Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for September 20, 2002


                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           09/19/2002 - 09/20/2002

                              ** EVENT NUMBERS **

38602  39194  39200  39202  

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38602       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CRYSTAL RIVER            REGION:  2  |NOTIFICATION DATE: 01/01/2002|
|    UNIT:  [3] [] []                 STATE:  FL |NOTIFICATION TIME: 10:08[EST]|
|   RXTYPE: [3] B&W-L-LP                         |EVENT DATE:        01/01/2002|
+------------------------------------------------+EVENT TIME:        09:19[EST]|
| NRC NOTIFIED BY:  BILL BANDHAUER               |LAST UPDATE DATE:  09/19/2002|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |ANNE BOLAND          R2      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|3     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION DUE RESCUED SEA TURTLE                                  |
|                                                                              |
| EN #37902 started the biennial report period.                                |
|                                                                              |
| On January 1, 2002 at 0919, a rescued sea turtle was identified as a green   |
| sea turtle.  This is the 62nd rescue of a live sea turtle at Crystal River   |
| Unit 3 (CR-3) in this biennial period. Notification to the National Marine   |
| Fisheries Service and the Florida Fish and Wildlife Conservation Commission. |
|                                                                              |
|                                                                              |
| The licensee intends to notify the NRC Resident Inspector.                   |
|                                                                              |
| * * *  UPDATE ON 1/05/02 @ 1002 BY RAWLS TO GOULD  * * *                     |
|                                                                              |
| On January 5, 2002, at 0720, a rescued sea turtle was identified as a        |
| Loggerhead Sea Turtle. This is the 63rd rescue of a live sea turtle at       |
| Crystal River Unit 3 (CR3) in this biennial period.  This is reportable as a |
| 4-hour report under 10 CFR 50.72(b)(2)(xi) as this event is related to the   |
| protection of the environment for which a notification to other government   |
| agencies (National Marine Fisheries Service and Florida Fish and Wildlife    |
| Conservation Commission) has been or will be made.                           |
|                                                                              |
| The NRC Resident Inspector was notified.                                     |
|                                                                              |
| Reg 2 RDO (Decker) was notified.                                             |
|                                                                              |
| * * * UPDATE ON 01/09/02 @ 1107 EST BY ANDY BARNES TAKEN BY MACKINNON * * *  |
|                                                                              |
| On January 9, 2002, at 0838, a rescued sea turtle was identified as a Kemp's |
| Ridley Sea Turtle. This is the 64th rescue of a live turtle at Crystal River |
| Unit 3 (CR-3) in this biennial period. This is reportable as a 4-hour 10 CFR |
| 50.72(b)(2)(xi) as this event is related to the protection of the            |
| environment for which a notification to other government agencies (National  |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation          |
| Commission) has been or will be made.                                        |
|                                                                              |
| The NRC Resident Inspector was notified.                                     |
|                                                                              |
| Reg 2 (Brian Bonser) was notified.                                           |
|                                                                              |
| * * * UPDATE ON 02/17/02 at 0940 EST BY RICKY RAWLS TO FANGIE JONES * * *    |
|                                                                              |
| "On February 17, 2002 at 0820, a rescued injured sea turtle was identified   |
| as a Kemp's Ridley Sea Turtle. The injury will require transportation to     |
| Clearwater Marine Science Center or Florida Fish and Wildlife Conservation   |
| Refuge. The Injury appears to be from a boat propeller. This is the 65th     |
| rescue of a live sea turtle at Crystal River Unit 3 (CR-3) in this biennial  |
| period. This is Reportable as a 4-Hour Report under 10 CFR 50.72(b)(2)(xi)   |
| as this event is related to the protection of the environment for which a    |
| notification to other government agencies (National Marine Fisheries Service |
| and Florida Fish and Wildlife Conservation Commission) has been or will be   |
| made. This Is an update to event 38602."                                     |
|                                                                              |
| The NRC Resident Inspector will be notified.  R2DO (Stephen Cahill) has been |
