suppression Pool (torus) during the October 2014 outage, degradation of the torus coating was discovered. Some of the coating had become delaminated. NextEra Energy DAEC [Duane Arnold Energy Center] took immediate action to restore the coating to within design parameters during the refueling outage and the degraded condition no longer exists. Extensive analysis was performed to determine effect of the delaminated material. Upon completion of this investigation, NextEra Energy DAEC has determined an unanalyzed condition existed as a result of the coating degradation and is reporting the condition under 10 CFR 50.72(b)(3)(ii)(B).

"A root cause evaluation has been performed to determine causes and corrective actions.

"The NRC Resident Inspector has been notified."

Page Last Reviewed/Updated Saturday, February 01, 2020