Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for October 11, 2002


                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           10/10/2002 - 10/11/2002

                              ** EVENT NUMBERS **

39199  39265  39266  39267  39268  

!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   39199       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PALO VERDE               REGION:  4  |NOTIFICATION DATE: 09/18/2002|
|    UNIT:  [1] [2] [3]               STATE:  AZ |NOTIFICATION TIME: 17:10[EDT]|
|   RXTYPE: [1] CE,[2] CE,[3] CE                 |EVENT DATE:        09/17/2002|
+------------------------------------------------+EVENT TIME:        16:52[MST]|
| NRC NOTIFIED BY:  DAN MARKS                    |LAST UPDATE DATE:  10/10/2002|
|  HQ OPS OFFICER:  RICH LAURA                   +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |DAVE LOVELESS        R4      |
|10 CFR SECTION:                                 |                             |
|NONR                     OTHER UNSPEC REQMNT    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       99       Power Operation  |99       Power Operation  |
|2     N          Y       98       Power Operation  |98       Power Operation  |
|3     N          Y       99.6     Power Operation  |99.6     Power Operation  |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| HEAT BALANCE CALCULATION ERROR  ON REACTOR POWER                             |
|                                                                              |
| "The following event description is based on information currently           |
| available. It through subsequent reviews of this event, additional           |
| information is identified that Is pertinent to this event or alters the      |
| information being provided at this time, a follow-up notification will be    |
| made via the ENS or under the reporting requirements of 10CFR50.73.          |
|                                                                              |
| "Palo Verde Nuclear Generating Station Units 1, 2, and 3 are evaluating the  |
| potential that the Maximum Power Level of 3876 megawatts thermal (100%       |
| power), specified in Operating License Condition 2.C(1) may have been        |
| exceeded in the past due to an unconservative value of reactor coolant pump  |
| (RCP) heat in the secondary calorimetric calculation since initial plant     |
| operation. The value of total energy input due to RCP operation used in the  |
| calorimetric is 29.53 megawatts (MW) in Unit 1,  29.61 MW in Unit 2 and      |
| 31.88 MW In Unit 3. Conservative engineering calculation of actual RCP heat  |
| input based on electrical load is as low as 24.72 MW. Similarly,             |
| conservative engineering calculation of actual RCP heat input based on fluid |
| power (pump differential pressure) is as low as 22.86 MW. Thus, the          |
| calorimetric error may be as large as (31.88-22.86) 9.02 MW or approximately |
| 0.23%.                                                                       |
|                                                                              |
| "The error could have resulted in core power levels above the Operating      |
| License limit of 3876 MW thermal. Due to current operating limitations on    |
| reactor coolant system hot leg temperature, none of the Palo Verde units are |
| presently exceeding the licensed power limit. Unit 1 is at approximately 99% |
| power (3837 MW thermal, 39 MW margin). Unit 2 is at approximately 98% power  |
| (3798 MW thermal, 78 MW margin). Unit 3 is at approximately 99.6% power      |
| (3861 MW thermal, 15 MW margin)                                              |
|                                                                              |
| "This report is being made because a review of historical operating data may |
| reveal that the Maximum Power Level was exceeded.                            |
|                                                                              |
| "The Palo Verde safety analyses bound a power level of 102%, thus the Units  |
| remain within the safety analyses. As a compensatory measure, the station    |
| has established an administrative limit of 99.75% power pending resolution   |
| of this issue.                                                               |
|                                                                              |
| "No ESF actuations occurred and none were required. There were no            |
| structures, systems, or components that were inoperable at the time of       |
| discovery that contributed to this condition. There were no failures that    |
| rendered a train of a safety system inoperable and no failures of components |
| with multiple functions were involved. The event did not result in the       |
| release of radioactivity to the environment and did not adversely affect the |
| safe operation of the plant or health and safety of the public."             |
|                                                                              |
| The NRC Resident Inspector has been notified.                                |
|                                                                              |
| * * * RETRACTION FROM DANIEL HAUTALA ON OCTOBER 10, 2002 AT 1534 EDT TO MIKE |
| RIPLEY  * * *                                                                |
