Skip to main content

Alert

Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for August 13, 2003








                    U.S. Nuclear Regulatory Commission

                              Operations Center



                              Event Reports For

                           08/12/2003 - 08/13/2003



                              ** EVENT NUMBERS **



40019  40057  



+------------------------------------------------------------------------------+

|General Information or Other                     |Event Number:   40019       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  CALIFORNIA RADIATION CONTROL PRGM    |NOTIFICATION DATE: 07/25/2003|

|LICENSEE:  DELLAVALLEY LABORATORIES             |NOTIFICATION TIME: 13:00[EDT]|

|    CITY:  SACRAMENTO               REGION:  4  |EVENT DATE:        07/25/2003|

|  COUNTY:                            STATE:  CA |EVENT TIME:        09:00[PDT]|

|LICENSE#:  3194-10               AGREEMENT:  Y  |LAST UPDATE DATE:  08/13/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |TROY PRUETT          R4      |

|                                                |FRED BROWN           NMSS    |

+------------------------------------------------+                             |

| NRC NOTIFIED BY:  KENT PREDERGAST              |                             |

|  HQ OPS OFFICER:  STEVE SANDIN                 |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|NAGR                     AGREEMENT STATE        |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| AGREEMENT STATE REPORT INVOLVING A STOLEN TROXLER GAUGE                      |

|                                                                              |

| "[The licensee] got in late from work, and failed to take the gauge to       |

| storage location but instead left the gauge in the back of his pickup and    |

| covered it.  The gauge was covered inside the camper shell.  Sometime        |

| between 11 PM on 7/24/03 and 1:00 AM on 7/25/03, the pickup was stolen from  |

| it's parking location.  The Sacramento Police were notified on 7/25/03 and   |

| the licensee will be placing an advertisement in the Sacramento Bee          |

| [newspaper], offering a reward for the stolen gauge.                         |

|                                                                              |

| "The Stolen gauge was a CPN 131, Model 503 DR, serial number H35126508       |

| containing 50 millicuries of Americium  241 Beryllium."                      |

|                                                                              |

| *****UPDATE 8/12/03 AT 12:46 GREGER TO LAURA*****                            |

|                                                                              |

| "The stolen nuclear gauge reported in Event # 030603 [NMED Database number]  |

| was found in a business dumpster in Sacramento, the city in which it was     |

| stolen, on August 3, 2003 by a member of the public. Both the gauge and the  |

| truck in which the gauge was stored overnight (inside a camper shell) was    |

| stolen from a private residence. The truck has not been recovered. The gauge |

| was found inside its protective transportation case. The lock on the         |

| transportation case had been removed, but the gauge remained locked          |

| (radioactive source not exposed). The individual finding the gauge stated he |

| had seen the newspaper ad offering a reward for return of the gauge. The     |

| gauge will be tested for radioactive leakage before being returned to        |

| service. Enforcement action is being taken against the gauge company for     |

| failing to properly store the gauge."                                        |

|                                                                              |

| Notified NMSS (J. Hickey) and R4DO (Phil Harrell).                           |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   40057       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: HOPE CREEK               REGION:  1  |NOTIFICATION DATE: 08/12/2003|

|    UNIT:  [1] [] []                 STATE:  NJ |NOTIFICATION TIME: 16:11[EDT]|

|   RXTYPE: [1] GE-4                             |EVENT DATE:        06/15/2003|

+------------------------------------------------+EVENT TIME:        14:47[EDT]|

| NRC NOTIFIED BY:  ART BREADY                   |LAST UPDATE DATE:  08/12/2003|

|  HQ OPS OFFICER:  ERIC THOMAS                  +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |GLENN MEYER          R1      |

|10 CFR SECTION:                                 |                             |

|AINV 50.73(a)(1)         INVALID SPECIF SYSTEM A|                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|1     N          Y       100      Power Operation  |100      Power Operation  |

|                                                   |                          |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| 10 CFR 50.73 REPORT                                                          |

|                                                                              |

| "The report is being made under 10 CFR 50.73(a)(2)(iv)(A) and is not         |

| considered a Licensee Event Report.                                          |

|                                                                              |

| "During performance of a Surveillance Order, a Reactor Building Ventilation  |

| System isolation was initiated at 14:47 on 6/15/03. The apparent cause of    |

| the isolation was human error due to the incorrect de-energizing and         |

| placement of test leads on the 'B' train component instead of the 'A' train  |

| component as required by procedure. After the 'B' Train Sorrento RM-80       |

| (1SP-RY4856B) was de-energized, the 'A' train detector (1SP-RE-4857A) was    |

| disconnected in accordance with the procedure. When the opposite train       |

| detector was disconnected, the Reactor Building Ventilation System isolation |

| was initiated.                                                               |

|                                                                              |

| "Upon receipt of the Reactor Building Equipment (RBE) isolation, the         |

| following systems isolated:                                                  |

|                                                                              |

| "Torus water cleanup, Drywell (DW) floor and equipment sumps, Drywell Leak   |

| Detection (DLD) sampling skid, Reactor Building Ventilation System (RBVS)    |

| isolated, Radwaste (RW) ventilation isolated, Filtration Recirculation       |

| Ventilation System (FRVS) auto started, B Station Service Water (SSW) pump   |

| and B Station Auxiliary Cooling System (SACS) pump auto started, Primary     |

| Containment Instrument (PCI) gas valves and compressors isolated.            |

|                                                                              |

| "The operating crew entered the procedure for Primary Containment abnormal   |

| condition B. When instrument technicians restored the 'B' RBE radiation      |

| monitor, the operating crew reset PCI Signal in accordance with the          |

| Operating Procedure and restored the systems to normal.                      |

|                                                                              |

| "All safety systems responded to the isolation signal according to design."  |

+------------------------------------------------------------------------------+



                    

Page Last Reviewed/Updated Wednesday, March 24, 2021

Page Last Reviewed/Updated Wednesday, March 24, 2021