Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for April 30, 2003








                    U.S. Nuclear Regulatory Commission

                              Operations Center



                              Event Reports For

                           04/29/2003 - 04/30/2003



                              ** EVENT NUMBERS **



39795  39798  39802  39807  39808  39809  39810  



+------------------------------------------------------------------------------+

|General Information or Other                     |Event Number:   39795       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  OHIO BUREAU OF RADIATION PROTECTION  |NOTIFICATION DATE: 04/24/2003|

|LICENSEE:  REPUBLIC ENGINEERED PRODUCTS LLC     |NOTIFICATION TIME: 15:59[EDT]|

|    CITY:  LORAIN                   REGION:  3  |EVENT DATE:        04/03/2003|

|  COUNTY:                            STATE:  OH |EVENT TIME:             [EDT]|

|LICENSE#:  OH31201480007         AGREEMENT:  Y  |LAST UPDATE DATE:  04/24/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |MONTE PHILLIPS       R3      |

|                                                |TOM ESSIG            NMSS    |

+------------------------------------------------+                             |

| NRC NOTIFIED BY:  SNEE                         |                             |

|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|NAGR                     AGREEMENT STATE        |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| REPORT OF EXPOSURE OF LICENSEE EMPLOYEES WAS MADE TO THE STATE               |

|                                                                              |

| The licensee reported the exposure of licensee employees to radiation from a |

| TN Technologies model 5174 (serial # B103) fixed gauge containing a 2 curie  |

| Cs-137 sealed source.  The gauge fell approximately 6 feet from its location |

| on a coke hopper on approximately 04/03/03.  The welds which attached the    |

| gauge anchoring bolts appear to have failed.  The gauge had been in place    |

| since 1992.  The gauge fell with the shutter open onto the first landing of  |

| the skip pit area.  The gauge went un-noticed for a week until April 11 @    |

| 1300 when maintenance workers were called to move what was thought to be a   |

| motor (all labels and markings on the gauge were unreadable).  The workers   |

| spent approximately 1.5 hours rigging and moving the gauge before an         |

| individual recognized the gauge and secured the area.   A contractor,        |

| Radiometrics, was then called in to secure the gauge.  The Ohio department   |

| of Health was called concerning the incident on April 17 @1400.  An on-site  |

| investigation was done and a dose assessment of affected personnel is in     |

| progress.                                                                    |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|General Information or Other                     |Event Number:   39798       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  KENTUCKY DEPT OF RADIATION CONTROL   |NOTIFICATION DATE: 04/25/2003|

|LICENSEE:  HAYES TESTING LABORATORY             |NOTIFICATION TIME: 10:26[EDT]|

|    CITY:  LOUISVILLE               REGION:  2  |EVENT DATE:        04/25/2003|

|  COUNTY:  JEFFERSON                 STATE:  KY |EVENT TIME:             [CDT]|

|LICENSE#:  201-168-05            AGREEMENT:  Y  |LAST UPDATE DATE:  04/25/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |MIKE ERNSTES         R2      |

|                                                |DANIEL GILLEN        NMSS    |

+------------------------------------------------+                             |

| NRC NOTIFIED BY:  BOB JOHNSON                  |                             |

|  HQ OPS OFFICER:  HOWIE CROUCH                 |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|NAGR                     AGREEMENT STATE        |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| AGREEMENT STATE REPORT - KENTUCKY                                            |

|                                                                              |

| "This letter is notification of a stuck radiography source event that        |

| occurred on March 28, 2003 at Marathon Petroleum in Louisville Kentucky.     |

| The licensee involved was Hayes Testing Laboratory, Inc., Radioactive        |

| Material License Number 201-168-05.  The radiography source was 92.7         |

| [curies] of Ir-192, housed in a 660 B Camera, S/N 1175.                      |

|                                                                              |

| "On March 28, 2003, during performance of radiography with the source        |

| extended, a magnet stand fell approximately 10 feet onto the source tube.    |

| This resulted in a crimp in the source tube, and the radiography source      |

| could not be retracted into the camera.  The area had been initially roped   |

| off and posted off at the 2 mrem/hr boundaries, but once the radiography     |

| source could not be retrieved, personnel followed licensed emergency         |

| procedures and secured the entire area.                                      |

|                                                                              |

| "The radiographer and the radiographer's supervisor attempted to use all     |

| safe means to retrieve the radiography source without success.  The          |

| Radiation Safety Officer (RSO) was contacted immediately, and was able to    |

| determine source location, and shielded the exposed source with four (4) 25  |

| lb. bags of lead shot.  The RSO using extended handle channel locks, was     |

| able to un-crimp the source tube and retrieve the radiography source back    |

| into the camera. The estimated time to un-crimp the source tube and retrieve |

| the source was approximately 2.5 minutes.                                    |

|                                                                              |

| "The radiographer, radiographer's assistant, radiographer's supervisor and   |

| RSO's dosimetry were immediately sent to ICN [a film processing lab] for     |

| processing.  The exposure results were highest in all aspects for the RSO at |

| 111 mrem deep dose, 107 mrem eye dose, and 103 shallow dose.                 |

|                                                                              |

| "The response to this event was considered appropriate and met licensing     |

| conditions. The Commonwealth of Kentucky considers this event closed."       |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Other Nuclear Material                           |Event Number:   39802       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  DELTA CONSULTING ENGINEER            |NOTIFICATION DATE: 04/28/2003|

