Event Notification Report for April 10, 2006
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
04/09/2006 - 04/10/2006
EVENT NUMBERS
42488424904248642487
Power Reactor
Event Number: 42488
Facility: BRUNSWICK
Region: 2 State: NC
Unit: [1] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: DAVE JESTER
HQ OPS Officer: STEVE SANDIN
Region: 2 State: NC
Unit: [1] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: DAVE JESTER
HQ OPS Officer: STEVE SANDIN
Notification Date: 04/10/2006
Notification Time: 23:33 [ET]
Event Date: 04/10/2006
Event Time: 16:30 [EDT]
Last Update Date: 04/10/2006
Notification Time: 23:33 [ET]
Event Date: 04/10/2006
Event Time: 16:30 [EDT]
Last Update Date: 04/10/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
BRIAN BONSER (R2)
BRIAN BONSER (R2)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 95 | Power Operation | 95 | Power Operation |
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
CONTROL ROOM EMERGENCY VENTILATION SYSTEM DECLARED INOPERABLE DUE TO DESIGN DEFICIENCY
"EVENT DESCRIPTION:
"At 1630 on 4/10/06, plant personnel identified a potential failure mode of the recently modified chlorine detectors. The failure mode has the potential to render the Control Room Emergency Ventilation (CREV) system inoperable following power restoration after a LOOP/LOCA event. Due to this design deficiency, the CREV system was declared inoperable per LCO 3.7.3, Control Room Emergency Ventilation System, which placed both units in LCO 3.7.3 Condition B. Required Actions for this Condition are to be in Hot Shutdown in 12 hours and in Cold Shutdown in 36 hours. In addition TRM [Technical Reference Manual] 3.18, CREV Smoke Protection Mode, is being entered for Condition B. The Plan required by TRM 3.18 Condition B is to remove the Chlorine Tank Car from site AND to disable the Chlorine detectors to prevent them from actuating. These actions were completed at 2100 on 4/10/06 and the CREV System Rad/Smoke Mode was restored to operable.
"This situation has been evaluated as reportable to the NRC within 8 hours per 0OI-01.07, Attachment 1. The criteria is 10CFR50.72 (b)(3)(v)(D). The condition at the time of discovery that could have prevented the fulfillment of safety function of structures or systems that are needed to mitigate the consequences of an accident. (Item # 3.4.4 of 0OI-01.07 Attachment1).
"INITIAL SAFETY SIGNIFICANCE EVALUATION:
"The initial safety significance of this event is considered minimal due to the immediate implementation of Tech Spec and TRM required actions following discovery of the design deficiency.
"CORRECTIVE ACTIONS:
"The Plan required by TRM 3.18 Condition B is to remove the Chlorine Tank Car from site AND to disable the Chlorine detectors to prevent them from actuating. These actions were completed at 2100 on 4/10106 and the CREV System Rad/Smoke Mode was restored to operable. The Chlorine Tank Car will remain off-site and the Chlorine detectors will remain disabled until the design deficiency is corrected."
The deficiency with the chlorine detectors which had been modified in February 2006 was identified using the plant simulator.
The licensee informed the NRC Resident Inspector.
"EVENT DESCRIPTION:
"At 1630 on 4/10/06, plant personnel identified a potential failure mode of the recently modified chlorine detectors. The failure mode has the potential to render the Control Room Emergency Ventilation (CREV) system inoperable following power restoration after a LOOP/LOCA event. Due to this design deficiency, the CREV system was declared inoperable per LCO 3.7.3, Control Room Emergency Ventilation System, which placed both units in LCO 3.7.3 Condition B. Required Actions for this Condition are to be in Hot Shutdown in 12 hours and in Cold Shutdown in 36 hours. In addition TRM [Technical Reference Manual] 3.18, CREV Smoke Protection Mode, is being entered for Condition B. The Plan required by TRM 3.18 Condition B is to remove the Chlorine Tank Car from site AND to disable the Chlorine detectors to prevent them from actuating. These actions were completed at 2100 on 4/10/06 and the CREV System Rad/Smoke Mode was restored to operable.
"This situation has been evaluated as reportable to the NRC within 8 hours per 0OI-01.07, Attachment 1. The criteria is 10CFR50.72 (b)(3)(v)(D). The condition at the time of discovery that could have prevented the fulfillment of safety function of structures or systems that are needed to mitigate the consequences of an accident. (Item # 3.4.4 of 0OI-01.07 Attachment1).
"INITIAL SAFETY SIGNIFICANCE EVALUATION:
"The initial safety significance of this event is considered minimal due to the immediate implementation of Tech Spec and TRM required actions following discovery of the design deficiency.
"CORRECTIVE ACTIONS:
"The Plan required by TRM 3.18 Condition B is to remove the Chlorine Tank Car from site AND to disable the Chlorine detectors to prevent them from actuating. These actions were completed at 2100 on 4/10106 and the CREV System Rad/Smoke Mode was restored to operable. The Chlorine Tank Car will remain off-site and the Chlorine detectors will remain disabled until the design deficiency is corrected."
