The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.
Event Notification Report for April 21, 2003
U.S. Nuclear Regulatory Commission
Operations Center
Event Reports For
04/18/2003 - 04/21/2003
** EVENT NUMBERS **
39754 39763 39770 39771 39772 39773 39774 39775 39776
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 39754 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SOUTH TEXAS REGION: 4 |NOTIFICATION DATE: 04/13/2003|
| UNIT: [1] [] [] STATE: TX |NOTIFICATION TIME: 19:06[EDT]|
| RXTYPE: [1] W-4-LP,[2] W-4-LP |EVENT DATE: 04/13/2003|
+------------------------------------------------+EVENT TIME: 16:56[CDT]|
| NRC NOTIFIED BY: RON GIBBS |LAST UPDATE DATE: 04/18/2003|
| HQ OPS OFFICER: STEVE SANDIN +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |DAVID LOVELESS R4 |
|10 CFR SECTION: | |
|ADEG 50.72(b)(3)(ii)(A) DEGRADED CONDITION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N N 0 Cold Shutdown |0 Cold Shutdown |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| REACTOR VESSEL BOTTOM HEAD DEGRADED CONDITION |
| |
| "On 4/12/2003, during the Unit 1 11th (1RE11) refueling outage, an |
| inspection was performed of the vessel bottom head. This bare metal |
| inspection identified a potential leak indication at the head to penetration |
| interface for Bottom Mounted Instrumentation (BMI) penetrations 1 and 46. |
| There was a small amount of residue around the outer circumference of the |
| BMI penetrations. No wastage was observed. Samples of the residue were taken |
| and the area was cleaned with demineralized water. Chemical sample results |
| available as of 1300 on 4/13/2003 are not conclusive; however, they have |
| confirmed that the residue found at the Penetration 46 contains boron, |
| indicating that this could be an RCS leak. The residue removed from |
| Penetration 1 was characterized as 'gummy' and its composition is still |
| under investigation. Additional exams are planned to confirm the likely |
| origin of the residue and to determine the scope of any repairs. There has |
| been no indication of RCS leakage observed at the BMI penetrations during |
| previous operational cycles. This notification is being made in accordance |
| with 10 CFR 50.72(b)(3)(ii)(A)." |
| |
| Unit 1 will remain in mode 5 until appropriate corrective actions are |
| identified. The licensee informed the NRC resident inspector. |
| |
| * * * * UPDATE 1151 EDT 04/18/03 FROM WAYNE HARRISON TO MIKE RIPLEY * * * |
| |
| "STP Nuclear Operating Co. will be making a press release [at 12:00 pm |
| 04/18/03] concerning the indications found on the Bottom Mounted |
| Instrumentation penetrations on Unit 1. The release is being coordinated |
| with NRC Region IV. |
| |
| "STP has notified or will be notifying various federal, state and local |
| agencies, including FEMA, the governors office, Matagorda County, Bay City. |
| City of Palacios, state representatives and state senators, US |
| representatives and US Senators." |
| |
| The licensee notified the NRC Resident Inspector. |
| |
| Notified R3DO (C. Johnson), HQ PAO (W. Beecher) |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|General Information or Other |Event Number: 39763 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: MA RADIATION CONTROL PROGRAM |NOTIFICATION DATE: 04/16/2003|
|LICENSEE: AEA TECHNOLOGY QSA |NOTIFICATION TIME: 10:07[EDT]|
| CITY: BURLINGTON REGION: 1 |EVENT DATE: 04/15/2003|
| COUNTY: STATE: MA |EVENT TIME: [EDT]|
|LICENSE#: 12-8361 AGREEMENT: Y |LAST UPDATE DATE: 04/16/2003|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |DAVID SILK R1 |
| |THOMAS ESSIG NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: BRUCE PACKARD | |
| HQ OPS OFFICER: RICH LAURA | |
+------------------------------------------------+ |
|EMERGENCY CLASS: NON EMERGENCY | |
|10 CFR SECTION: | |
