Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for March 10, 2003








                    U.S. Nuclear Regulatory Commission

                              Operations Center



                              Event Reports For

                           03/07/2003 - 03/10/2003



                              ** EVENT NUMBERS **



39526  39575  39630  39643  39644  39645  39646  39647  39648  39649  39650  39651  



!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!

+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39526       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: BEAVER VALLEY            REGION:  1  |NOTIFICATION DATE: 01/20/2003|

|    UNIT:  [] [2] []                 STATE:  PA |NOTIFICATION TIME: 20:13[EST]|

|   RXTYPE: [1] W-3-LP,[2] W-3-LP                |EVENT DATE:        01/20/2003|

+------------------------------------------------+EVENT TIME:        14:30[EST]|

| NRC NOTIFIED BY:  JAMES WITTER                 |LAST UPDATE DATE:  03/07/2003|

|  HQ OPS OFFICER:  RICH LAURA                   +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |JOHN ROGGE           R1      |

|10 CFR SECTION:                                 |MOHAMED SHANBAKY     R1      |

|AUNA 50.72(b)(3)(ii)(B)  UNANALYZED CONDITION   |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|2     N          Y       100      Power Operation  |100      Power Operation  |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| SERVICE WATER SYSTEM VALVE PIT PIPING PENETRATION SEAL                       |

|                                                                              |

| "On 1/20/2003 at 1430 hours, the Beaver Valley Power Station control room    |

| was notified by Engineering that a penetration seal previously installed in  |

| a wall which separates two service water system valve pits may have not been |

| adequate. A review of the supporting analysis shows that this penetration    |

| seal may not be qualified to withstand the hydraulic pressure which could    |

| result from a postulated internal flooding event occurring due to a service  |

| water system pipe failure filling the valve pit and its above compartment    |

| prior to operator intervention. A failure of this seal during a postulated   |

| internal flooding event may result in the loss of motor operated valve       |

| movement in both trains of the service water system that would be needed     |

| following a design basis accident (DBA).                                     |

|                                                                              |

| "This design basis calculation and the penetration seal capability are       |

| continuing to be evaluated. However, this seal could potentially have        |

| prevented the service water system from meeting single failure criterion     |

| during a postulated service water system pipe failure. Therefore, Technical  |

| Specification (TS) 3.7.4.1 was entered due to less than two trains of        |

| service water system being operable as a conservative decision based upon    |

| the limited information immediately available to show acceptable seal        |

| integrity at the postulated conditions. The TS Action requires restoration   |

| of two independent service water system trains within 72 hours. Actions are  |

| in progress to install a qualified seal which will prevent the unacceptable  |

| flooding conditions from being able to occur.                                |

|                                                                              |

| "This condition is being reported pursuant to 10 CFR 50.72(b)(3)(ii) as an   |

| unanalyzed condition that significantly degraded plant safety since this     |

| seal has been installed for five months and may have invalidated the         |

| independence between the two service water system trains. The NRC resident   |

| has been notified of the degraded condition."                                |

|                                                                              |

| * * * RETRACTION RECEIVED AT 1002 EST ON 3/07/2003 BY WITTER TO CROUCH * * * |

|                                                                              |

|                                                                              |

| "Beaver Valley Power Station (BVPS) Unit No. 2 retracts the notification     |

| made on 01/20/2003 at 20:13 hrs [EST] regarding the event reported under 10  |

| CFR 50.72(b)(3)(ii)(B) [ENS #39526]. The previous notification identified a  |

| potential issue with a seal penetration which may have invalidated the       |

| independence between two Service Water System trains.                        |

|                                                                              |

| "Subsequent analysis of the event identified that the installed penetration  |

| seal between the two Service Water System valve pits would have been capable |

| of performing its intended safety function. Therefore, the separation and    |

| independence between the two Service Water System trains, as required by     |

| Technical Specification 3.7.4.1, would have been satisfied.                  |

|                                                                              |

| "Given that both trains of the Service Water System were able to perform     |

| their safety functions, this was not a condition that significantly degraded |

| plant safety."                                                               |

|                                                                              |

| The licensee has notified the NRC Resident Inspector.                        |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|General Information or Other                     |Event Number:   39575       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  MA RADIATION CONTROL PROGRAM         |NOTIFICATION DATE: 02/10/2003|

