Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for July 10, 2003




                    U.S. Nuclear Regulatory Commission

                              Operations Center



                              Event Reports For

                           07/09/2003 - 07/10/2003



                              ** EVENT NUMBERS **



39978  39979  39985  39986  39987  





+------------------------------------------------------------------------------+

|General Information or Other                     |Event Number:   39978       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  COLORADO DEPT OF HEALTH              |NOTIFICATION DATE: 07/07/2003|

|LICENSEE:                                       |NOTIFICATION TIME: 11:04[EDT]|

|    CITY:  DENVER                   REGION:  4  |EVENT DATE:        07/06/2003|

|  COUNTY:  ARAPAHOE                  STATE:  CO |EVENT TIME:        16:00[MDT]|

|LICENSE#:                        AGREEMENT:  Y  |LAST UPDATE DATE:  07/07/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |KRISS KENNEDY        R4      |

|                                                |MARISSA BAILEY       NMSS    |

+------------------------------------------------+                             |

| NRC NOTIFIED BY:  GREG STASINOS                |                             |

|  HQ OPS OFFICER:  GERRY WAIG                   |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|NAGR                     AGREEMENT STATE        |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| AGREEMENT STATE REPORT - STOLEN ASPHALT CONTENT OVEN                         |

|                                                                              |

| The following is taken from a facsimile sent from the Colorado Department of |

| Health and Environment:                                                      |

|                                                                              |

| On 7/6/03 at 2230 MDT Robin Koons, Colorado State Department of Health and   |

| Environment, was notified by the Arapahoe County Hazmat Response Team of the |

| theft of an asphalt content oven at a construction site located on Highway   |

| 36, mile marker 119 - 20 miles east of Byers, CO. Arapahoe County Hazmat     |

| responded to initiate an investigation into the incident. Initial            |

| information and indications pointed to a moisture density gauge being        |

| stolen. The moisture density gauge has been found and accounted for. The     |

| asphalt content oven contains a 100 milliCurie (plus or minus 10%) Americium |

| 241:Be source. The oven is used to test for oily content in asphalt during   |

| road construction process. The area is considered a crime scene and has been |

| secured.                                                                     |

|                                                                              |

| Colorado Case Number: 2003-372                                               |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|General Information or Other                     |Event Number:   39979       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  TENNESSEE DIV OF RAD HEALTH          |NOTIFICATION DATE: 07/07/2003|

|LICENSEE:  Radiological Assistance, Consulting, |NOTIFICATION TIME: 13:09[EDT]|

|    CITY:  Memphis                  REGION:  2  |EVENT DATE:        06/26/2003|

|  COUNTY:                            STATE:  TN |EVENT TIME:        18:00[EDT]|

|LICENSE#:  R-79266               AGREEMENT:  Y  |LAST UPDATE DATE:  07/07/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |JOEL MUNDAY          R2      |

|                                                |THOMAS ESSIG         NMSS    |

+------------------------------------------------+                             |

| NRC NOTIFIED BY:  Debra Shults                 |                             |

|  HQ OPS OFFICER:  ERIC THOMAS                  |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|NAGR                     AGREEMENT STATE        |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| AGREEMENT STATE REPORT                                                       |

|                                                                              |

| "The [Tennessee Division of Radiological Health] was notified on Monday,     |

| June 30, 2003 by three employees of RACE [Radiological Assistance,           |

| Consulting, & Engineering] of a contamination event that occurred on June    |

| 26, 2003. The employees were sorting and segregating materials contaminated  |

| with low-level radioactive waste. The waste had been delivered to RACE by a  |

| waste broker. The employees ended the shift and frisked for personnel        |

| contamination prior to exiting the building. Several employees alarmed the   |

| PCM and were decontaminated prior to release. One employee had high levels   |

| of skin contamination and underwent several hours of decontamination.        |

| Preliminary results from urinalyses are negative according to the licensee.  |

| The employees are undergoing whole body counts today. The shop area was      |

| closed for routine business and decontaminated.  It was opened on Sunday,    |

| June 29, 2003. DRH staff from Memphis and Nashville visited the site to      |

| begin the investigation. Staff continue to investigate and will continue to  |

| keep the NRC informed of the status of our investigation. This incident is   |

| reportable under 1200-2-5.141 (2)(c)1(i) of 'State Regulations for           |

| Protection Against Radiation.'"                                              |

|                                                                              |

| Tennessee Report ID:  TN-03-100                                              |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39985       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: COMANCHE PEAK            REGION:  4  |NOTIFICATION DATE: 07/09/2003|

|    UNIT:  [] [2] []                 STATE:  TX |NOTIFICATION TIME: 03:05[EDT]|

|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        07/09/2003|

+------------------------------------------------+EVENT TIME:        01:09[CDT]|

| NRC NOTIFIED BY:  LES MILLER                   |LAST UPDATE DATE:  07/09/2003|

|  HQ OPS OFFICER:  HOWIE CROUCH                 +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |KRISS KENNEDY        R4      |

|10 CFR SECTION:                                 |                             |

|ARPS 50.72(b)(2)(iv)(B)  RPS ACTUATION - CRITICA|                             |

|AESF 50.72(b)(3)(iv)(A)  VALID SPECIF SYS ACTUAT|                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|2     A/R        Y       99       Power Operation  |0        Hot Standby      |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| AUTOMATIC REACTOR TRIP DUE TO REACTOR COOLANT PUMP BREAKER OPENING WITH      |