|                                                                              |
| "The following event description is based on information currently           |
| available. If through subsequent reviews or this event, additional           |
| information is identified that is pertinent to this event or alters the      |
| information being provided at this time, a follow-up notification will be    |
| made via the ENS or under the reporting requirements of 10CFR50.73.          |
|                                                                              |
| "This notification is a retraction to the September 17, 2002, ENS #39199     |
| which reported a calorimetric input error that could have resulted in core   |
| power levels above the Operating License limit of 3876 MW thermal at Palo    |
| Verde Nuclear Generating Station Units 1, 2, and 3. Further evaluation of    |
| the calorimetric power calculation indicated the installed values were       |
| conservative and no correction is required.                                  |
|                                                                              |
| "The NRC Resident Inspector has been notified."                              |
|                                                                              |
| Notified R4 DO (William Jones)                                               |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   39265       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SUSQUEHANNA              REGION:  1  |NOTIFICATION DATE: 10/10/2002|
|    UNIT:  [1] [] []                 STATE:  PA |NOTIFICATION TIME: 00:20[EDT]|
|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        10/10/2002|
+------------------------------------------------+EVENT TIME:        00:08[EDT]|
| NRC NOTIFIED BY:  ROBERT BOESCH                |LAST UPDATE DATE:  10/10/2002|
|  HQ OPS OFFICER:  MIKE NORRIS                  +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |JOHN WHITE           R1      |
|10 CFR SECTION:                                 |                             |
|ASHU 50.72(b)(2)(i)      PLANT S/D REQD BY TS   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| TECH SPEC REQUIRED SHUTDOWN DUE TO FAILURE TO MEET 2 OFFSITE POWER SUPPLIES  |
|                                                                              |
| "Susquehanna Unit 1 initiated a Technical Specification required shutdown    |
| due to failure to meet LCO 3.8.1 Action A.3 and the Notice of Enforcement    |
| Discretion (Docket No. 50-387), for operating with one inoperable offsite    |
| power supply. The offsite power supply was originally lost due to a          |
| Transformer failure on 10/3/02 at 0230 est. The NOED allowed Unit One to     |
| continue operation until 10/1 0/02 at 0230. The shutdown requirements of LCO |
| 3.8.1 Action F (Mode 3 within 12 hours and Mode 4 within 36 hours) are being |
| implemented. It has been determined that replacement activities of the       |
| transformer will not be completed in time to meet the NOED, and therefore    |
| shutdown of unit 1 has been initiated as of 0008.                            |
|                                                                              |
| "This event is a Technical Specification required shutdown, and is           |
| reportable as a four hour ENS Notification under 10 CFR 50.72(b)(2)(I)."     |
|                                                                              |
| The Licensee has notified the NRC Resident Inspector.                        |
|                                                                              |
| ***UPDATE 1113 EDT 10/10/02 ART FITCH TO MIKE NORRIS***                      |
|                                                                              |
| "At 09:35 hours on 10/10/2002 transformer T-20 was successfully connected to |
| start-up bus 20 restoring the second offsite power source. This allowed Unit |
| 1 to exit LCO 3.8.1 Action F and LCO 3.8.1 Action A.3 and the Notice of      |
| Enforcement Discretion (Docket No. 50-387). Power reduction was halted at    |
| 31% and plans are currently underway to restore Unit 1 to 100% power.        |
|                                                                              |
| "Unit 2 continues in Mode 4."                                                |
|                                                                              |
| The Licensee has notified the NRC Resident Inspector and plans a press       |
| release.                                                                     |
|                                                                              |
| Notified R1DO (White).                                                       |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   39266       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CALVERT CLIFFS           REGION:  1  |NOTIFICATION DATE: 10/10/2002|
|    UNIT:  [1] [2] []                STATE:  MD |NOTIFICATION TIME: 10:29[EDT]|
|   RXTYPE: [1] CE,[2] CE                        |EVENT DATE:        10/10/2002|
+------------------------------------------------+EVENT TIME:        09:45[EDT]|
| NRC NOTIFIED BY:  JAMES GROOMS                 |LAST UPDATE DATE:  10/10/2002|
|  HQ OPS OFFICER:  MIKE NORRIS                  +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |JOHN WHITE           R1      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 4 HOUR OFFSITE NOTIFICATION TO MD DEPARTMENT OF ENVIRONMENT                  |