|LICENSEE:  PERKINELMER LIFE SCIENCES            |NOTIFICATION TIME: 14:29[EST]|

|    CITY:  BOSTON                   REGION:  1  |EVENT DATE:        07/18/2002|

|  COUNTY:                            STATE:  MA |EVENT TIME:             [EST]|

|LICENSE#:  00-3200               AGREEMENT:  Y  |LAST UPDATE DATE:  03/07/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |GLENN MEYER          R1      |

|                                                |DON COOL     EO      NMSS    |

+------------------------------------------------+                             |

| NRC NOTIFIED BY:  CARPENITO                    |                             |

|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|NAGR                     AGREEMENT STATE        |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| POTENTIALLY MISSING  PHOSPHORUS-32 SHIPPING PACKAGES                         |

|                                                                              |

| Single packages containing P-32 (~14 day half-life) were destined for four   |

| different out-of-state locations (in CA, KS, NY and TX). Intended shipping   |

| dates were July 18, August 5 and August 6, 2002. Carrier reported packages   |

| potentially missing within 2-3 days after intended shipping dates. The       |

| per-package activities ranged from 250 microcuries to 1 millicurie. All      |

| subject radioactive material contents are presently well past ten            |

| half-lives. After several months of shipper-carrier joint investigation, the |

| cause(s) remain undetermined. Actions have been taken by shipper and carrier |

| to prevent recurrence.                                                       |

|                                                                              |

| * * * * UPDATE RECEIVED BY RIPLEY FROM CARPENITO 1448 EST ON 03/07/03 VIA    |

| FAX                                                                          |

|                                                                              |

| "Five additional single-package shipments (four P-32 and one I-125),         |

| destined for five different locations, shipped August 27, October 17,        |

| November 4 and 26, and December 13, 2002, were reported to MARCP as missing  |

| on 2/14/03.  The per-package activities ranged from 250 to 500 microcuries   |

| of P-32 and 50 microcuries I-125.  All subject packages were shipped before  |

| the shipper and carrier corrective actions had been implemented in late      |

| December 2002.  No packages shipped since the corrective actions have been   |

| implemented have been reported to MARCP as missing."                         |

|                                                                              |

| Notified NMSS EO (Reamer) and R1 DO (Shanbaky)                               |

+------------------------------------------------------------------------------+



!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!

+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39630       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: COOPER                   REGION:  4  |NOTIFICATION DATE: 03/02/2003|

|    UNIT:  [1] [] []                 STATE:  NE |NOTIFICATION TIME: 10:43[EST]|

|   RXTYPE: [1] GE-4                             |EVENT DATE:        03/02/2003|

+------------------------------------------------+EVENT TIME:        03:35[CST]|

| NRC NOTIFIED BY:  LONG                         |LAST UPDATE DATE:  03/07/2003|

|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |DAVID GRAVES         R4      |

|10 CFR SECTION:                                 |                             |

|AUNA 50.72(b)(3)(ii)(B)  UNANALYZED CONDITION   |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|1     N          N       0        Cold Shutdown    |0        Cold Shutdown    |

|                                                   |                          |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| PRIMARY CONTAINMENT MEASURED LEAKAGE EXCEEDS THE ALLOWED LEAKAGE.            |

