Skip to main content

Event Notification Report for December 17, 2005

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
12/16/2005 - 12/17/2005

EVENT NUMBERS
42211
Power Reactor
Event Number: 42211
Facility: MCGUIRE
Region: 2     State: NC
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: TONY COOK
HQ OPS Officer: PETE SNYDER
Notification Date: 12/17/2005
Notification Time: 03:45 [ET]
Event Date: 12/17/2005
Event Time: 03:11 [EST]
Last Update Date: 12/17/2005
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
THOMAS DECKER (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 100 Power Operation 0 Hot Standby
Event Text
AUTOMATIC REACTOR TRIP FROM FULL POWER DUE TO A FAILED FEED FLOW CHANNEL

"'A' Steam Generator hi/hi level caused a turbine trip which in turn caused a Unit 1 reactor trip. The hi/hi steam generator level also caused both feedwater pumps to trip which caused the auxiliary feedwater pumps to auto-start. The hi/hi level also caused a feedwater isolation. Appropriate emergency procedures have been implemented and the plant is currently stable."

All control rods fully inserted on the trip. Offsite power is available and powering safety related buses. The emergency diesel generators are available if required. There are no known primary to secondary leaks in the steam generators.

The licensee will notify the NRC Resident Inspector.