The deficiency with the chlorine detectors which had been modified in February 2006 was identified using the plant simulator.
The licensee informed the NRC Resident Inspector.
Power Reactor
Event Number: 42490
Facility: HATCH
Region: 2 State: GA
Unit: [1] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: ALAN WOLFE
HQ OPS Officer: BILL GOTT
Region: 2 State: GA
Unit: [1] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: ALAN WOLFE
HQ OPS Officer: BILL GOTT
Notification Date: 04/11/2006
Notification Time: 11:06 [ET]
Event Date: 04/10/2006
Event Time: 16:25 [EDT]
Last Update Date: 04/11/2006
Notification Time: 11:06 [ET]
Event Date: 04/10/2006
Event Time: 16:25 [EDT]
Last Update Date: 04/11/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
26.73 - FITNESS FOR DUTY
10 CFR Section:
26.73 - FITNESS FOR DUTY
Person (Organization):
BRIAN BONSER (R2)
BRIAN BONSER (R2)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
FITNESS FOR DUTY
A contract employee supervisor had a confirmed positive for illegal drugs during a random fitness-for-duty test. The employee's access to the plant has been terminated. Contact the Headquarters Operations Officer for additional details.
The licensee notified the NRC Resident Inspector.
A contract employee supervisor had a confirmed positive for illegal drugs during a random fitness-for-duty test. The employee's access to the plant has been terminated. Contact the Headquarters Operations Officer for additional details.
The licensee notified the NRC Resident Inspector.
Power Reactor
Event Number: 42486
Facility: FT CALHOUN
Region: 4 State: NE
Unit: [1] [] []
RX Type: [1] CE
NRC Notified By: KEN KINGSTON
HQ OPS Officer: JOHN KNOKE
Region: 4 State: NE
Unit: [1] [] []
RX Type: [1] CE
NRC Notified By: KEN KINGSTON
HQ OPS Officer: JOHN KNOKE
Notification Date: 04/10/2006
Notification Time: 14:24 [ET]
Event Date: 04/10/2006
Event Time: 10:55 [CDT]
Last Update Date: 04/10/2006
Notification Time: 14:24 [ET]
Event Date: 04/10/2006
Event Time: 10:55 [CDT]
Last Update Date: 04/10/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(i) - PLANT S/D REQD BY TS
10 CFR Section:
50.72(b)(2)(i) - PLANT S/D REQD BY TS
Person (Organization):
TROY PRUETT (R4)
TROY PRUETT (R4)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 96 | Power Operation |
PERSONNEL AIR LOCK DOOR EQUALIZING VALVE LEAKING BY
"It was reported to the Shift Manager this morning in Condition Report 200601444 that the inner Personnel Air Lock (PAL) door equalizing valve was leaking by. Although the condition was reported this morning, it was actually discovered following a containment entry on Friday, April 7, 2006. Fort Calhoun Station Technical Specification 2.6(1)b,(ii) states that with the PAL inoperable, except as the result of an inoperable air lock door, maintain at least one air lock door closed; restore the inoperable air lock to operable status within 24 hours or be in at least hot shutdown within the next six hours and in cold shutdown within the following thirty hours. The leak by past the inner air lock door is applicable to this Fort Calhoun Station Technical Specification. The Shift Manager determined at 10:00 CDT that Fort Calhoun was in excess of the Limiting Conditions for Operation of Technical Specification 2.6(1)b(ii) and entered Technical Specification 2.0.1 (Motherhood) which requires the unit to be placed in at least hot shutdown within six hours, in at least subcritical and less than 300°F within the next six hours, and at least cold shutdown within the following thirty hours, unless corrective measures are completed that permit operation under the permissible action requirements for the specified time interval as measured from initial discovery or until the reactor is placed in an operating mode in which the specification is not applicable.
"At 10:55 CDT on April 10, 2006, a shutdown was commenced and negative reactivity was introduced to the core. At the same time, machinists were dispatched to troubleshoot the situation and found a loose collar on the valve assembly that was preventing full closure of the valve. The collar was adjusted and post-maintenance testing was completed. The inner PAL door equalizing valve was declared operable at 13:10 CDT. Technical Specifications 2.0.1 and 2.6(1)b(ii) were exited, the unit shutdown was ceased at a power level of 96.04% and preparations are being made to return the unit to full power."
The licensee notified the NRC Resident Inspector.