|                                                                              |

| During routine scheduled LLRT (Local Leak Rate Testing) of Penetration       |

| X-214,  HPCI (High Pressure Coolant Injection) Exhaust Discharge to the      |

| Torus, leakage was unable to be quantified.   Additionally, of the two       |

| isolation check valves in the line, the licensee could not determine which   |

| one was leaking.   As such, Primary Containment Allowed Leakage (La) is      |

| unable to be verified to be less than allowed.                               |

|                                                                              |

| The plant was in Mode 4 (Cold S/D) for a scheduled refueling outage with     |

| temperature being maintained between 130 and 145 degrees Fahrenheit and      |

| Primary Containment not required at the time of discovery.  The plant will   |

| remain in cold shutdown until repairs are completed.                         |

|                                                                              |

| The NRC Resident Inspector was notified.                                     |

|                                                                              |

| * * * * RETRACTION RECEIVED AT 1326 EST ON 03/07/03 BY BLAIR TO RIPLEY * * * |

| *                                                                            |

|                                                                              |

| "On 3/2/03 at 0943 CST, Cooper Nuclear Station made an 8 hour 50.72          |

| non-emergency notification to the NRC.  This was done due to the failure of  |

| Local Leak Rate Testing (LLRT) involving the High Pressure Coolant Injection |

| (HPCI) exhaust discharge to the Suppression Chamber.  Leakage was unable to  |

| be quantified.  Additionally, of the two isolation check valves in the line, |

| testing was unable to determine which one was leaking.                       |

|                                                                              |

| "Based on indications of leakage during the LLRT, maintenance activities     |

| were started on one of the valves (HPCI-15CV).  Upon removal of the          |

| HPCI-15CV bonnet it was noticed that the valve was not properly seated.      |

| Engineering is continuing to evaluate this condition.  To facilitate         |

| continuing troubleshooting HPCI-15CV was manually closed by pushing the disk |

| into the valve seat.  The bonnet was re-installed and the LLRT was repeated. |

| The other check valve in this line (HPCI-44) was not touched or manipulated  |

| during the period of time between successive LLRT's.                         |

|                                                                              |

| "The results of the repeat LLRT were well within acceptance criteria limits  |

| demonstrating that HPCI-44 was properly performing its containment isolation |

| function.  Since HPCI-44 was working properly, the conditions that required  |

| an 8 hour 50.72 notification no longer apply. The penetration was always     |

| capable of performing the containment isolation function.                    |

|                                                                              |

| "The NRC Resident Inspector was notified."                                   |

|                                                                              |

| Notified R4 DO (D. Powers).                                                  |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39643       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: PERRY                    REGION:  3  |NOTIFICATION DATE: 03/07/2003|

|    UNIT:  [1] [] []                 STATE:  OH |NOTIFICATION TIME: 19:17[EST]|

|   RXTYPE: [1] GE-6                             |EVENT DATE:        03/07/2003|

+------------------------------------------------+EVENT TIME:        14:40[EST]|

| NRC NOTIFIED BY:  ROBERT KIDDER                |LAST UPDATE DATE:  03/07/2003|

|  HQ OPS OFFICER:  MIKE RIPLEY                  +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |MONTE PHILLIPS       R3      |

|10 CFR SECTION:                                 |JOHN DAVIDSON        IAT     |

|DDDD 73.71(b)(1)         SAFEGUARDS REPORTS     |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|1     N          Y       83       Power Operation  |83       Power Operation  |

|                                                   |                          |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| 1- HOUR SAFEGUARD REPORT                                                     |

|                                                                              |

| Discovery of criminal act involving individual granted access to the site.   |

| Immediate compensatory measures taken upon discovery.  Contact the           |

| Headquarters Operations Officer for details.                                 |

|                                                                              |

| The licensee notified the NRC Resident Inspector.                            |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39644       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: MILLSTONE                REGION:  1  |NOTIFICATION DATE: 03/07/2003|

|    UNIT:  [] [2] []                 STATE:  CT |NOTIFICATION TIME: 15:46[EST]|

|   RXTYPE: [1] GE-3,[2] CE,[3] W-4-LP           |EVENT DATE:        03/07/2003|

+------------------------------------------------+EVENT TIME:        14:39[EST]|

| NRC NOTIFIED BY:  JOHN CHUNIS                  |LAST UPDATE DATE:  03/07/2003|

|  HQ OPS OFFICER:  MIKE RIPLEY                  +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          UNUSUAL EVENT         |MOHAMED SHANBAKY     R1      |