|NAGR AGREEMENT STATE | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| MASSACHUSETTS AGREEMENT STATE REPORT ON SHIPPING PACKAGE RADIOLOGICAL ISSUE |
| |
| "On April 15, 2003, a Yellow-III Package containing 30 millicuries (1.1 Gbq) |
| of Co-60 measured 400 millirem/hr on the surface. The Shipper was AEA |
| Technology QSA GMBH, Giesilweg 1, D-38110 Braunschweig, Germany. The |
| carriers included Federal Express Freight and Ground Control. Immediate |
| reporting requirements means investigation is not complete at the time of |
| report." |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 39770 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SEQUOYAH REGION: 2 |NOTIFICATION DATE: 04/18/2003|
| UNIT: [1] [2] [] STATE: TN |NOTIFICATION TIME: 16:59[EDT]|
| RXTYPE: [1] W-4-LP,[2] W-4-LP |EVENT DATE: 04/18/2003|
+------------------------------------------------+EVENT TIME: 14:08[EDT]|
| NRC NOTIFIED BY: MICHAEL HOWARD |LAST UPDATE DATE: 04/18/2003|
| HQ OPS OFFICER: HOWIE CROUCH +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |THOMAS DECKER R2 |
|10 CFR SECTION: |SUSIE BLACK NRR |
|APRE 50.72(b)(2)(xi) OFFSITE NOTIFICATION |JOSEPH HOLONICH IRO |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N N 0 Refueling |0 Refueling |
|2 N Y 100 Power Operation |100 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| NON- WORK RELATED FATALITY TO CONTRACT EMPLOYEE PROMPTS OFFSITE |
| NOTIFICATION |
| |
| The following information was received from the licensee via facsimile: |
| |
| "At approximately 1408 EDT on April 18, 2003, a non-work related medical |
| emergency occurred at the Sequoyah Nuclear Plant (SNP). Specifically, a |
| contract laborer went into cardiac arrest. The individual was attended to |
| by SNP Emergency Medical Technicians (EMTs). The individual was transported |
| off-site in a TVA ambulance and was subsequently transferred to a Hamilton |
| County ambulance. The individual was pronounced dead on arrival at the |
| hospital. The fatality was not related to the health and safety of the |
| public or on-site personnel. |
| |
| "The individual was outside of the Radiological Controlled Area and no |
| radioactive material or contamination was involved. |
| |
| "A notification was made to the Occupational Safety and Health |
| Administration at 1555 EDT this date. This ENS notification is in response |
| to a notification to a other government agency in accordance with 10 CFR |
| 50.72(b)(2)(xi)." |
| |
| The licensee has notified the NRC Resident Inspector. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Fuel Cycle Facility |Event Number: 39771 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PORTSMOUTH GASEOUS DIFFUSION PLANT |NOTIFICATION DATE: 04/19/2003|
| RXTYPE: URANIUM ENRICHMENT FACILITY |NOTIFICATION TIME: 00:45[EDT]|
| COMMENTS: 2 DEMOCRACY CENTER |EVENT DATE: 04/18/2003|
| 6903 ROCKLEDGE DRIVE |EVENT TIME: 23:15[EDT]|
| BETHESDA, MD 20817 (301)564-3200 |LAST UPDATE DATE: 04/19/2003|
| CITY: PIKETON REGION: 3 +-----------------------------+
| COUNTY: PIKE STATE: OH |PERSON ORGANIZATION |
|LICENSE#: GDP-2 AGREEMENT: N |THOMAS KOZAK R3 |
| DOCKET: 0707002 |JOHN GREEVES NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: KURT SISLER | |
| HQ OPS OFFICER: ARLON COSTA | |
+------------------------------------------------+ |
|EMERGENCY CLASS: NON EMERGENCY | |
|10 CFR SECTION: | |
|NONR OTHER UNSPEC REQMNT | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION TO OHIO EPA OF OPACITY EXCEEDANCE |
| |
| "On 4/18/03 at 2315 hours, the high pressure blower overload tripped on |
| X-600 [Steam Plant] #3 boiler. This equipment failure caused two opacity |
| readings (six minute average) to be above 20%. This requires a verbal |
| notification to the Ohio Environmental Protection Agency (OEPA). |
| |
| "At 2350 hours, the Plant Shift Superintendent notified OEPA of the X-600 |
| Steam Plant opacity exceedance. UE-RA-RE1030, App. D, section P, requires a |