| notified.                                                                    |
|                                                                              |
| * * * UPDATE ON 03/01/02 AT 1122 EST BY RICKY RAWLS TO GERRY WAIG * * *      |
|                                                                              |
| "On March 1, 2002 at 0952, a healthy rescued sea turtle was identified as a  |
| Green Sea Turtle. This is the 66th rescue of a live sea turtle at Crystal    |
| River Unit 3 (CR-3) in this biennial period. This is Reportable as a 4-Hour  |
| Report under 10 CFR 50.72(b)(2)(xi) as this event is related to the          |
| protection of the environment for which a notification to other government   |
| agencies (National Marine Fisheries Service and Florida Fish and Wildlife    |
| Conservation Commission) has been or will be made. This is an update to      |
| event 38602."                                                                |
|                                                                              |
| The NRC Resident Inspector was notified. R2DO (Julian) was notified.         |
|                                                                              |
| * * * UPDATE ON 03/07/02 AT 1114 EST BY CHUCK MORRIS TO MIKE NORRIS * * *    |
|                                                                              |
| "On March 7, 2002 at 0835, two healthy sea turtles rescued at CR#3 were      |
| identified as Green Sea Turtles. These are the 67th and 68th live sea turtle |
| rescues at the Crystal River Energy Complex in this biennial period. This is |
| Reportable as a 4-Hour Report under 10 CFR 50.72(b)(2)(xi) as this event is  |
| related to the protection of the environment for which a notification to     |
| other government agencies (National Marine Fisheries Service and Florida     |
| Fish and Wildlife Conservation Commission) has been or will be made. This is |
| an update to event 38602."                                                   |
|                                                                              |
| The NRC Resident Inspector was notified. R2DO (Henson) was notified.         |
|                                                                              |
| * * * UPDATE ON 04/02/02 at 0408 EST BY RICKY RAWLS TO FANGIE JONES * * *    |
|                                                                              |
| "On April 2, 2002 at 0236, two sea turtles previously rescued at CR#3 intake |
| area were identified by FPC Mariculture staff as Kemp Ridley Sea Turtles.    |
| One of the turtles appears to be in distress and may require transportation  |
| to Clearwater Marine Science Center of Florida Fish and Wildlife             |
| Conservation Refuge. These are the 69th and 70th live sea turtle rescues at  |
| the Crystal River Energy Complex in this biennial period. This is Reportable |
| as a 4-Hour Report under 10 CFR 50.72(b)(2)(xi) as this event is related to  |
| the protection of the environment for which a notification to other          |
| government agencies (National Marine Fisheries Service and Florida Fish and  |
| Wildlife Conservation Commission) has been or will be made. This is an       |
| update to event 38602."                                                      |
|                                                                              |
| The NRC Resident Inspector will be notified.  The R2DO (Carolyn Evans) was   |
| notified.                                                                    |
|                                                                              |
| ***** UPDATE AT 1023 EDT ON 05/19/02 FROM PELLERIN TO LEIGH TROCINE *****    |
|                                                                              |
| The following text is a portion of a facsimile received from the licensee:   |
|                                                                              |
| "On May 19, 2002, at 0916, a sea turtle previously rescued at CR#3 intake    |
| area was identified by FPC Mariculture staff as Green Sea Turtle.  This is   |
| the 71st live sea turtle rescue at the Crystal River Energy Complex in this  |
| biennial period.  This is Reportable as a 4-Hour Report under 10 CFR         |
| 50.72(b)(2)(xi) as this event is related to the protection of the            |
| environment for which a notification to other government agencies (National  |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation          |
| Commission) has been or will be made.  This is an update to event 38602."    |
|                                                                              |
| The licensee plans to notify the National Marine Fisheries Service and       |
| Florida Fish and Wildlife Conservation Commission and the NRC resident       |
| inspector.  The NRC operations officer notified the R2DO (Paul               |
| Fredrickson).                                                                |
|                                                                              |
| * * * UPDATE 1816 EDT ON 5/28/02 FROM BERRY FOSTER TO S. SANDIN * * *        |
|                                                                              |
| "On May 28, 2002 at 1700, a sea turtle previously rescued at CR#3 intake     |
| area was identified by FPC Mariculture staff as a Green Sea Turtle. This is  |