|LICENSEE:  DELTA CONSULTING ENGINEER            |NOTIFICATION TIME: 12:03[EDT]|

|    CITY:  GUAYNABO                 REGION:  2  |EVENT DATE:        04/28/2003|

|  COUNTY:                            STATE:  PR |EVENT TIME:        10:00[EDT]|

|LICENSE#:  522541501             AGREEMENT:  N  |LAST UPDATE DATE:  04/29/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |MIKE ERNSTES         R2      |

|                                                |FRED BROWN           NMSS    |

+------------------------------------------------+                             |

| NRC NOTIFIED BY:  SOUSA                        |                             |

|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|BLO2 20.2201(a)(1)(ii)   LOST/STOLEN LNM>10X    |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| STOLEN TROXLER GAUGE                                                         |

|                                                                              |

| Licensee reported that a Troxler Gauge Model 3430 serial number #029673      |

| containing approximately 90 millicuries of Cs-137 and 44 millicuries of      |

| Am-241 was stolen from a construction site trailer in Guaynabo, Puerto Rico. |

| Sometime between the evening of 4/25/03 and 10:00 on 4/28/03.   The licensee |

| has notified the local law enforcement.                                      |

|                                                                              |

| Note From HOO: Troxler model 3430 normally has 8 millicuries of Cs-137.      |

|                                                                              |

| * * * UPDATE ON 04/29/03 @ 1515 BY SOUSA TO GOULD * * *                      |

|                                                                              |

| The Troxler gauge was returned on 04/29/03 @ 1400 to the licensee.  There    |

| appeared to be no damage to the gauge, but they will be performing a leak    |

| test on it.                                                                  |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39807       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: INDIAN POINT             REGION:  1  |NOTIFICATION DATE: 04/29/2003|

|    UNIT:  [] [3] []                 STATE:  NY |NOTIFICATION TIME: 04:52[EDT]|

|   RXTYPE: [2] W-4-LP,[3] W-4-LP                |EVENT DATE:        04/29/2003|

+------------------------------------------------+EVENT TIME:             [EDT]|

| NRC NOTIFIED BY:  CARL SMYERS /JOHN BRAKHIA    |LAST UPDATE DATE:  04/29/2003|

|  HQ OPS OFFICER:  HOWIE CROUCH                 +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          UNUSUAL EVENT         |TODD JACKSON         R1      |

|10 CFR SECTION:                                 |JAMES LYONS          NRR     |

|AAEC 50.72(a) (1) (i)    EMERGENCY DECLARED     |MICHELE EVANS        IRO     |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|3     M/R        Y       60       Power Operation  |0        Hot Standby      |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| UNUSUAL EVENT DECLARED DUE TO FIRE IN THE TURBINE                            |

|                                                                              |

| The following information was obtained from the licensee via facsimile:      |

|                                                                              |

| "Class B fire south end of Main High Pressure Turbine located 53 foot        |

| elevation of turbine building.  Reactor and turbine were manually tripped.   |

| Fire brigade was dispatched.  Fire was out in 47 minutes.  There were no ESF |

| actuations or other anomalies during trip with one exception - letdown       |

| isolated on low pressurizer [level] and was subsequently restore[d].  No     |

| injuries."                                                                   |

|                                                                              |

| The NRC Resident Inspector was notified by the licensee.                     |

|                                                                              |

| * * * UPDATE ON 4/29/03 @ 0527 EDT FROM MIKE DONEGAN TO HOWIE CROUCH * * *   |

|                                                                              |

| The licensee has terminated the NOUE at 0520 EDTon the basis that the fire   |

| is out and the plant is stable.                                              |

|                                                                              |

| Notified R1DO (Jackson), NRR EO (Lyons), DIRO (Evans), DENVER and FEMA       |

| (Sullivan).                                                                  |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39808       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: INDIAN POINT             REGION:  1  |NOTIFICATION DATE: 04/29/2003|

