Event Notification Report for September 10, 2002
Operations Center Event Reports For 09/09/2002 - 09/10/2002 ** EVENT NUMBERS ** 39175 39178 39179 +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 39175 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: POINT BEACH REGION: 3 |NOTIFICATION DATE: 09/09/2002| | UNIT: [1] [2] [] STATE: WI |NOTIFICATION TIME: 13:58[EDT]| | RXTYPE: [1] W-2-LP,[2] W-2-LP |EVENT DATE: 09/09/2002| +------------------------------------------------+EVENT TIME: 10:08[CDT]| | NRC NOTIFIED BY: RICK ROBBINS |LAST UPDATE DATE: 09/09/2002| | HQ OPS OFFICER: GERRY WAIG +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: NON EMERGENCY |CHRISTINE LIPA R3 | |10 CFR SECTION: | | |APRE 50.72(b)(2)(xi) OFFSITE NOTIFICATION | | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N Y 100 Power Operation |100 Power Operation | |2 N Y 100 Power Operation |100 Power Operation | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | MEDICAL EMERGENCY INVOLVING CONTRACT EMPLOYEE | | | | "Today at approximately 10:08 AM a report was received in the control room | | of a medical emergency involving a contract employee at the Point Beach | | nuclear power plant. Onsite medical personnel responded and commenced first | | aid including CPR. CPR was continued until ambulance personnel arrived on | | site. The individual was transported to a local hospital. | | | | "We have been informed by a subsequent report from the hospital that the | | individual died from an apparent heart attack. | | | | "The Manitowoc County coroner's office and OSHA have been informed of the | | fatality. At this time no press release is planned." | | | | The licensee notified the NRC Resident Inspector. | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |General Information or Other |Event Number: 39178 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | REP ORG: ROSEMOUNT NUCLEAR INSTUMENTS, INC |NOTIFICATION DATE: 09/09/2002| |LICENSEE: ROSEMOUNT NUCLEAR INSTUMENTS, INC |NOTIFICATION TIME: 15:15[EDT]| | CITY: EDEN PRAIRIE REGION: 3 |EVENT DATE: 09/09/2002| | COUNTY: STATE: MN |EVENT TIME: [CDT]| |LICENSE#: AGREEMENT: N |LAST UPDATE DATE: 09/09/2002| | DOCKET: |+----------------------------+ | |PERSON ORGANIZATION | | |DAVID LEW R1 | | |DAVID AYRES R2 | +------------------------------------------------+CHRISTINE LIPA R3 | | NRC NOTIFIED BY: EMERSON PROCESS MGMT. |JACK WHITTEN R4 | | HQ OPS OFFICER: GERRY WAIG |TIM MCGINTY IRO | +------------------------------------------------+VERN HODGE NRR | |EMERGENCY CLASS: NON EMERGENCY | | |10 CFR SECTION: | | |CCCC 21.21 UNSPECIFIED PARAGRAPH | | | | | | | | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | NOTIFICATION UNDER 10 CFR PART 21 FOR MODEL 1153 DIFFERENTIAL PRESSURE | | TRANSMITTERS | | | | The following is taken from a facsimile report sent by Emerson Process | | Management: | | | | "Pursuant to 10 CFR Part 21, section 21.21(b), Rosemount Nuclear | | Instruments, Inc. (RNII) is writing to inform you that: | | | | (a) certain Model 1153 differential pressure transmitters with model codes | | beginning with '1153D' or '1153H' shipped between March 2001 and August | | 2002, and | | | | (b) spare sensor modules shipped between March 2001 and August t2002 with | | kit part numbers: | | | | 01153-0320-0232 | | 01153-0320-0352 | | 01153-0320-0252 | | | | "may not meet RNII's published temperature effect specification. Other Model | | 1152, 1153 and 1154 pressure transmitters are not affected. A list of | | affected Model 1153 pressure transmitters and spare sensor modules shipped | | to the end user's facility is provided in Attachment A. | | | | "1.0 Name and address of the individual providing the information: | | | | Mr. Jeffrey W. Schmitt | | Vice President & General Manager | | Rosemount Nuclear Instruments, Inc. | | 12001 Technology Drive | | Eden Prairie, MN 55344 | | | | "2.0 Identification of items supplied: | | | | Certain Model 1153 differential pressure transmitters with model codes | | beginning with 1153D or 1153H shipped between March 2001 and August 2002 | | and; | | | | "Spare sensor modules shipped between March 2001 and August 2002 with kit | | part numbers: | | | | 01153-0320-0232 | | 01153-0320-0352 | | 01153-0320-0252 | | | | "See Attachment A for complete listing of affected equipment shipped to the | | end user's facility. | | | | "3.0 Identification of firm supplying the item: | | | | Rosemount Nuclear Instruments, Inc. | | 12001 Technology Drive | | Eden Prairie, MN 55344 | | | | "4.0 Nature of the failure and potential safety hazard: | | | | During the course of quality testing and data review, RNII has determined | | that certain Model 1153 differential pressure transmitters and spare sensor | | modules may not meet the published temperature effect specification. The | | temperature effect specification establishes an expected analog output error | | interval during normal ambient temperature variations occurring between 40 | | [degrees] F (4.4 [degrees] C) and 200 [degrees] F (93.3 [degrees] C). While | | analysis is still ongoing, the root cause of the potential nonconformance | | has been narrowed to the effect of temperature changes on the transmitter | | module. | | | | Based on data review and analysis, RNII has