| the 72nd live sea turtle rescue at the Crystal River Energy Complex in this  |
| biennial period. The turtle is being transported to the Clearwater Marine    |
| Science Center. This is Reportable as a 4-Hour Report under 10 CFR 50.72 (b) |
| (2) (xi) as this event is related to the protection of the environment for   |
| which a notification to other government agencies (National Marine Fisheries |
| Service and Florida Fish and Wildlife Conservation Commission) has been or   |
| will be made. This is an update to event 38602."                             |
|                                                                              |
| The licensee will inform the NRC Resident Inspector.  Notified               |
| R2DO(Landis).                                                                |
|                                                                              |
| * * * UPDATE 1602 EDT ON 5/31/02 FROM BILL BANDHAUER TO MIKE NORRIS * * *    |
|                                                                              |
| "On May 30, 2002 at 1323, a sea turtle previously rescued at CR#3 intake     |
| area was identified by FPC Mariculture staff as a Kemp's Ridley Sea Turtle.  |
| This is the 72nd live sea turtle rescue at the Crystal River Energy Complex  |
| in this biennial period. (Note: The sequential numbering of the live sea     |
| turtle takes has been modified to reflect the actual live sea turtle takes,  |
| On 4/02/02, a live rescue of two turtles was reported, however, one of the   |
| turtles died and was reclassified as a non-causal mortality, which is        |
| non-reportable). This event is Reportable as a 4-Hour Report under 10 CFR    |
| 50.72(b) (2) (xi) as this event is related to the protection of the          |
| environment for which a notification to other government agencies (National  |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation          |
| Commission) has been or will be made. This is an update to event 38602."     |
|                                                                              |
| The NRC Resident Inspector has been notified.  Notified R2DO (Landis).       |
|                                                                              |
| *****UPDATE AT 13:58 EDT ON 7/18/02 FROM SWEENEY TO LAURA*****               |
|                                                                              |
| An offsite notification to the State regarding a green sea turtle that was   |
| rescued from the CR#3 intake area by the FPC Mariculture staff.              |
|                                                                              |
| The NRC resident inspector was notified.  Notified R2DO (C. Payne).          |
|                                                                              |
| * * * UPDATE 1126 EDT ON 8/1/02 FROM BILL BANDHAUER TO FANGIE JONES * * *    |
|                                                                              |
| "At 0915 on August 1,2002, a dead sea turtle recovered at the CR#3 intake    |
| area was identified by FPC Mariculture staff as a Kemps Ridley Turtle. FPC   |
| determined that the cause of death was non-causally related to the operation |
| of CR3. This is the 7th dead Kemps Ridley Turtle recovery at the Crystal     |
| River Energy Complex in this biennial period. The threshold for reporting    |
| non-causal sea turtle deaths is 6 in a biennial period. This event is        |
| Reportable as a 4-Hour Report under 10 CFR 50.72 (b) (2) (xi) as this event  |
| is related to the protection of the environment for which a notification to  |
| other government agencies (National Marine Fisheries Service and Florida     |
| Fish and Wildlife Conservation Commission) will be made. This is an update   |
| to event 38602."                                                             |
|                                                                              |
| The licensee intends to notify the NRC Resident Inspector.  The R2DO (Mike   |
| Ernstes) has been notified.                                                  |
|                                                                              |
| * * * UPDATE 1529 EDT ON 8/8/02 FROM DAN DeBOER TO GERRY WAIG * * *          |
|                                                                              |
| "At 1234 on August 8, 2002, FPC determined that the dead Kemps-Ridley sea    |
| turtle recovered at 1930 on May 11, 2002, at the Crystal River Unit 3 intake |
| area was reportable as a 4-Hour Report under 10 CFR 50.72 (b) (2) (xi). This |
| event is related to the protection of the environment for which a            |
| notification to other government agencies (National Marine Fisheries Service |
| and Florida Fish and Wildlife Conservation Commission) has been made. At     |
| 1347 on May 13, 2002 the FPC Mariculture Center determined that the cause of |
| death was non-causally related to the operation of Crystal River Unit 3.     |
| This was the 6th non-causal dead turtle recovery at the Crystal River Energy |
| Complex in this biennial period. The threshold for reporting non-causal sea  |
| turtle deaths is 6 in a biennial period. This is an update to event 38602."  |
|                                                                              |
