The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.
Event Notification Report for January 27, 2003
U.S. Nuclear Regulatory Commission
Operations Center
Event Reports For
01/24/2003 - 01/27/2003
** EVENT NUMBERS **
38513 39528 39531 39532 39535 39536 39537
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38513 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SAINT LUCIE REGION: 2 |NOTIFICATION DATE: 11/23/2001|
| UNIT: [1] [] [] STATE: FL |NOTIFICATION TIME: 12:30[EST]|
| RXTYPE: [1] CE,[2] CE |EVENT DATE: 11/23/2001|
+------------------------------------------------+EVENT TIME: 12:10[EST]|
| NRC NOTIFIED BY: CHARLIE PIKE |LAST UPDATE DATE: 01/25/2003|
| HQ OPS OFFICER: STEVE SANDIN +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |CAUDLE JULIAN R2 |
|10 CFR SECTION: | |
|APRE 50.72(b)(2)(xi) OFFSITE NOTIFICATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION TO FLORIDA STATE INVOLVING RECOVERED SEA TURTLE FROM |
| UNIT 1 INTAKE STRUCTURE |
| |
| "A sea turtle with no external injuries but appearing to be distressed was |
| recovered from the Unit 1 Intake Structure. The State Stranding Coordinator |
| for sea turtles has been contacted." |
| |
| * * * UPDATE 11/23/01 AT 1255EST FROM CHARLIE PIKE TO S. SANDIN * * * |
| |
| "Turtle has died." |
| |
| The licensee informed both the State of Florida and the NRC Resident |
| Inspector. |
| |
| * * * UPDATE 1413EST ON 12/3/01 FROM JACK BREEN TO FANGIE JONES * * * |
| |
| At approximately 1215 EST on 12/3/01, a report was made to the Florida |
| Department of Fish and Wildlife concerning the recovery of an injured sea |
| turtle from the plant's intake canal. The turtle was a green sea turtle in |
| the intake canal that appeared distressed and looked to have a wound from a |
| boat motor on its back. It will be transferred to the State for |
| rehabilitation. |
| |
| The licensee plans to notify the NRC resident inspector. Notified |
| R2DO(MacAlpine). |
| |
| * * * UPDATE 1333EST ON 12/15/01 FROM JACK BREEN TO JOHN MACKINNON * * * |
| |
| At approximately 1215 EST on 12/15/01, a report was made to the Florida |
| Department of Fish and Wildlife Conservation Commission to pick up a Green |
| Turtle for rehabilitation. The Green Turtle was taken from the plant's |
| intake canal, and the turtle appears to have shark bites. |
| |
| The licensee plans to notify the NRC resident inspector. Notified R2DO |
| (Chuck Ogle). |
| |
| * * * UPDATE 1450EST ON 01/06/02 FROM TULLIDGE TO JOHN MACKINNON * * * |
| |
| At 1350EST, a notification to the State of Florida Department of Fish and |
| Wildlife Conservation Commission was made due to finding an injured |
| Loggerhead sea turtle in Unit 1 intake. The sea turtle was transported |
| offsite for rehabilitation. R2DO (Tom Decker) notified. |
| |
| The licensee notified the NRC Resident Inspector. |
| |
| ***UPDATE 1330EST ON 4/23/02 FROM JACK BREEN TO RICH LAURA*** |
| |
| The licensee rescued a Loggerhead sea turtle from the intake canal. The |
| Florida Fish and Wildlife Conservation Commission was notified, and the |
| turtle was turned over for rehabilitation. |
| |
| The NRC Resident Inspector was informed. Notified R2DO (B. Bonser). |
| |
| ***UPDATE 1241EDT ON 5/29/02 FROM DAVE WILLIAMS TO RICHARD LAURA*** |
| |
| The licensee reported that an offsite notification was made to the Florida |
| Fish and Wildlife Conservation Commission concerning the discovery of a live |
| loggerhead sea turtle found in the plant's intake canal. The turtle was |
| lethargic and was sent for rehabilitation. |
| |
| The NRC Resident Inspector was informed. Notified R2DO (K. Landis). |
| |
| ***** UPDATE AT 1125 EDT ON 06/01/02 FROM CHARLES MARPLE TO LEIGH TROCINE |
| ***** |
| |
| The following text is a portion of a facsimile received from the licensee: |
| |
| "At 1020 on 06/01/02, a notification was made to the Florida Fish and |
| Wildlife Conservation Commission regarding a weak and emaciated Loggerhead |
| turtle found in the plant intake barrier net. The turtle will be sent |
| off-site to the Marine Life Center for Rehabilitation." |
| |
| The licensee notified the NRC resident inspector. The NRC operations |
| officer notified the R2DO (Kerry Landis). |