established the following | | ambient temperature effect specification for transmitters affected by this | | notification. This specification supercedes the published temperature effect | | specification for all pressure transmitters affected by this notification. | | | | All Range Codes: � 3.0% of Upper Range Limit per 100 [degrees] F (55.6 | | [degrees] C) | | | | RNII does not have sufficient information relative to each end user's | | specific applications to determine the potential safety-related impact to | | each end users plant. Each end user must determine the impact on its plant | | operations and plant safety and take action as deemed necessary. | | | | "5.0 The corrective action which is taken, the name of the individual or | | organization responsible for that action, and the length of time taken to | | complete that action: | | | | (a) RNII has expanded its temperature effect test screen to include all | | model 1153 pressure transmitters to assure that all further shipments of | | model 1153 pressure transmitters meet RNII's published temperature effect | | specification. | | | | (b) RNII has placed a hold on spare sensor module shipments. | | | | (c) RNII has established a new temperature effect specification for pressure | | transmitters impacted by this notification as noted in Section 4.0. | | | | (d) RNII will verify ambient temperature effect performance to the original | | specification on any returned Model 1153 differential pressure transmitter | | or sensor module affected by this notification and repair or replace if | | required. | | | | (e) RNII will continue root cause analysis of the temperature effect | | potential non-conformance. Action will be taken consistent with the findings | | of this analysis to assure conformance to RNII's published temperature | | effect specifications. Anticipated completion date: 1 November 2002. | | | | (f) RNII will remove the hold on spare sensor modules when actions per 5.0 | | (e) are complete. | | | | "6.0 Any advice related to the potential failure of the item: | | | | The end user must determine the impact of this potential non-conformance | | upon its plant's operation and safety and take action as deemed necessary. | | If the end user determines that return of a pressure transmitter or sensor | | module is required, RNII should be contacted to facilitate the return | | process. | | | | Rosemount Nuclear Instruments, Inc. has a strong commitment to the nuclear | | industry and assures you that we are dedicated to the supply of high quality | | products and services to our customers. We are sorry for any potential | | impact that this notification might cause. If there are any questions, or | | you require additional information related to this issue, please contact | | Mike Dougherty (952) 828-5626, Gerard Hanson (952) 828-3951, Bob Cleveland | | at (952) 828-8255, or Matt Doyle at (952) 828-3480." | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 39179 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: WOLF CREEK REGION: 4 |NOTIFICATION DATE: 09/09/2002| | UNIT: [1] [] [] STATE: KS |NOTIFICATION TIME: 22:30[EDT]| | RXTYPE: [1] W-4-LP |EVENT DATE: 09/09/2002| +------------------------------------------------+EVENT TIME: 15:59[CDT]| | NRC NOTIFIED BY: RICK HUBBARD |LAST UPDATE DATE: 09/09/2002| | HQ OPS OFFICER: RICH LAURA +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: NON EMERGENCY |JACK WHITTEN R4 | |10 CFR SECTION: | | |AESF 50.72(b)(3)(iv)(A) VALID SPECIF SYS ACTUAT| | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N Y 100 Power Operation |100 Power Operation | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | FAILED RELAY CARD CAUSE AUTOMATIC START OF THE "A" EDG AND THE TURBINE | | DRIVEN AUXILIARY FEED WATER PUMP | | | | "On September 9, 2002 at 1559, with Wolf Creek in Mode 1 at 100 % power, the | | Control Room received annunciator 19E, NB01 degraded voltage. Approximately | | 90 seconds later, the NB01 normal feeder breaker opened. The 'A' Emergency | | Diesel Generator (EDG) started and loaded onto the bus as expected. After | | the 'A' EDG restored NB01 bus voltage to normal, annunciator 19E remained | | locked in. The cause of the actuation appears to be a failure of the relay | | driver card that supplies the degraded voltage signal to the Load Sequencer | | Emergency Load Shedder (LSELS). Instrumentation and Control Technicians | | (INC) expect repairs to be complete by 0000, September 10, 2002. | | | | "As expected, an automatic start of the turbine driven auxiliary feedwater | | pump occurred upon the under voltage condition on NB01. After the bus was | | re-energized, the shutdown sequencer actuated and emergency loads sequenced | | as expected. | | | | "Based on the guidance provided in NUREG 1022, Revision 2, this situation | | meets the criteria of 10 CFR 50.72 (b)(3)(iv)(A) for an 8-hour ENS | | notification as it relates to actuation of the emergency ac electrical power | | systems, which includes emergency diesel generators. | | | | "The licensee has notified the NRC resident inspector." | +------------------------------------------------------------------------------+
Page Last Reviewed/Updated Thursday, March 25, 2021
Page Last Reviewed/Updated Thursday, March 25, 2021