|10 CFR SECTION:                                 |CHRISTOPHER GRIMES   NRR     |

|AAEC 50.72(a) (1) (i)    EMERGENCY DECLARED     |JOSEPH HOLONICH      IRO     |

|                                                |MIKE EACHES          FEMA    |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|2     A/R        Y       100      Power Operation  |0        Hot Standby      |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| PLANT DECLARED UNUSUAL EVENT DUE TO REACTOR TRIP WITH LEAKAGE FROM CHARGING  |

| SYSTEM                                                                       |

|                                                                              |

| A reactor automatic trip was received at 1439 EST.  The cause of the trip is |

| unknown and investigation continues, although reactor protection system      |

| testing was in progress at the time of the trip.  All systems responded      |

| normally with the exception of the charging system.  The licensee declared   |

| an unusual event at 1516 EST due to charging pump discharge relief valves    |

| lifting thereby creating leakage into the auxiliary building.                |

| Preliminarily, the cause of the relief valve discharge was blockage in the   |

| normal charging line downstream.  Charging flow was reestablished via the    |

| alternate flowpath.  A minimal radioactive release from the auxiliary        |

| building ventilation resulted from the charging system leakage.              |

|                                                                              |

| The NRC Resident Inspector was notified.  State and local officials were     |

| notified and the licensee issued a press release.                            |

|                                                                              |

| * * * UPDATE 0420EST ON 3/8/03 FROM ROBERT MALONEY TO S.SANDIN * * *         |

| The licensee terminated the Unusual Event at 0146EST after Unit 2 entered    |

| mode 4.  The licensee informed state/local agencies and the NRC resident     |

| inspector.  Notified R1DO(Shanbaky), EO(Grimes) and FEMA(Stinedurf).         |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39645       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: MILLSTONE                REGION:  1  |NOTIFICATION DATE: 03/07/2003|

|    UNIT:  [] [2] []                 STATE:  CT |NOTIFICATION TIME: 21:32[EST]|

|   RXTYPE: [1] GE-3,[2] CE,[3] W-4-LP           |EVENT DATE:        03/07/2003|

+------------------------------------------------+EVENT TIME:        20:49[EST]|

| NRC NOTIFIED BY:  ROBERT WHITE                 |LAST UPDATE DATE:  03/07/2003|

|  HQ OPS OFFICER:  MIKE RIPLEY                  +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          UNUSUAL EVENT         |MOHAMED SHANBAKY     R1      |

|10 CFR SECTION:                                 |JOSEPH HOLONICH      IRO     |

|AAEC 50.72(a) (1) (i)    EMERGENCY DECLARED     |CHRISTOPHER GRIMES   NRR     |

|ASHU 50.72(b)(2)(i)      PLANT S/D REQD BY TS   |FEMA WATCH OFFICER   FEMA    |

|ADEV 50.72(b)(1)         DEVIATION FROM T SPEC  |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|2     N          N       0        Hot Standby      |0        Hot Standby      |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| UNUSUAL EVENT DECLARED DUE TO INABILITY TO REACH HOT SHUTDOWN WITHIN TECH    |

| SPEC ACTION STATEMENT TIME LIMIT                                             |

|                                                                              |

| The licensee declared an unusual event at 2049 EST due to the inability to   |

| reach Mode 4  within the Technical Specification action statement time limit |

| of 2049 EST for charging pumps inoperable.  The charging pumps were declared |

| inoperable as a result of system complications associated with the reactor   |

| trip and charging system leakage occurring at 1439 EST 3/7/03 (see Event #   |

| 39644).                                                                      |

|                                                                              |

| The licensee notified the NRC Resident Inspector.                            |

|                                                                              |

| * * * UPDATE 0420EST ON 3/8/03 FROM ROBERT MALONEY TO S.SANDIN * * *         |

| The licensee terminated the Unusual Event at 0146EST after Unit 2 entered    |

| mode 4.  The licensee informed state/local agencies and the NRC resident     |

| inspector.  Notified R1DO(Shanbaky), EO(Grimes) and FEMA(Stinedurf).         |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39646       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: RIVER BEND               REGION:  4  |NOTIFICATION DATE: 03/07/2003|