| 4 hour NRC event [notification] when other government agencies are |
| notified." |
| |
| The high pressure blower overload breaker was reset and the #3 boiler is |
| currently operational. The Licensee is investigating the cause of the |
| blower overload trip. |
| |
| The Licensee informed both the NRC Resident Inspector and the DOE Site |
| Representative. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 39772 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CALVERT CLIFFS REGION: 1 |NOTIFICATION DATE: 04/19/2003|
| UNIT: [] [2] [] STATE: MD |NOTIFICATION TIME: 19:33[EDT]|
| RXTYPE: [1] CE,[2] CE |EVENT DATE: 04/19/2003|
+------------------------------------------------+EVENT TIME: 15:30[EDT]|
| NRC NOTIFIED BY: JAMES GROOMS |LAST UPDATE DATE: 04/19/2003|
| HQ OPS OFFICER: HOWIE CROUCH +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |DAVID SILK R1 |
|10 CFR SECTION: | |
|AESF 50.72(b)(3)(iv)(A) VALID SPECIF SYS ACTUAT| |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
| | |
|2 N N 0 Hot Standby |0 Hot Standby |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| REACTOR PROTECTION SYSTEM ACTUATION |
| |
| The following information was received from the licensee via facsimile: |
| |
| "While performing STP [Surveillance Test Procedure] M-200-2, the RPS |
| [Reactor Protection System] S/G [Steam Generator] Low Press[ure] Trip Units |
| were bypassed using the S/G Low Press[ure] Bypass key. The bypass was |
| automatically removed early before the S/G Low Press[ure] trips were |
| clear[ed]. This resulted in the RPS calling for the TCBs [Trip Circuit |
| Breakers] to open. The CEAs [control rods] were already in the core. This |
| is an 8 hr. report[able] per [10 CFR] 50.72(b)(3)(iv)(A). S/G Press[ures] |
| were [approximately] 700 psi." |
| |
| The surveillance test procedure was to allow time response testing on the |
| trip circuit breakers by the Electrical department (which requires the TCBs |
| to be closed). The plant was also performing a plant heatup in preparation |
| for plant startup. During normal operations, the S/G Low Pressure Trip |
| setpoint is 700 psi. The surveillance test procedure allowed the S/G Low |
| Pressure Trip to be bypassed via the bypass key. If the S/G Low Pressure |
| Trip is keyed to bypass and the S/G pressure increases to greater than 785 |
| psi, then the 700 psi trip setpoint is automatically re-instated regardless |
| of bypass key position. The licensee is investigating the reason that the |
| S/G Low Pressure Trip was automatically re-instated with S/G pressure at |
| approximately 700 psi. |
| |
| The NRC Resident Inspector has been notified. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 39773 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: NORTH ANNA REGION: 2 |NOTIFICATION DATE: 04/19/2003|
| UNIT: [1] [] [] STATE: VA |NOTIFICATION TIME: 23:23[EDT]|
| RXTYPE: [1] W-3-LP,[2] W-3-LP |EVENT DATE: 04/19/2003|
+------------------------------------------------+EVENT TIME: 20:08[EDT]|
| NRC NOTIFIED BY: BRAD BROWN |LAST UPDATE DATE: 04/19/2003|
| HQ OPS OFFICER: HOWIE CROUCH +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |THOMAS DECKER R2 |
|10 CFR SECTION: | |
|ARPS 50.72(b)(2)(iv)(B) RPS ACTUATION - CRITICA| |
|AESF 50.72(b)(3)(iv)(A) VALID SPECIF SYS ACTUAT| |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 M/R Y 74 Power Operation |0 Hot Standby |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| MANUAL REACTOR TRIP WITH A SUBSEQUENT AUXILIARY FEEDWATER ACTUATION |
| |
| The following information was received from the licensee via facsimile: |
| |
| "A 4 hr. report due to a manual reactor trip (RPS actuation) due to an oil |
| leak on the main turbine. |
| |
| "An 8 hr. report due to Aux[iliary] Feedwater System initiation due to the |
| reactor trip (expected response)." |
| |
| The manual reactor trip was due to a lube oil leak through the diaphragm on |