"It was reported to the Shift Manager this morning in Condition Report 200601444 that the inner Personnel Air Lock (PAL) door equalizing valve was leaking by. Although the condition was reported this morning, it was actually discovered following a containment entry on Friday, April 7, 2006. Fort Calhoun Station Technical Specification 2.6(1)b,(ii) states that with the PAL inoperable, except as the result of an inoperable air lock door, maintain at least one air lock door closed; restore the inoperable air lock to operable status within 24 hours or be in at least hot shutdown within the next six hours and in cold shutdown within the following thirty hours. The leak by past the inner air lock door is applicable to this Fort Calhoun Station Technical Specification. The Shift Manager determined at 10:00 CDT that Fort Calhoun was in excess of the Limiting Conditions for Operation of Technical Specification 2.6(1)b(ii) and entered Technical Specification 2.0.1 (Motherhood) which requires the unit to be placed in at least hot shutdown within six hours, in at least subcritical and less than 300°F within the next six hours, and at least cold shutdown within the following thirty hours, unless corrective measures are completed that permit operation under the permissible action requirements for the specified time interval as measured from initial discovery or until the reactor is placed in an operating mode in which the specification is not applicable.
"At 10:55 CDT on April 10, 2006, a shutdown was commenced and negative reactivity was introduced to the core. At the same time, machinists were dispatched to troubleshoot the situation and found a loose collar on the valve assembly that was preventing full closure of the valve. The collar was adjusted and post-maintenance testing was completed. The inner PAL door equalizing valve was declared operable at 13:10 CDT. Technical Specifications 2.0.1 and 2.6(1)b(ii) were exited, the unit shutdown was ceased at a power level of 96.04% and preparations are being made to return the unit to full power."
The licensee notified the NRC Resident Inspector.
Power Reactor
Event Number: 42487
Facility: PALO VERDE
Region: 4 State: AZ
Unit: [] [2] []
RX Type: [1] CE,[2] CE,[3] CE
NRC Notified By: ALLAN BRIESE
HQ OPS Officer: STEVE SANDIN
Region: 4 State: AZ
Unit: [] [2] []
RX Type: [1] CE,[2] CE,[3] CE
NRC Notified By: ALLAN BRIESE
HQ OPS Officer: STEVE SANDIN
Notification Date: 04/10/2006
Notification Time: 15:39 [ET]
Event Date: 04/10/2006
Event Time: 12:33 [MST]
Last Update Date: 04/10/2006
Notification Time: 15:39 [ET]
Event Date: 04/10/2006
Event Time: 12:33 [MST]
Last Update Date: 04/10/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(i) - PLANT S/D REQD BY TS
10 CFR Section:
50.72(b)(2)(i) - PLANT S/D REQD BY TS
Person (Organization):
TROY PRUETT (R4)
TROY PRUETT (R4)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | N | Y | 91 | Power Operation | 88 | Power Operation |
UNIT 2 ENTERED A TS REQUIRED SHUTDOWN DUE TO INOPERABLE AUXILIARY FEEDWATER PUMPS
"The following event description is based on information currently available. If through subsequent reviews of this event, additional information is identified that is pertinent to this event or alters the information being provided at this time, a follow-up notification will be made via the ENS or under the reporting requirements of 10CFR50.73.
"On April 10. 2006, at approximately 12:33 hours Mountain Standard Time (MST), Palo Verde Nuclear Generating Station (PVNGS) Unit 2 commenced a reactor shutdown required by Technical Specification [TS] 3.7.5 Condition C. Limiting Condition for Operability (LCO) 3.7.5 requires three AFW trains to be Operable. Condition A of this LCO provides allowance for one steam supply to the turbine driven AFW to be inoperable for a 7 day period. If the inoperable SGAUV138A valve is not restored to an operable condition within 7 days, Unit 2 will be required to shutdown to Mode 3 in 6 hours and to Mode 4 in 12 hours, starting at 10:41 MST on April 10, 2006.
"The event did not result in the release of radioactivity to the environment and did not adversely affect the safe operation of the plant or health and safety of the public.
"The NRC Resident Inspector has been notified and is present in the control room."
"The following event description is based on information currently available. If through subsequent reviews of this event, additional information is identified that is pertinent to this event or alters the information being provided at this time, a follow-up notification will be made via the ENS or under the reporting requirements of 10CFR50.73.
"On April 10. 2006, at approximately 12:33 hours Mountain Standard Time (MST), Palo Verde Nuclear Generating Station (PVNGS) Unit 2 commenced a reactor shutdown required by Technical Specification [TS] 3.7.5 Condition C. Limiting Condition for Operability (LCO) 3.7.5 requires three AFW trains to be Operable. Condition A of this LCO provides allowance for one steam supply to the turbine driven AFW to be inoperable for a 7 day period. If the inoperable SGAUV138A valve is not restored to an operable condition within 7 days, Unit 2 will be required to shutdown to Mode 3 in 6 hours and to Mode 4 in 12 hours, starting at 10:41 MST on April 10, 2006.
"The event did not result in the release of radioactivity to the environment and did not adversely affect the safe operation of the plant or health and safety of the public.
"The NRC Resident Inspector has been notified and is present in the control room."