|    UNIT:  [1] [] []                 STATE:  LA |NOTIFICATION TIME: 22:06[EST]|

|   RXTYPE: [1] GE-6                             |EVENT DATE:        03/07/2003|

+------------------------------------------------+EVENT TIME:        13:31[CST]|

| NRC NOTIFIED BY:  BRYAN KELLEY                 |LAST UPDATE DATE:  03/07/2003|

|  HQ OPS OFFICER:  MIKE RIPLEY                  +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |DALE POWERS          R4      |

|10 CFR SECTION:                                 |                             |

|AINC 50.72(b)(3)(v)(C)   POT UNCNTRL RAD REL    |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|1     N          Y       88       Power Operation  |88       Power Operation  |

|                                                   |                          |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| OPEN AUXILIARY BUILDING DOOR COULD HAVE CAUSED A LOSS OF SECONDARY           |

| CONTAINMENT FUNCTION                                                         |

|                                                                              |

| "At 1622 CST on 3/7/03, a Condition Report was written to identify that      |

| Auxiliary Building door PW-95-02 was open because a door assist device       |

| malfunction prevented closure of the door. This condition existed from 1331  |

| until 1449 on 3/7/03.                                                        |

|                                                                              |

| "This condition could have resulted in a loss of function of the Secondary   |

| Containment since Standby Gas Treatment system may not have been able to     |

| draw down pressure in the Auxiliary Building to the required vacuum."        |

|                                                                              |

| The licensee notified the NRC Resident Inspector.                            |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39647       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: BRUNSWICK                REGION:  2  |NOTIFICATION DATE: 03/08/2003|

|    UNIT:  [] [2] []                 STATE:  NC |NOTIFICATION TIME: 01:58[EST]|

|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        03/07/2003|

+------------------------------------------------+EVENT TIME:        23:55[EST]|

| NRC NOTIFIED BY:  DAVE JESTER                  |LAST UPDATE DATE:  03/08/2003|

|  HQ OPS OFFICER:  ARLON COSTA                  +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |CAROLYN EVANS        R2      |

|10 CFR SECTION:                                 |                             |

|AESF 50.72(b)(3)(iv)(A)  VALID SPECIF SYS ACTUAT|                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|2     N          Y       22       Power Operation  |0        Hot Shutdown     |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| AUTOMATIC DIESEL ACTUATION CAUSED BY LOSS OF GENERATION EXCITATION TRIP      |

|                                                                              |

| "During planned Unit Two manual scram in preparation for refueling outage,   |

| all four Emergency Diesel Generators received an auto start signal.  Auto    |

| start signal was generated from a Primary Generator Lockout caused by a Loss |

| of Generator ExcitatIon Trip.  A 1/2 Group 1 signal was also received during |

| the shutdown due to a steam flow trip unit failure, which has been repaired. |

| All other systems operated as designed, scram actions completed, plant       |

| stable.  The Loss of Excitation Trip should have been blocked by main        |

| generator PCB openings.  Investigation currently underway to determine cause |

| of Loss of Excitation Trip malfunction."                                     |

|                                                                              |

| There was no loss of power.  The busses were not loaded after all four       |

| diesels started. The diesels operated normally and have been returned to a   |

| standby lineup.  All other systems operated as required.                     |

|                                                                              |

| The Licensee notified the NRC Resident Inspector.                            |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39648       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: SUSQUEHANNA              REGION:  1  |NOTIFICATION DATE: 03/09/2003|