| the EHC (Electro-Hydraulic Control) interface valve. The leak caused the |
| interface valve to close therefore isolating EHC hydraulic fluid to the |
| turbine control system. During the trip, all rods inserted into the core. |
| As a result of the transient, a pressurizer power-operated relief valve |
| lifted and indications show that it subsequently re-seated. There are no |
| indications that the blow-out plug on the pressurizer relief tank was |
| damaged. Pressurizer relief tank pressure has been reduced to normal. |
| Additionally, a secondary tube side relief lifted and was re-seated after |
| the second running feedwater pump was secured. Decay heat is being removed |
| via the steam dump to condenser system operating in automatic. The |
| electrical grid is stable and supplying plant loads. There was no affect on |
| the other operating unit. |
| |
| As expected, the Auxiliary Feedwater System initiated. The system has been |
| returned to normal, standby configuration and steam generator level is being |
| controlled by the main feedwater system operating in manual control. |
| |
| The licensee has notified the NRC Resident Inspector. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 39774 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PALO VERDE REGION: 4 |NOTIFICATION DATE: 04/20/2003|
| UNIT: [1] [2] [3] STATE: AZ |NOTIFICATION TIME: 05:40[EDT]|
| RXTYPE: [1] CE,[2] CE,[3] CE |EVENT DATE: 04/20/2003|
+------------------------------------------------+EVENT TIME: 00:00[MST]|
| NRC NOTIFIED BY: RUSSELL STROUD |LAST UPDATE DATE: 04/20/2003|
| HQ OPS OFFICER: ARLON COSTA +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |CLAUDE JOHNSON R4 |
|10 CFR SECTION: | |
|APRE 50.72(b)(2)(xi) OFFSITE NOTIFICATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 98 Power Operation |98 Power Operation |
|2 N Y 98 Power Operation |98 Power Operation |
|3 N N 0 Refueling |0 Refueling |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| PALO VERDE SPURIOUS ACTUATION OF OFFSITE EMERGENCY NOTIFICATION SIREN |
| |
| "At 0000 MST on April 20, 2003, the Palo Verde Unit 1 Control Room was |
| notified of a spurious actuation of an emergency warning siren in the |
| vicinity of 348th avenue and Buckeye Road. While not confirmed at this |
| time, the siren is believed to be siren #17 which is approximately five |
| miles to the Northeast of Palo Verde. At approximately 0035 MST, the Unit 1 |
| Control Room was informed [that] the siren was no longer actuating. This |
| siren provides emergency notification to approximately 89 members of the |
| public. |
| |
| "No press release is planned at this time, however, the event is being |
| reported due to the inquiry of a citizen to the Energy Control Center (ECC) |
| and a subsequent notification to the Maricopa County Sheriff's Office. |
| |
| "There is no event in progress and no risk to the health and safety of the |
| public. Members of the public within audible range of the siren may have a |
| concern for their radiological health and safety. |
| |
| "Unit 1 is at approximately 98% power in Mode 1 at normal operating |
| temperature and pressure. |
| |
| "Unit 2 is at approximately 98% power in Mode 1 at normal operating |
| temperature and pressure. |
| |
| "Unit 3 is at 0% [power] in a refueling outage. |
| |
| "The NRC Sr. Resident Inspector has been informed of the siren actuation and |
| [of] this ENS notification. |
| |
| "Note: The checkbox below for 'OTHER GOV AGENCIES' is referring to the |
| Maricopa County Sheriff's Office." |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 39775 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: DUANE ARNOLD REGION: 3 |NOTIFICATION DATE: 04/20/2003|
| UNIT: [1] [] [] STATE: IA |NOTIFICATION TIME: 16:28[EDT]|
| RXTYPE: [1] GE-4 |EVENT DATE: 04/20/2003|