|                                                                              |
| A sample of drinking water taken during a routine test come up positive for  |
| Coliform(which is a bacteria).  The levels are still low enough as not to    |
| preclude the use of this water for drinking. The licensee has contacted the  |
| MD Department of Environment to take and test additional samples.            |
|                                                                              |
| The licensee has notified the NRC Resident Inspector.                        |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   39267       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SALEM                    REGION:  1  |NOTIFICATION DATE: 10/10/2002|
|    UNIT:  [1] [] []                 STATE:  NJ |NOTIFICATION TIME: 23:08[EDT]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        10/10/2002|
+------------------------------------------------+EVENT TIME:        20:16[EDT]|
| NRC NOTIFIED BY:  ROBERT MELTON                |LAST UPDATE DATE:  10/10/2002|
|  HQ OPS OFFICER:  GERRY WAIG                   +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |JOHN WHITE           R1      |
|10 CFR SECTION:                                 |                             |
|AESF 50.72(b)(3)(iv)(A)  VALID SPECIF SYS ACTUAT|                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     M/R        Y       20       Power Operation  |0        Hot Standby      |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AUXILIARY FEEDWATER START ON PLANNED MANUAL REACTOR TRIP                     |
|                                                                              |
| THIS 8 HOUR NOTIFICATION IS BEING MADE TO REPORT THAT SALEM UNIT 1 HAD       |
| EXPERIENCED A 13 AUXILIARY FEED WATER PUMP AUTO START. THIS AUTO START       |
| OCCURRED FOLLOWING A PLANNED MANUAL REACTOR TRIP FOR A SHUTDOWN FOR          |
| REFUELING. 11 & 12 AFW PUMPS WERE STARTED MANUALLY PRIOR TO THE TRIP PER     |
| PROCEDURE. THE 13 AFW PUMP STARTED POST TRIP DUE TO VALID STEAM GENERATOR    |
| LOW LEVELS WHICH ARE EXPECTED ON A REACTOR TRIP. THE STEAM GENERATOR LOW     |
| LEVEL AUTO START SET POINT WAS RAISED FROM 9% TO 14% EARLIER THIS YEAR BASED |
| ON INDUSTRY EVENTS. THIS MADE THE 13 AFW PUMP AUTO START MORE LIKELY DURING  |
| A PLANT TRIP.                                                                |
| POST TRIP MAIN FEEDWATER TO THE STEAM GENERATORS WAS ISOLATED DUE TO THE     |
| 'FEED WATER INTERLOCK' WHICH IS EXPECTED WITH A REACTOR TRIP. 13 AFW PUMP    |
| HAS BEEN SHUTDOWN BY PROCEDURE SINCE 11 & 12 AFW PUMPS ARE MAINTAINING       |
| ADEQUATE FEED FLOW. SALEM UNIT 1 IS CURRENTLY IN MODE 3. REACTOR COOLANT     |
| SYSTEM TEMPERATURE IS 547 DEGREES (F) WITH PRESSURE AT 2235 PSIG. THERE WERE |
| TWO SHUT DOWN TECHNICAL SPECIFICATIONS IN EFFECT PRIOR TO THE TRIP; ONE      |
| ASSOCIATED WITH THE 11 & 12 AFW PUMPS INOPERABLE BY PROCEDURE DUE TO THEIR   |
| FLOW CONTROL VALVES BEING CLOSED PRIOR TO THE MANUAL REACTOR TRIP. THE       |
| SECOND SHUT DOWN TECHNICAL SPECIFICATION IN EFFECT WAS ASSOCIATED WITH THE   |
| 13 CONTAINMENT FAN COIL UNIT WHICH WAS TAGGED FOR REPAIR OF A LEAK. THE 11 & |
| 12 AFW PUMPS ARE NOW OPERABLE. THE FOLLOWING MAJOR SECONDARY EQUIPMENT WAS   |
| TAGGED FOR MAINTENANCE: 13A CIRCULATING WATER PUMP, 12 HEATER DRAIN PUMP AND |
| 11 CONDENSATE PUMP.                                                          |
|                                                                              |
| THE NRC RESIDENT INSPECTOR WAS NOTIFIED OF THIS EVENT BY THE LICENSEE.       |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   39268       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: HATCH                    REGION:  2  |NOTIFICATION DATE: 10/10/2002|
|    UNIT:  [1] [] []                 STATE:  GA |NOTIFICATION TIME: 23:10[EDT]|
|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        10/10/2002|
+------------------------------------------------+EVENT TIME:        22:22[EDT]|
| NRC NOTIFIED BY:  GARY BRINSON                 |LAST UPDATE DATE:  10/10/2002|
|  HQ OPS OFFICER:  GERRY WAIG                   +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |GEORGE MCDONALD      R2      |
|10 CFR SECTION:                                 |                             |
|AESF 50.72(b)(3)(iv)(A)  VALID SPECIF SYS ACTUAT|                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     M/R        Y       50       Power Operation  |0        Hot Shutdown     |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| RECEIVED A GROUP II ISOLATION DURING A PLANNED REACTOR SCRAM                 |
|                                                                              |
| "Inserted Manual Scram for planned outage. Received a Group II isolation     |
| (containment isolation valves) on RWL [less than] 3". Lowest indication      |
| level -10". Group II isolation confirmed by STA." Plant shutdown to replace  |
| 3 SRVs. All system operate properly.                                         |
|                                                                              |
| The NRC Resident Inspector was notified of this event by the licensee..      |
+------------------------------------------------------------------------------+