|    UNIT:  [1] [2] []                STATE:  PA |NOTIFICATION TIME: 04:08[EST]|

|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        03/09/2003|

+------------------------------------------------+EVENT TIME:        03:12[EST]|

| NRC NOTIFIED BY:  DON ROLAND                   |LAST UPDATE DATE:  03/09/2003|

|  HQ OPS OFFICER:  ARLON COSTA                  +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |MOHAMED SHANBAKY     R1      |

|10 CFR SECTION:                                 |                             |

|APRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|1     N          Y       100      Power Operation  |100      Power Operation  |

|2     N          N       0        Cold Shutdown    |0        Cold Shutdown    |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| OFFSITE NOTIFICATION                                                         |

|                                                                              |

| "On 3/9/03 at 0140 the Main Control Room was notified that an ambulance was  |

| requested at the site.  A contract pipe fitter working in Primary            |

| Containment on unit 2 experienced heat stress.  Site EMT's stabilized the    |

| individual and he was transported to a local hospital for treatment.  The    |

| individual was not contaminated.  The ambulance left site at 0216, and the   |

| Pennsylvania Emergency Management Agency was notified at 0312.  Due to       |

| notification to another government agency, this event is reportable under    |

| 10CFR50.72(b)(2)(xi)."                                                       |

|                                                                              |

| The Licensee notified the State of Pennsylvania and will notify the NRC      |

| Resident Inspector.                                                          |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39649       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: SUSQUEHANNA              REGION:  1  |NOTIFICATION DATE: 03/09/2003|

|    UNIT:  [] [2] []                 STATE:  PA |NOTIFICATION TIME: 12:08[EST]|

|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        03/08/2003|

+------------------------------------------------+EVENT TIME:        22:18[EST]|

| NRC NOTIFIED BY:  GRANT FERNSLER               |LAST UPDATE DATE:  03/09/2003|

|  HQ OPS OFFICER:  MIKE RIPLEY                  +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |MOHAMED SHANBAKY     R1      |

|10 CFR SECTION:                                 |                             |

|ACOM 50.72(b)(3)(xiii)   LOSS COMM/ASMT/RESPONSE|                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|2     N          N       0        Cold Shutdown    |0        Cold Shutdown    |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| LOSS OF EMERGENCY ASSESSMENT CAPABILITY FOR GREATER THAN 8 HOURS             |

|                                                                              |

| "On 3/9/03 the Main Control Room was notified that the Unit 2 SPDS [Safety   |

| Parameter Display System] computer was not updating properly.  A review into |

| the history identified that the SPDS computer had stopped updating at 22:18  |

| on 3/8/03.  The computer group attempted to reset the SPDS computer to       |

| correct the condition.  The reset was successful and all indication returned |

| to normal.                                                                   |

|                                                                              |

| "Since the Unit 2 SPDS computer system was unavailable for greater than 8    |

| hours, this is considered a Loss of Emergency Assessment Capability and      |

| therefore reportable under 10CFR50.72(b)(3)(xiii)."                          |

|                                                                              |

| The licensee notified the NRC Resident Inspector.                            |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39650       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: SOUTH TEXAS              REGION:  4  |NOTIFICATION DATE: 03/10/2003|

|    UNIT:  [] [2] []                 STATE:  TX |NOTIFICATION TIME: 00:46[EST]|

|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        03/09/2003|

+------------------------------------------------+EVENT TIME:        20:47[CST]|

| NRC NOTIFIED BY:  JONATHAN PIERCE              |LAST UPDATE DATE:  03/10/2003|

|  HQ OPS OFFICER:  ARLON COSTA                  +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |DALE POWERS          R4      |

|10 CFR SECTION:                                 |                             |

|AESF 50.72(b)(3)(iv)(A)  VALID SPECIF SYS ACTUAT|                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|2     N          N       0        Hot Standby      |0        Hot Standby      |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| SAFETY INJECTION SYSTEM  ACTUATION AND CAUSE UNDER INVESTIGATION             |