| |
| *****UPDATE AT 11:53 EDT ON 6/2/02 FROM MARPLE TO LAURA****** |
| |
| "A notification was made to the Florida Fish and Wildlife Conservation |
| Commission regarding a dead small green sea turtle found in the tangle net. |
| The turtle will be maintained on ice for a postmortem examination." |
| |
| The NRC resident inspector was notified. Notified R2DO (K. Landis) |
| |
| *****UPDATE AT 12:45 EDT ON 7/18/02 FROM BREEN TO LAURA****** |
| |
| A notification was made to the State regarding a dead green sea turtle that |
| was removed from the intake canal. |
| |
| The NRC resident inspector will be notified. |
| |
| Notified R2DO (C. Payne |
| |
| ***UPDATE AT 1045 EDT ON 10/20/02 FROM KORTH TO NORRIS*** |
| |
| A Loggerhead turtle was retrieved from the plant's intake canal. The turtle |
| was in need of rehabilitation. Per the plant's turtle permit, the Florida |
| Fish and Wildlife Conservation Commission (FWCC) was notified at 0927 EDT. |
| |
| The NRC Resident Inspector has been notified. |
| |
| Notified R2DO (Barr) |
| |
| * * * UPDATE AT 1338 EDT ON 10/22/02 FROM KELLY KORTH TO GERRY WAIG * * * |
| |
| A Loggerhead turtle was retrieved from the plant's intake canal. The turtle |
| was in need of rehabilitation. Per the plant's turtle permit, the Florida |
| Fish and Wildlife Conservation Commission (FWCC) was notified at 1250 EDT. |
| |
| The NRC Resident Inspector will be notified by the licensee. |
| |
| Notified R2DO (Bob Haag) |
| |
| * * * UPDATE ON 11/22/2002 @ 1821 BY FIELDS TO GOULD * * * |
| |
| The licensee notified the Florida Department of Environmental Protection of |
| the recovery of a distressed loggerhead sea turtle from their intake canal. |
| The turtle was taken to a rehabilitation facility. |
| |
| The NRC Resident inspector will be notified. Notified R2DO (David Ayres). |
| |
| * * * UPDATE AT 1320 EST ON 12/16/02 FROM BILL PARKS TO GERRY WAIG * * * |
| |
| "On 12-16-02, two loggerhead turtles were retrieved from the plant's intake |
| canal. The turtles were determined to be in need of rehabilitation. The |
| injuries to the turtles are not causal to plant operation. Per the plant's |
| turtle permit, the Florida Fish and Wildlife Conservation Commission (FWCC) |
| was notified at 1230 EST. This non-emergency notification is being made |
| pursuant to 10 CFR 50.72(b)(2)(xi) due to the notification of FWCC." |
| |
| The NRC Resident inspector will be notified. Notified R2DO (Mike Ernstes). |
| |
| * * * UPDATE AT 1350 EST ON 1/25/03 FROM DAVE FIELDS TO MIKE RIPLEY * * * |
| |
| "The State of Florida Department of Environmental Protection was notified |
| that an injured juvenile loggerhead sea turtle was retrieved from the plant |
| intake canal. The turtle was sent to a rehabilitation facility." |
| |
| The NRC Resident inspector will be notified. Notified R2DO (Ken Barr). |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|General Information or Other |Event Number: 39528 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: TEXAS DEPARTMENT OF HEALTH |NOTIFICATION DATE: 01/21/2003|
|LICENSEE: FUGRO SOUTH |NOTIFICATION TIME: 12:10[EST]|
| CITY: HOLLYWOOD PARK REGION: 4 |EVENT DATE: 01/20/2003|
| COUNTY: STATE: TX |EVENT TIME: 16:30[CST]|
|LICENSE#: L03875-002 AGREEMENT: Y |LAST UPDATE DATE: 01/21/2003|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |GREG PICK R4 |
| |TOM ESSIG NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: JIM OGDEN | |
| HQ OPS OFFICER: HOWIE CROUCH | |
+------------------------------------------------+ |
|EMERGENCY CLASS: NON EMERGENCY | |
|10 CFR SECTION: | |
|NAGR AGREEMENT STATE | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT - LOST AND SUBSEQUENTLY FOUND TROXLER MOISTURE |
| DENSITY GAUGE |
| |
| The following information was received from the Texas Department of Health, |
| Bureau of Radiation Control, Incident Investigation Group via facsimile: |
| |
| "Driver/Operator was at construction site on north side of San Antonio. |
| Reported that he placed the gauge, without transport case, on the tailgate |
| of his company pickup and completed his paperwork in the cab. When [he] |
| completed [the paperwork], he forgot the gauge was still sitting on the |