|    UNIT:  [] [3] []                 STATE:  NY |NOTIFICATION TIME: 06:01[EDT]|

|   RXTYPE: [2] W-4-LP,[3] W-4-LP                |EVENT DATE:        04/29/2003|

+------------------------------------------------+EVENT TIME:        03:13[EDT]|

| NRC NOTIFIED BY:  MIKE DONEGAN                 |LAST UPDATE DATE:  04/29/2003|

|  HQ OPS OFFICER:  HOWIE CROUCH                 +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |TODD JACKSON         R1      |

|10 CFR SECTION:                                 |JAMES LYONS          NRR     |

|ARPS 50.72(b)(2)(iv)(B)  RPS ACTUATION - CRITICA|                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|3     M/R        Y       60       Power Operation  |0        Hot Standby      |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| MANUAL REACTOR TRIP DUE TO FIRE IN THE HIGH PRESSURE TURBINE                 |

|                                                                              |

|                                                                              |

| The following information was received from the licensee via facsimile:      |

|                                                                              |

| "Class B fire south end of turbine resulted in manual trip of the Rx and     |

| Turbine.  The fire was out in 47 minutes.  There were no ESF actuations -    |

| all systems responded as expected except let down isolated on a low          |

| pressurizer level.  Due to the fire being greater than 15 minutes a [Notice  |

| of Unusual Event] was entered at 0313 [EDT] and exited at 0520 [see event    |

| notification 39807].  The plant is currently in Mode 3 Hot Standby."         |

|                                                                              |

| During the reactor trip, all rods inserted.  The electrical bus is stable    |

| and supplying required plant loads.  The other unit on the site was already  |

| shutdown and unaffected by the fire or reactor trip.  Core decay heat is     |

| being removed using the steam dump to condenser system and the auxiliary     |

| feedwater system. The extent of damage to the turbine is under investigation |

| by the licensee.                                                             |

|                                                                              |

| The NRC Resident Inspector has been notified by the licensee.                |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Other Nuclear Material                           |Event Number:   39809       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  US ARMY                              |NOTIFICATION DATE: 04/29/2003|

|LICENSEE:  US ARMY                              |NOTIFICATION TIME: 13:37[EDT]|

|    CITY:  FORT KNOX                REGION:  2  |EVENT DATE:        03/12/2003|

|  COUNTY:                            STATE:  KY |EVENT TIME:        10:00[CDT]|

|LICENSE#:                        AGREEMENT:  Y  |LAST UPDATE DATE:  04/29/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |JOEL MUNDY           R2      |

|                                                |DOUG BROADDUS        NMSS    |

+------------------------------------------------+RONALD GARDNER       R3      |

| NRC NOTIFIED BY:  MARY CRUTCHER                |                             |

|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|BLO2 20.2201(a)(1)(ii)   LOST/STOLEN LNM>10X    |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| LICENSEE REPORTED TWO LOSS/STOLEN TRITIUM EXIT SIGNS                         |

|                                                                              |

| The licensee reported that two tritium exit signs stored in boxes in a       |

| storage building in the hazmat center turned up missing.   Each sign had 15  |

| curies of tritium for a total of 30 curies.  Last inventory made on these    |

| signs was 09/00.  They have searched for them with no success.  They are     |

| continuing further investigation to determine if the signs had been          |

| installed.                                                                   |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Other Nuclear Material                           |Event Number:   39810       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  SUSTAINABLE RESOURCES CENTER         |NOTIFICATION DATE: 04/29/2003|

|LICENSEE:  SUSTAINABLE RESOURCES CENTER         |NOTIFICATION TIME: 16:04[EDT]|

|    CITY:  MINNEAPOLIS              REGION:  3  |EVENT DATE:        04/25/2003|

|  COUNTY:                            STATE:  MN |EVENT TIME:        19:30[CDT]|

|LICENSE#:                        AGREEMENT:  N  |LAST UPDATE DATE:  04/29/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |RONALD GARDNER       R3      |

|                                                |TRISH HOLAHAN        NMSS    |

+------------------------------------------------+                             |

| NRC NOTIFIED BY:  CHRIS PETROSKAS              |                             |

|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|BLO2 20.2201(a)(1)(ii)   LOST/STOLEN LNM>10X    |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| STOLEN X-RAY FLORESCENCE DEVICE                                              |

|                                                                              |

| Sustainable Resources Center reported that their cleaning people let an      |

| individual into the building on 4/25/2003 at approximately 1930 and believe  |

| that he stole the X-Ray Florescence ( XRF) device.  The unit was a Niton     |

| model XL300 serial # U2830NR2200 containing 14 millicuries of cadmium-109    |

| and was inside a case resembling a camera case.  This device is used to      |

| analyze lead base paint and was on lease to Sustainable Resources Center.    |

| The Minneapolis Police Department will be notified.                          |

+------------------------------------------------------------------------------+



                    