| The licensee notified the NRC Resident Inspector. The R2DO (Claude Julian)   |
| has been notified.                                                           |
|                                                                              |
| ***UPDATE 11:10 EDT ON 8/20/02 FROM McCallum to LAURA***                     |
|                                                                              |
| "On August 20, 2002 at 0932, a sea turtle previously rescued at CR#3 intake  |
| area was identified by FPC Mariculture staff as a Kemp's Ridley Sea Turtle.  |
| This is the 74th live sea turtle rescue at the Crystal River Energy Complex  |
| in this biennial period. This event is Reportable as a 4-Hour Report under   |
| 10 CFR 50.72(b) (2) (xi) as this event is related to the protection of the   |
| environment for which a notification to other government agencies (National  |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation          |
| Commission) has been or will be made. This is an update to event 38602."     |
|                                                                              |
| The licensee notified the NRC Resident Inspector.  The R2DO (M. LESSER) has  |
| been notified.                                                               |
|                                                                              |
| * * * UPDATE 1449 EDT ON 09/10/02 FROM BILL BANDHAUER TO G. WAIG * * *       |
|                                                                              |
| "On September 10, 2002 at 1328, a sea turtle previously rescued at CR#3      |
| intake area was identified by FPC Mariculture staff as a Kemp's Ridley Sea   |
| Turtle. This is the 75th live sea turtle rescue at the Crystal River Energy  |
| Complex in this biennial period. This event is Reportable as a 4-Hour Report |
| under 10 CFR 50.72 (b) (2) (xi) as this event is related to the protection   |
| of the environment for which a notification to other government agencies     |
| (National Marine Fisheries Service and Florida Fish and Wildlife             |
| Conservation Commission) has been or will be made. This is an update to      |
| event 38602."                                                                |
|                                                                              |
| The licensee will notify the NRC Resident Inspector. The R2DO (Jack Whitten) |
| was notified by the Hq Ops Officer.                                          |
|                                                                              |
| ****UPDATE 18:35 EDT on 9/19/02 FROM SWEENEY TO LAURA****                    |
|                                                                              |
| "On September 19, 2002 at 1730, a sea turtle was rescued at CR#3 intake area |
| and identified by FPC Mariculture as a Green Sea Turtle. This is the 76th    |
| live sea turtle resue at the Crystal River Energy Complex in this biennial   |
| period. The event is reportable as a 4-Hour Report under 10 CFR 50.72 (b)    |
| (2) (xi) as this event is related to the proptection of the environment for  |
| which a notification to other government agencies (National Marine Fisheries |
| Service and Florida Fish and Wildlife Conservation Commission) has been or   |
| will be made. This is an update to event 38602."                             |
|                                                                              |
| The licensee intends to notify the NRC Resident Inspector.  Notified R2DO    |
| (Fredrickson).                                                               |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   39194       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  ILLINOIS DEPT OF NUCLEAR SAFETY      |NOTIFICATION DATE: 09/17/2002|
|LICENSEE:  ILLINOIS ROOF CONSULTING ASSOC. INC  |NOTIFICATION TIME: 10:25[EDT]|
|    CITY:  CHICAGO                  REGION:  3  |EVENT DATE:        09/16/2002|
|  COUNTY:                            STATE:  IL |EVENT TIME:        14:35[CDT]|
|LICENSE#:  IL-01713-01           AGREEMENT:  Y  |LAST UPDATE DATE:  09/17/2002|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |ANNE MARIE STONE     R3      |
|                                                |FRED BROWN           NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  STEVE COLLINS                |                             |
|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| STOLEN TROXLER MODEL 3216 GAUGE                                              |
|                                                                              |
| During the afternoon of September 16, 2002, a roof moisture gauge in its     |
| locked case was stolen from a locked van belonging to an Illinois            |
| Radioactive Material Licensee--IL Roof Consulting Associates, Inc. with      |
| license IL-01713-01.  The Radiation Safety Officer (RSO) reported the        |
| break-in and theft to the IDNS and the Chicago Police within an hour of the  |
| theft.  The gauge was a Troxler Model 3216, Serial Number 00173 with 40      |
| millicuries of americium-241and was used for roofing moisture measurements.  |
| The van was parked in front of a Chicago public school while two workers     |
| were on the roof of the school--Leif Ericson Scholastic Academy--at 3600 W.  |