| tailgate and drove off from the site. Approximately 300 feet down the |
| access road to Loop 1604, he realized that he had not put his gauge away. |
| To return to the site, he had to loop around several access roads to get |
| back to the area. When he arrived back at the construction site, he could |
| not locate the gauge. He called his company for assistance. The company |
| sent other employees to search the entire area without result and then |
| reported the gauge missing to both the Hollywood Park and San Antonio Police |
| Departments. In a call to the Agency [Texas Department of Health] at |
| approximately 7:30 a.m. on January 21, 2003, it was reported that they |
| believe the gauge was found by another contractor who was also departing the |
| site the night before. It is believed that the gauge was put into the back |
| of [the other contractor's] truck. The gauge is a Troxler 3440, Serial |
| Number 30433, with two sealed sources: Cs-137, 8 millicuries, Serial Number |
| 750-4901: and Am-241/Be, 40 millicuries, Serial Number 47-27488. The |
| Radiation Safety Officer called at 10:53 a.m. on January 21, 2003, saying |
| the gauge was recovered at the construction site at 7:30 a.m. this morning |
| (01/21/2003) from another contractor who had found it onsite. The |
| construction superintendent, when notified at home on the evening on January |
| 20, 2003, had located the contractor who found the gauge, and arranged for |
| the pickup this morning. The RSO did not have full details but has the |
| gauge back in his possession. The gauge was visually inspected for damage |
| and no apparent damage was noted. Radiation levels were normal for the |
| gauge. However, a leak test was performed on the gauge. Results are |
| pending. Both Police Departments have been notified of the recovery. It is |
| not known if the helicopter flight was performed during the hours of |
| darkness. [Hollywood Park Police notified the FBI and arranged for a |
| helicopter to search for the gauge with infrared equipment.]" |
| |
| The vehicle was a company pick-up truck. (No description given or known by |
| reporting official.) |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 39531 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: MCGUIRE REGION: 2 |NOTIFICATION DATE: 01/24/2003|
| UNIT: [1] [] [] STATE: NC |NOTIFICATION TIME: 08:32[EST]|
| RXTYPE: [1] W-4-LP,[2] W-4-LP |EVENT DATE: 01/24/2003|
+------------------------------------------------+EVENT TIME: 00:45[EST]|
| NRC NOTIFIED BY: KEN HOFFMAN |LAST UPDATE DATE: 01/24/2003|
| HQ OPS OFFICER: MIKE NORRIS +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |KEN BARR R2 |
|10 CFR SECTION: | |
|AIND 50.72(b)(3)(v)(D) ACCIDENT MITIGATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| FAILURE OF ALL REFUELING WATER STORAGE TANK LEVEL INDICATORS |
| |
| "Event or condition that at time of discovery could have prevented the |
| fulfillment of the safety function (FWST [Refueling Water Storage Tank] Auto |
| Swap over). |
| |
| "Refueling Water Tank Level indication for all three channels failed high |
| due to failure of automatic heat tracing which resulted in instrument lines |
| freezing. Exited condition at 0342 hours on 1/24/03." |
| |
| The NRC Resident Inspector will be notified. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 39532 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: HATCH REGION: 2 |NOTIFICATION DATE: 01/24/2003|
| UNIT: [1] [2] [] STATE: GA |NOTIFICATION TIME: 11:23[EST]|
| RXTYPE: [1] GE-4,[2] GE-4 |EVENT DATE: 01/24/2003|
+------------------------------------------------+EVENT TIME: [EST]|
| NRC NOTIFIED BY: BARRY D. COLEMAN |LAST UPDATE DATE: 01/24/2003|
| HQ OPS OFFICER: ARLON COSTA +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |KEN BARR R2 |
|10 CFR SECTION: | |
|ACOM 50.72(b)(3)(xiii) LOSS COMM/ASMT/RESPONSE| |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
|2 N Y 100 Power Operation |100 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| LOSS ENS AND OFFSITE COMMUNICATION |
| |
| "A major telephone line between Plant Hatch and Uvalda [GA] was damaged |
| (cut) causing a major loss of communication system. |
| |