|                                                                              |

| "At 20:47 on 3/9/03, Unit 2 experienced a Safety Injection while the plant   |

| was stable at NOP(2235 psig)/NOT                                             |

| (567 degrees) in Mode 3.  All systems actuated as designed.  An operator was |

| operating the 'B'  S/G PORV shortly                                          |

| before the event occurred.  All MSIVs were closed for ongoing work on the    |

| main turbine. The Sequence of                                                |

| events report showed all 3 channels of steam pressure spiking low on the 'B' |

| Steam Generator as the cause of the event. Initial look at trends on the     |

| integrated computer system showed [that] steam pressure channels did not     |

| lower to a point to cause the safety injection.  An Event Review Team is     |

| being formed to investigate this event.                                      |

|                                                                              |

| "A Reactor Coolant System PORV opened due to high pressure when the Spray    |

| valves closed due to the Instrument Air isolation (due to phase 'A') with    |

| the Pressurizer Heaters in manual. The Pressurizer heaters were secured and  |

| Reactor coolant System pressure stabilized.  All ESF systems actuated as     |

| designed. The following systems actuated: Auxiliary Feedwater, Safety        |

| Injection, Phase 'A', Control Room Envelope and Fuel Handling Building HVAC  |

| systems, Essential Cooling Water, Component Cooling Water, Emergency Diesel  |

| Generators and ESF sequencers."                                              |

|                                                                              |

| There was no safety injection since pressure was maintained above 2199 psi   |

| during the transient (Hi Head is 1700 psi).  Heat removal is being performed |

| through S/G PORVs and Unit 2 is currently stable at Mode 3.                  |

|                                                                              |

| The Licensee notified the NRC Resident Inspector.                            |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39651       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: WATTS BAR                REGION:  2  |NOTIFICATION DATE: 03/10/2003|

|    UNIT:  [1] [] []                 STATE:  TN |NOTIFICATION TIME: 03:45[EST]|

|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        03/10/2003|

+------------------------------------------------+EVENT TIME:        00:12[EST]|

| NRC NOTIFIED BY:  JOHN RODEN                   |LAST UPDATE DATE:  03/10/2003|

|  HQ OPS OFFICER:  ARLON COSTA                  +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |STEPHEN CAHILL       R2      |

|10 CFR SECTION:                                 |CAROLYN EVANS        R2      |

|ARPS 50.72(b)(2)(iv)(B)  RPS ACTUATION - CRITICA|                             |

|AESF 50.72(b)(3)(iv)(A)  VALID SPECIF SYS ACTUAT|                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|1     N          Y       100      Power Operation  |0        Hot Standby      |

|                                                   |                          |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| AUTOMATIC REACTOR TRIP DUE TO TURBINE TRIP ON GENERATOR DIFFERENTIAL RELAY   |

| ACTUATION                                                                    |

|                                                                              |

| "At 0012 EST on March 10, 2003, with Watts Bar Unit 1 in Mode 1 at 100%      |

| power, the reactor tripped due to an automatic signal.  All plant safety     |

| systems were in service at the time to the trip, except  for the 2B-B diesel |

| generator which was out of service for scheduled maintenance, and all        |

| [safety systems] responded as designed.  All control rods inserted as        |

| required and the Auxiliary Feedwater System [AFW] initiated as expected.     |

|                                                                              |

| "The reactor trip resulted from a turbine trip signal that was generated as  |

| a result of a main generator/transformer differential electrical relay       |

| actuation.  The plant is currently stable in Mode 3 and will remain in this  |

| Mode until completion of the investigation."                                 |

|                                                                              |

| AFW was removed from operation and the main feed pumps have resumed normal   |

| feed to the Steam Generators.  The Licensee notified the NRC Resident        |

| Inspector.                                                                   |

+------------------------------------------------------------------------------+





                    