| 5th Avenue, Chicago.  Near the end of the job the RSO had joined the two     |
| workers and then discovered the theft that occurred approximately 1435 as he |
| was returning to the van with a second gauge that had been in use.  The      |
| windows of the van were tinted to reduce visibility except for the drivers   |
| side window.                                                                 |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   39200       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: RIVER BEND               REGION:  4  |NOTIFICATION DATE: 09/19/2002|
|    UNIT:  [1] [] []                 STATE:  LA |NOTIFICATION TIME: 00:41[EDT]|
|   RXTYPE: [1] GE-6                             |EVENT DATE:        09/18/2002|
+------------------------------------------------+EVENT TIME:        20:25[CDT]|
| NRC NOTIFIED BY:  DON CHASE                    |LAST UPDATE DATE:  09/19/2002|
|  HQ OPS OFFICER:  GERRY WAIG                   +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |DAVE LOVELESS        R4      |
|10 CFR SECTION:                                 |                             |
|ARPS 50.72(b)(2)(iv)(B)  RPS ACTUATION - CRITICA|                             |
|AESF 50.72(b)(3)(iv)(A)  VALID SPECIF SYS ACTUAT|                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     A/R        Y       100      Power Operation  |0        Hot Shutdown     |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| REACTOR SCRAM DUE TO AUTOMATIC REACTOR PROTECTION SYSTEM ACTUATION           |
|                                                                              |
| "A reactor scram occurred at River Bend Station @ 2025 on 09/18/02. The      |
| plant was operating at 100% reactor power at the time of the scram. The      |
| plant systems performed as required post scram. Reactor pressure and water   |
| level are stable with reactor level being controlled by the reactor core     |
| isolation cooling system. This event is being reported pursuant to l0 CFR    |
| 50.72 (b)(2)(IV) B (1) a reactor protection system (RPS) scram while         |
| critical (a 4 hour report) and a manual actuation of the reactor core        |
| isolation cooling system (RCIC) pursuant to 10 CFR 50.72 (b)(3)(IV) B (5).   |
| The cause of the scram is still under investigation."                        |
|                                                                              |
| The licensee reported that all control rods fully inserted during the scram  |
| and that there was no indication of SRV actuation during the event.          |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   39202       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: MCGUIRE                  REGION:  2  |NOTIFICATION DATE: 09/20/2002|
|    UNIT:  [1] [] []                 STATE:  NC |NOTIFICATION TIME: 04:12[EDT]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        09/20/2002|
+------------------------------------------------+EVENT TIME:        01:12[EDT]|
| NRC NOTIFIED BY:  TIM JOHNSON                  |LAST UPDATE DATE:  09/20/2002|
|  HQ OPS OFFICER:  STEVE SANDIN                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |PAUL FREDRICKSON     R2      |
|10 CFR SECTION:                                 |                             |
|AESF 50.72(b)(3)(iv)(A)  VALID SPECIF SYS ACTUAT|                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Refueling        |0        Refueling        |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| INADVERTENT ACTUATION OF BLACKOUT SIGNAL ON UNIT 1 DURING SURVEILLANCE       |
| TESTING                                                                      |
|                                                                              |
| "Inadvertent Actuation of B Train Blackout Signal on Unit 1. Actuation       |
| occurred during testing of the 1B Diesel Generator sequence panel. The       |
| actuation caused the B Train Nuclear Service Water System to realign to the  |
| standby Nuclear Service Water Pond on both Unit 1 and Unit 2. Unit 2 was not |
| affected due to the realignment. The Unit 1 Boric Acid pump transfer pump    |
| automatically secured and various containment and Auxiliary Building         |
| Ventilation components were affected due to the actuation. The procedure     |
| used for testing the sequencer simulated an undervoltage signal on the B     |
| Train Emergency Bus. Plans are being evaluated to restore the sequencer from |
| the test alignment and realign all affected equipment."                      |
|                                                                              |
| Reactor residual heat removal cooling was not affected by this event. Spent  |
| fuel pool cooling was not affected by this event. Electrical buses remained  |
| energized and no EDG autostart occurred since the blackout signal was        |
| simulated and not based on an actual undervoltage condition.  The licensee   |
| is attributing the cause preliminarily to an inadequate procedure.           |
|                                                                              |
| The licensee will notify the NRC Resident Inspector.                         |
+------------------------------------------------------------------------------+