| "The ENS was inoperable, but the NRC could be notified by commercial line. |
| The Prompt Notification (NOAA radios) was inoperable. Approximately one |
| half of the ability to call offsite was lost (one half of the lines). |
| |
| "Note: The Prompt Notification System (NOAA radios) were returned to service |
| at 1115 [EST]. Total out of service time was 45 minutes." |
| |
| The licensee notified the NRC resident inspector. |
| |
| * * * * UPDATE RECEIVED VIA FAX AT 1601 EST ON 1/24/03 FROM BARRY COLEMAN TO |
| MIKE RIPLEY * * * * |
| |
| "We have a new update from Bell South. The line that was cut was not between |
| the plant and Uvalda [GA]. They're repairing the cable now and expect all |
| circuits to be restored by 4:00 PM. Apparently, some land clearing crews |
| were working near the buried fiber between the plant and Baxley [GA] and |
| severed BellSouth's fiber. |
| |
| "NOAA Problem - NOAA was already running on the secondary transmitter fed |
| from Baxley. When the Baxley feed was cut this morning, the whole system |
| shut down because the primary transmitter (fed from Brunswick) was already |
| in error mode, for reasons unknown to us. We powered the entire system down |
| and it started transmitting on the primary Brunswick feed as it should have |
| been." |
| |
| The licensee notified the NRC resident inspector. Notified R2 DO (K. Barr). |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 39535 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SURRY REGION: 2 |NOTIFICATION DATE: 01/25/2003|
| UNIT: [1] [] [] STATE: VA |NOTIFICATION TIME: 09:25[EST]|
| RXTYPE: [1] W-3-LP,[2] W-3-LP |EVENT DATE: 01/25/2003|
+------------------------------------------------+EVENT TIME: 07:00[EST]|
| NRC NOTIFIED BY: ALISON MacKELLAR |LAST UPDATE DATE: 01/25/2003|
| HQ OPS OFFICER: STEVE SANDIN +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |KEN BARR R2 |
|10 CFR SECTION: | |
|ARPS 50.72(b)(2)(iv)(B) RPS ACTUATION - CRITICA| |
|AESF 50.72(b)(3)(iv)(A) VALID SPECIF SYS ACTUAT| |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 A/R Y 25 Power Operation |0 Hot Shutdown |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| UNIT 1 EXPERIENCED AN AUTOMATIC REACTOR TRIP ON LO-LO STEAM GENERATOR WATER |
| LEVEL |
| |
| "At 0700 hours, with Surry Power Station Unit 1 at 25% reactor power during |
| power ascension, an automatic reactor trip was generated due to 2/3 channels |
| on 'B' S/G Lo-Lo Level. |
| |
| "All control rods fully inserted into the core as designed. Borated as |
| necessary to ensure adequate shutdown margin. The shutdown margin for Unit 1 |
| was determined to be satisfactory. 'A' and 'B' motor driven auxiliary |
| feedwater pumps automatically initiated as designed on low low steam |
| generator level following the trip. The turbine driven auxiliary feedwater |
| pump tripped. All three Main Steam Trip Valves were manually closed due to |
| the primary RCS cooldown. Primary RCS temperature decreased to approximately |
| 526 degrees. Currently RCS temperature is stable at 547 degrees on the |
| Secondary Power Operated Relief Valves. |
| |
| "No primary safety or power operated relief valves were actuated during the |
| event. No indication of primary to secondary leakage exists, therefore no |
| adverse radiological consequences resulted from this event. |
| |
| "All electrical busses remained energized following the trip and all |
| emergency diesel generators are operable. There were no radiation releases |
| due to this event, nor were there any personnel injuries or contamination |
| events. The cause of the event is being investigated. |
| |
| "Unit 1 is currently at Hot Shutdown with RCS temperature being maintained |
| at approximately 547 degrees. |
| |
| 'Unit 2 was not affected by this event and remains stable at 100% power |
| operations. |
| |
| "This event is being reported in accordance with 10CFR50.72(b)(2)(iv) and |
| 10CFR50.72(b)(3)(iv)." |
| |
| Operators were in the process of transitioning between manual and automatic |
| S/G water level control when the automatic trip occurred. The licensee will |
| investigate the cause of the automatic turbine driven auxiliary feedwater |
| pump trip. |
| |
