Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for August 12, 2003








                    U.S. Nuclear Regulatory Commission

                              Operations Center



                              Event Reports For

                           08/11/2003 - 08/12/2003



                              ** EVENT NUMBERS **



40048  40054  



+------------------------------------------------------------------------------+

|General Information or Other                     |Event Number:   40048       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  SC DIV OF HEALTH & ENV CONTROL       |NOTIFICATION DATE: 08/06/2003|

|LICENSEE:  Medical University of South Carolina |NOTIFICATION TIME: 15:53[EDT]|

|    CITY:  Charleston               REGION:  2  |EVENT DATE:        07/31/2003|

|  COUNTY:                            STATE:  SC |EVENT TIME:        16:00[EDT]|

|LICENSE#:  081                   AGREEMENT:  Y  |LAST UPDATE DATE:  08/06/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |STEPHEN CAHILL       R2      |

|                                                |M. WAYNE HODGES      NMSS    |

+------------------------------------------------+                             |

| NRC NOTIFIED BY:  Melinda Bradshaw             |                             |

|  HQ OPS OFFICER:  ERIC THOMAS                  |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|NAGR                     AGREEMENT STATE        |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| AGREEMENT STATE REPORT - MEDICAL EVENT                                       |

|                                                                              |

| On 7/31/03, at approximately 1600 EDT, an Iotrex I-125 sealed source was     |

| administered to a brachytherapy patient to treat a brain tumor.  The sealed  |

| source contained 325 millicuries of I-125.  On 8/5/03 at 1148 EDT, upon      |

| removal of the sealed source from the patient, the hospital staff noted that |

| the amount of I-125 withdrawn from the patient was only 31.5 millicuries.    |

|                                                                              |

| The source is a liquid that is inserted into a balloon inside the patient's  |

| skull, then removed after a designated amount of time.  On 8/6/03, a         |

| manufacturer's representative from Proxima accompanied hospital staff to     |

| inspect the catheter and balloon that were used during this administration.  |

| The catheter and balloon were visually inspected and tested with a dye for   |

| leaks.  No leaks were apparent during either test.                           |

|                                                                              |

| The licensee did not report any immediate adverse affects on the patient.    |

| The referring physician was informed of this event.                          |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   40054       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: BROWNS FERRY             REGION:  2  |NOTIFICATION DATE: 08/11/2003|

|    UNIT:  [] [2] []                 STATE:  AL |NOTIFICATION TIME: 05:04[EDT]|

|   RXTYPE: [1] GE-4,[2] GE-4,[3] GE-4           |EVENT DATE:        08/10/2003|

+------------------------------------------------+EVENT TIME:        23:31[CDT]|

| NRC NOTIFIED BY:  DAVID TIDWELL                |LAST UPDATE DATE:  08/11/2003|

|  HQ OPS OFFICER:  GERRY WAIG                   +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |STEPHEN CAHILL       R2      |

|10 CFR SECTION:                                 |                             |

|AESF 50.72(b)(3)(iv)(A)  VALID SPECIF SYS ACTUAT|                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|2     N          Y       100      Power Operation  |100      Power Operation  |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| AUTOMATIC START OF EMERGENCY DIESEL GENERATORS DURING BUS TRANSFER FOR       |

| MAINTENANCE                                                                  |

|                                                                              |

| "Unit 1/2 A and B Diesel Generators auto started on Undervoltage while       |

| attempting to transfer Shutdown Bus 1 to Alternate supply, the alternate     |

| supply breaker failed to close, resulting in a momentary undervoltage        |

| condition on the Shutdown Bus and 4160V Shutdown Boards A & B. Shutdown Bus  |

| 1 was reenergized by reclosure of the Normal feeder breaker. The Diesel      |

| Generators did not tie onto the board due to the voltage returned to normal  |

| prior to the DG obtaining rated speed and voltage when the operator reclosed |

| the normal supply breaker. SBGT [Standby Gas Treatment] & CREV [Control Room |

| Emergency Ventilation] auto started and Refuel Zone ventilation isolated due |

| to a failure of Unit 1 Refuel Zone Rad monitor; Unit 2 Reactor Zone          |

| ventilation isolated due to a momentary loss of I & C 'A'.                   |

|                                                                              |

| "This event is reportable as an 8 hour report per 10CFR50.72(b)(3)(iv)(A) as |

| 'Any event or condition that results in valid actuation of any of the        |

| systems listed in (b)(3)(iv)(B), specifically Emergency AC Electrical power  |

| systems, including: Emergency Diesel Generators (EDGs).'                     |

|                                                                              |

| "This is also reportable per 10CFR50.73(a)(2)(iv)(A) for the above           |

| conditions as a 60 day written report."                                      |

|                                                                              |

| The licensee reported that affected ventilation systems and electrical       |

| systems have been returned to a normal configuration with the exception of   |

| the shutdown bus "43 switch" [in normal supply]. All Emergency Diesel        |

| Generators are operable and in standby. Offsite electrical power supply to   |

| the station is in a normal configuration.                                    |

|                                                                              |

| The licensee has notified the NRC Resident Inspector.                        |

+------------------------------------------------------------------------------+





                    