| INITIATION OF AUXILIARY FEEDWATER SYSTEM AFTER THE TRIP                      |

|                                                                              |

| "At 0109 hrs. CDT, Unit 2 reactor tripped due to opening of RCP [Reactor     |

| Coolant Pump] 2-04 breaker resulting in "Rx >48% 1/4 loop flow low trip".    |

| Cause of the breaker opening is unknown and under investigation.  All        |

| systems responded as required.  Auxiliary Feed Water auto-start occurred due |

| to steam generator shrink, both motor driver AFW pumps and Turbine Driven    |

| AFW pump started (ESF)."                                                     |

|                                                                              |

| All rods inserted into the core during the trip.  The electrical grid is     |

| stable.  There were no power-operated or manual relief valve lifts during    |

| the transient.  The other unit was not affected by the transient.  Decay     |

| heat is being removed via steam generator blowdown and AFW.  The plant is    |

| maintaining at NOP/NOT in mode 3 until the cause of the breaker trip is      |

| known and repaired.  Pressurizer pressure control is in automatic.  There is |

| no identified primary-to-secondary leakage.                                  |

|                                                                              |

| The licensee has informed the NRC Resident Inspector.                        |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Hospital                                         |Event Number:   39986       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  UNIVERSITY OF WISCONSIN - MADISON    |NOTIFICATION DATE: 07/09/2003|

|LICENSEE:  UNIVERSITY OF WISCONSIN              |NOTIFICATION TIME: 18:07[EDT]|

|    CITY:  Madison                  REGION:  3  |EVENT DATE:        07/09/2003|

|  COUNTY:  Dane                      STATE:  WI |EVENT TIME:        13:00[CDT]|

|LICENSE#:  48-09843-18           AGREEMENT:  N  |LAST UPDATE DATE:  07/09/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |CHRIS MILLER         R3      |

|                                                |SUSAN FRANT          NMSS    |

+------------------------------------------------+                             |

| NRC NOTIFIED BY:  RONALD BRESELL               |                             |

|  HQ OPS OFFICER:  ERIC THOMAS                  |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|LDIF 35.3045(a)(1)       DOSE <> PRESCRIBED DOSA|                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| MEDICAL EVENT                                                                |

|                                                                              |

| At 1300 CDT on 7/9/03, an underadministration of Yttrium-90 (Y-90) occurred  |

| at the University of Wisconsin Hospital in Madison, WI.  A patient being     |

| treated for secondary liver cancer was to receive a dose of approximately 50 |

| millicuries of Y-90.  The dose was delivered using a SIRTECH (Selective      |

| Radiation Implantation) to pulse microspheres of Y-90 from a vial into the   |

| liver via a needle and catheter.                                             |

|                                                                              |

| During the procedure, the SIRTECH did not develop enough pressure to deliver |

| the entire dose to the patient, and only about 8 percent of the Y-90 was     |

| delivered to the patient (between 3-4 millicuries).  The remainder of the    |

| Y-90 microspheres were contained within the vial.                            |

|                                                                              |

| There was no adverse affect on the patient due to this underadministration,  |

| and the licensee is still investigating how to prevent a re-currence.  The   |

| patient was notified of the underadministration.                             |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39987       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: DRESDEN                  REGION:  3  |NOTIFICATION DATE: 07/10/2003|

|    UNIT:  [] [2] [3]                STATE:  IL |NOTIFICATION TIME: 04:03[EDT]|

|   RXTYPE: [1] GE-1,[2] GE-3,[3] GE-3           |EVENT DATE:        07/09/2003|

+------------------------------------------------+EVENT TIME:        22:00[CDT]|

| NRC NOTIFIED BY:  RON WIGGINS                  |LAST UPDATE DATE:  07/10/2003|

|  HQ OPS OFFICER:  HOWIE CROUCH                 +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |CHRIS MILLER         R3      |

|10 CFR SECTION:                                 |                             |

|AIND 50.72(b)(3)(v)(D)   ACCIDENT MITIGATION    |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|2     N          Y       99       Power Operation  |99       Power Operation  |

|3     N          Y       99       Power Operation  |99       Power Operation  |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| CONTROL ROOM HVAC REFRIGERATION AND CONDENSING UNIT TRIPPED DURING           |

| SURVEILLANCE TEST                                                            |

|                                                                              |

| "At 2200 hours on July 9, 2003, the B Control Room HVAC Refrigeration and    |

| Condensing Unit (RCU) tripped and would not stay running during surveillance |

| testing.  The RCU is a single train system and therefore is reportable per   |

| SAF 1.8 and LS-AA-1400, Event Reporting Guidelines Section 3.2.7.  The RCU   |

| is required to operate during a design basis accident to remove heat from    |

| the Main Control Room.  The Air Filtration Unit (AFU) of CREVS [Control Room |

| Emergency Ventilation System] remains operable.  This places both units in a |

| 30 day LCORA [Limiting Condition for Operation Required Action] per Tech     |

| Spec 3.7.5 Required Action A.1."                                             |

|                                                                              |

| The licensee has notified the NRC Resident Inspector.                        |

+------------------------------------------------------------------------------+