| The licensee informed the NRC resident inspector. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 39536 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SURRY REGION: 2 |NOTIFICATION DATE: 01/25/2003|
| UNIT: [] [2] [] STATE: VA |NOTIFICATION TIME: 17:35[EST]|
| RXTYPE: [1] W-3-LP,[2] W-3-LP |EVENT DATE: 01/25/2003|
+------------------------------------------------+EVENT TIME: 14:14[EST]|
| NRC NOTIFIED BY: JOHN DUFF |LAST UPDATE DATE: 01/25/2003|
| HQ OPS OFFICER: MIKE RIPLEY +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |KEN BARR R2 |
|10 CFR SECTION: |HERB BERKOW NRR |
|ARPS 50.72(b)(2)(iv)(B) RPS ACTUATION - CRITICA| |
|AESF 50.72(b)(3)(iv)(A) VALID SPECIF SYS ACTUAT| |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
| | |
|2 A/R Y 100 Power Operation |0 Hot Shutdown |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| UNIT 2 EXPERIENCED AN AUTOMATIC REACTOR TRIP DUE TO A MAIN GENERATOR TRIP |
| |
| "At 1414 hours, with Surry Power Station Unit 2 at 100% reactor power an |
| automatic reactor trip was generated due to a main generator trip. The main |
| generator tripped due to a differential lockout. |
| |
| "Individual rod position indications (IRPI) for three control rods indicated |
| between 11 and 20 steps following the trip. An emergency boration was |
| initiated followed by a normal boration in accordance with station |
| procedures to ensure adequate shutdown margin. The shutdown margin for Unit |
| 2 was determined to be satisfactory. All other control rod indications fully |
| inserted into the core as designed. The three IRPIs that initially did not |
| indicate fully inserted slowly drifted to less that 10 steps. |
| |
| "All three auxiliary feedwater pumps automatically initiated as designed on |
| low low steam generator level following the trip. Currently RCS temperature |
| is stable at 547 degrees and being controlled by condenser steam dump |
| valves. No primary or secondary safety or power operated relief valves were |
| actuated during the event. No indications of primary to secondary leakage |
| exist. |
| |
| "All electrical busses transferred properly following the trip and all |
| emergency diesel generators are operable. At the time of the Unit 2 reactor |
| trip, Surry Unit 1 was off-line due to a previous trip. Load shed occurred |
| on the station service busses as designed. As a result of the load shed |
| signal, the Surry Unit 1 "A" Main Feed Pump tripped. The Unit 1 "B" Main |
| Feed Pump had previously been shut down. This resulted in a loss of both |
| Main Feed Pumps on Unit 1 and restarted the Unit 1 Motor Driven Auxiliary |
| Feedwater Pumps. |
| |
| "There were no radiation releases due to this event, nor were there any |
| personnel injuries or contamination events. The cause of the Unit 2 trip is |
| being investigated. |
| |
| "Unit 2 is currently at Hot Shutdown with RCS temperature being maintained |
| at approximately 547 degrees. Unit 1 is also at Hot Shutdown with RCS |
| temperature being maintained at approximately 547 degrees. |
| |
| "This event is being reported in accordance with 10CFR50.72(b)(2)(iv) and |
| 10CFR50.72(b)(3)(iv)." |
| |
| The licensee is investigating the cause of the main generator trip. The |
| licensee notified the NRC resident inspector. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 39537 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: COOK REGION: 3 |NOTIFICATION DATE: 01/26/2003|
| UNIT: [] [2] [] STATE: MI |NOTIFICATION TIME: 02:21[EST]|
| RXTYPE: [1] W-4-LP,[2] W-4-LP |EVENT DATE: 01/26/2003|
+------------------------------------------------+EVENT TIME: 00:17[EST]|
| NRC NOTIFIED BY: CHARLES ARCHEY |LAST UPDATE DATE: 01/26/2003|
| HQ OPS OFFICER: ARLON COSTA +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |CHRISTINE LIPA R3 |
|10 CFR SECTION: | |
|ASHU 50.72(b)(2)(i) PLANT S/D REQD BY TS | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
| | |
|2 N Y 100 Power Operation |55 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| PLANT SHUTDOWN REQUIRED BY TECHNICAL SPECIFICATIONS |
| |
| "Cook Nuclear Plant Unit 2 Technical Specification 3.8.1.1.b requires two |
| separate and independent diesel generators to be operable. Action b |