+------------------------------------------------+EVENT TIME: 15:13[CDT]|
| NRC NOTIFIED BY: ROBERT TEMPLE |LAST UPDATE DATE: 04/20/2003|
| HQ OPS OFFICER: GERRY WAIG +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |THOMAS KOZAK R3 |
|10 CFR SECTION: | |
|AIND 50.72(b)(3)(v)(D) ACCIDENT MITIGATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 18 Power Operation |18 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| LEAK DISCOVERED ON HIGH PRESSURE CORE INJECTION PIPING DURING SURVEILLANCE |
| TESTING |
| |
| "During the performance of STP [Surveillance Test Procedure] 3.5.1-09, HPCI |
| [High Pressure Core Injection] System Post-Startup Operability Test, on |
| 4/20/03, a small leak was detected on a � inch pipe nipple on the seal water |
| line on the main HPCI pump. Engineers determined that the leak is from a |
| small crack at a threaded connection. This piping is ASME class 2 piping. |
| This leak constitutes a loss of structural integrity of a Class 2 component |
| as required by section 3.7.3 of the Technical Requirements Manual [TRM]. |
| |
| "At 1337 CDT, on 4/20/03, entered T[TRM] LCO [Limiting Condition of |
| Operation] T3.7.3 condition A, Structural Integrity of Class 1 or Class 2 |
| components not maintained in MODES 1, 2 and 3. |
| |
| "At 1513 CDT on 4/20/03, the HPCI system was isolated and declared |
| Inoperable. Entered [Technical Specification] LCO 3.5.1 Condition F, HPCI |
| System Inoperable, 14 days to restore HPCI. This unplanned HPCI System |
| inoperability is reportable under 10CFR50.72(b)(3)(v)(d) as a single train |
| failure that could have prevented the fulfillment of a safety function of |
| structures or systems designed to mitigate the consequences of an |
| accident." |
| |
| The licensee has notified the NRC Resident Inspector. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 39776 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SURRY REGION: 2 |NOTIFICATION DATE: 04/20/2003|
| UNIT: [1] [2] [] STATE: VA |NOTIFICATION TIME: 17:21[EDT]|
| RXTYPE: [1] W-3-LP,[2] W-3-LP |EVENT DATE: 04/20/2003|
+------------------------------------------------+EVENT TIME: 12:35[EDT]|
| NRC NOTIFIED BY: JOHN DUFF |LAST UPDATE DATE: 04/20/2003|
| HQ OPS OFFICER: GERRY WAIG +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |THOMAS DECKER R2 |
|10 CFR SECTION: | |
|ACOM 50.72(b)(3)(xiii) LOSS COMM/ASMT/RESPONSE| |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N N 0 Cold Shutdown |0 Cold Shutdown |
|2 N Y 100 Power Operation |100 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| LOSS OF SAFETY PARAMETER DISPLAY SYSTEM (SPDS) FOR GREATER THAN 1 HOUR |
| |
| "At 1235 hours EDT on 04/20/03, the Safety Parameter Display System (SPDS) |
| portion of the Emergency Response Facility Computer System (ERFCS) was noted |
| to be inoperable due to all outputs being displayed in 'magenta' color. At |
| the time of the failure, the ERFCS computer was being re-initiated by |
| Instrumentation & Controls personnel and failed to restart following the |
| re-initiation sequence. |
| |
| "As of 1335 hours EDT on 4/20/03, SPDS has been out of service for greater |
| then 1 hour. which is considered a major loss of emergency assessment |
| capability. |
| |
| "Troubleshooting of the ERFCS by Instrumentation & Controls personnel |
| identified a software problem. At 1600 hours EDT on 04/20/03, |
| Instrumentation & Controls personnel were able to restore the 'A' train |
| ERFCS and at 1630 hours EDT on 04/20/03 the ERFCS and SPDS were declared |
| operable [efforts to restore the 'B' train are ongoing]. |
| |
| "This report is being made in accordance with I0CFR50.72(b)(3)(xiii)." |
| |
| The Licensee has notified the NRC Resident Inspector. |
+------------------------------------------------------------------------------+
Page Last Reviewed/Updated Wednesday, March 24, 2021
Page Last Reviewed/Updated Wednesday, March 24, 2021