| specifies [that] if one diesel is inoperable, then 'restore diesel |
| generators to OPERABLE status within 72 hours or be in at least HOT STANDBY |
| within the next 6 hours and in COLD SHUTDOWN within the following 30 hours.' |
| Unit 2 diesel generator 2-OME-150-CD (Unit 2 CD diesel generator) has been |
| inoperable since 04:00 on January 23, 2003 for scheduled maintenance. |
| During post-maintenance testing, diesel load fluctuations occurred which |
| continued to render the diesel inoperable. Diagnostic testing continues on |
| the Unit 2 CD diesel generator. When it became evident operability of the |
| Unit 2 CD diesel generator would not occur by the expiration of the 72 hour |
| Limiting Condition of Operation at 04:00 on January 26, Cook Unit 2 began a |
| power reduction from 100% reactor thermal power. The power reduction began |
| at 00:17 on January 26 at a rate of approximately 20% per hour with a plan |
| to manually trip the reactor to enter Mode 3 (Hot Standby) at 17% reactor |
| thermal power at approximately 05:00. A cooldown to Mode 5 (Cold Shutdown) |
| is expected within 30 hours of the entry to Mode 3 (Hot Standby) in |
| accordance with Technical Specification 3.8.1.1, action b. |
| |
| "This Four Hour Report is being made in accordance with 10 CFR |
| 50.72(b)(2)(i) for the initiation of a nuclear plant shutdown required by a |
| plant's Technical Specifications. |
| |
| "There were no emergency plan or radiological release issues with this Unit |
| 2 event. Unit 1 remains in Mode 5 with a main transformer replacement in |
| progress." |
| |
| The Licensee notified the NRC Resident Inspector. |
| |
| * * * * UPDATE FROM CHARLES ARCHEY TAKEN BY MIKE RIPLEY AT 2310 EST ON |
| 1/26/03 * * * * |
| |
| The licensee provided the following revised wording to reflect a |
| re-evaluation of the Technical Specification requirements for the transition |
| to Mode 5 if the Unit 2 CD diesel generator remains inoperable: |
| |
| "Cook Nuclear Plant Unit 2 Technical Specification 3.8. 1. 1 .b requires two |
| separate and independent diesel generators to be operable. Action b |
| specifies if one diesel is inoperable, then 'restore diesel generators to |
| OPERABLE status within 72 hours or be in at least HOT STANDBY within the |
| next 6 hours and in COLD SHUTDOWN within the following 30 hours.' Unit 2 |
| diesel generator 2-OME-150-CD ('Unit 2 CD diesel generator') has been |
| inoperable since 04:00 on January 23, 2003 for scheduled maintenance. |
| During post-maintenance testing, diesel load fluctuations occurred which |
| continued to render the diesel inoperable. Diagnostic testing continues on |
| the Unit 2 CD diesel generator. When it became evident operability of the |
| Unit 2 CD diesel generator would not occur by the expiration of the 72 hour |
| Limiting Condition of Operation at 04:00 on January 26, Cook Unit 2 began a |
| power reduction from 100% reactor thermal power. The power reduction began |
| at 00:17 on January 26 at a rate of approximately 20% per hour with a plan |
| to manually trip the reactor to enter Mode 3 (Hot Standby) at 17% reactor |
| thermal power at approximately 05:00. |
| |
| "Transition to Mode 3 is expected after the 72 hour time limit is exceeded |
| (04:00 on January 26) and before 10:00 on January 26 (6 hours following |
| expiration of the 72 hour time limit). Transition to Mode 5 is expected |
| before 16:00 on January 27 (within the following 30 hours) if the Unit 2 CD |
| diesel generator remains inoperable. |
| |
| "This Four Hour Report is being made in accordance with 10 CFR |
| 50.72(b)(2)(i) for the initiation of a nuclear plant shutdown required by a |
| plant's Technical Specifications. |
| |
| "There were no emergency plan or radiological release issues with this Unit |
| 2 event. Unit 1 remains in Mode 5 (Cold Shutdown) with a main transformer |
| replacement in progress." R3DO (Christine Lipa) notified. |
| |
| The NRC Resident Inspector was notified of this update by the licensee. |
+------------------------------------------------------------------------------+
Page Last Reviewed/Updated Thursday, March 25, 2021
Page Last Reviewed/Updated Thursday, March 25, 2021