Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for August 2, 2002

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           08/01/2002 - 08/02/2002

                              ** EVENT NUMBERS **

38602  39089  39099  39102  39103  
.
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38602       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CRYSTAL RIVER            REGION:  2  |NOTIFICATION DATE: 01/01/2002|
|    UNIT:  [3] [] []                 STATE:  FL |NOTIFICATION TIME: 10:08[EST]|
|   RXTYPE: [3] B&W-L-LP                         |EVENT DATE:        01/01/2002|
+------------------------------------------------+EVENT TIME:        09:19[EST]|
| NRC NOTIFIED BY:  BILL BANDHAUER               |LAST UPDATE DATE:  08/01/2002|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |ANNE BOLAND          R2      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|3     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION DUE RESCUED SEA TURTLE                                  |
|                                                                              |
| EN #37902 started the biennial report period.                                |
|                                                                              |
| On January 1, 2002 at 0919, a rescued sea turtle was identified as a green   |
| sea turtle.  This is the 62nd rescue of a live sea turtle at Crystal River   |
| Unit 3 (CR-3) in this biennial period. Notification to the National Marine   |
| Fisheries Service and the Florida Fish and Wildlife Conservation Commission. |
|                                                                              |
|                                                                              |
| The licensee intends to notify the NRC Resident Inspector.                   |
|                                                                              |
| * * *  UPDATE ON 1/05/02 @ 1002 BY RAWLS TO GOULD  * * *                     |
|                                                                              |
| On January 5, 2002, at 0720, a rescued sea turtle was identified as a        |
| Loggerhead Sea Turtle. This is the 63rd rescue of a live sea turtle at       |
| Crystal River Unit 3 (CR3) in this biennial period.  This is reportable as a |
| 4-hour report under 10 CFR 50.72(b)(2)(xi) as this event is related to the   |
| protection of the environment for which a notification to other government   |
| agencies (National Marine Fisheries Service and Florida Fish and Wildlife    |
| Conservation Commission) has been or will be made.                           |
|                                                                              |
| The NRC Resident Inspector was notified.                                     |
|                                                                              |
| Reg 2 RDO (Decker) was notified.                                             |
|                                                                              |
| * * * UPDATE ON 01/09/02 @ 1107 EST BY ANDY BARNES TAKEN BY MACKINNON * * *  |
|                                                                              |
| On January 9, 2002, at 0838, a rescued sea turtle was identified as a Kemp's |
| Ridley Sea Turtle. This is the 64th rescue of a live turtle at Crystal River |
| Unit 3 (CR-3) in this biennial period. This is reportable as a 4-hour 10 CFR |
| 50.72(b)(2)(xi) as this event is related to the protection of the            |
| environment for which a notification to other government agencies (National  |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation          |
| Commission) has been or will be made.                                        |
|                                                                              |
| The NRC Resident Inspector was notified.                                     |
|                                                                              |
| Reg 2 (Brian Bonser) was notified.                                           |
|                                                                              |
| * * * UPDATE ON 02/17/02 at 0940 EST BY RICKY RAWLS TO FANGIE JONES * * *    |
|                                                                              |
| "On February 17, 2002 at 0820, a rescued injured sea turtle was identified   |
| as a Kemp's Ridley Sea Turtle. The injury will require transportation to     |
| Clearwater Marine Science Center or Florida Fish and Wildlife Conservation   |
| Refuge. The Injury appears to be from a boat propeller. This is the 65th     |
| rescue of a live sea turtle at Crystal River Unit 3 (CR-3) in this biennial  |
| period. This is Reportable as a 4-Hour Report under 10 CFR 50.72(b)(2)(xi)   |
| as this event is related to the protection of the environment for which a    |
| notification to other government agencies (National Marine Fisheries Service |
| and Florida Fish and Wildlife Conservation Commission) has been or will be   |
| made. This Is an update to event 38602."                                     |
|                                                                              |
| The NRC Resident Inspector will be notified.  R2DO (Stephen Cahill) has been |
| notified.                                                                    |
|                                                                              |
| * * * UPDATE ON 03/01/02 AT 1122 EST BY RICKY RAWLS TO GERRY WAIG * * *      |
|                                                                              |
| "On March 1, 2002 at 0952, a healthy rescued sea turtle was identified as a  |
| Green Sea Turtle. This is the 66th rescue of a live sea turtle at Crystal    |
| River Unit 3 (CR-3) in this biennial period. This is Reportable as a 4-Hour  |
| Report under 10 CFR 50.72(b)(2)(xi) as this event is related to the          |
| protection of the environment for which a notification to other government   |
| agencies (National Marine Fisheries Service and Florida Fish and Wildlife    |
| Conservation Commission) has been or will be made. This is an update to      |
| event 38602."                                                                |
|                                                                              |
| The NRC Resident Inspector was notified. R2DO (Julian) was notified.         |
|                                                                              |
| * * * UPDATE ON 03/07/02 AT 1114 EST BY CHUCK MORRIS TO MIKE NORRIS * * *    |
|                                                                              |
| "On March 7, 2002 at 0835, two healthy sea turtles rescued at CR#3 were      |
| identified as Green Sea Turtles. These are the 67th and 68th live sea turtle |
| rescues at the Crystal River Energy Complex in this biennial period. This is |
| Reportable as a 4-Hour Report under 10 CFR 50.72(b)(2)(xi) as this event is  |
| related to the protection of the environment for which a notification to     |
| other government agencies (National Marine Fisheries Service and Florida     |
| Fish and Wildlife Conservation Commission) has been or will be made. This is |
| an update to event 38602."                                                   |
|                                                                              |
| The NRC Resident Inspector was notified. R2DO (Henson) was notified.         |
|                                                                              |
| * * * UPDATE ON 04/02/02 at 0408 EST BY RICKY RAWLS TO FANGIE JONES * * *    |
|                                                                              |
| "On April 2, 2002 at 0236, two sea turtles previously rescued at CR#3 intake |
| area were identified by FPC Mariculture staff as Kemp Ridley Sea Turtles.    |
| One of the turtles appears to be in distress and may require transportation  |
| to Clearwater Marine Science Center of Florida Fish and Wildlife             |
| Conservation Refuge. These are the 69th and 70th live sea turtle rescues at  |
| the Crystal River Energy Complex in this biennial period. This is Reportable |
| as a 4-Hour Report under 10 CFR 50.72(b)(2)(xi) as this event is related to  |
| the protection of the environment for which a notification to other          |
| government agencies (National Marine Fisheries Service and Florida Fish and  |
| Wildlife Conservation Commission) has been or will be made. This is an       |
| update to event 38602."                                                      |
|                                                                              |
| The NRC Resident Inspector will be notified.  The R2DO (Carolyn Evans) was   |
| notified.                                                                    |
|                                                                              |
| ***** UPDATE AT 1023 EDT ON 05/19/02 FROM PELLERIN TO LEIGH TROCINE *****    |
|                                                                              |
| The following text is a portion of a facsimile received from the licensee:   |
|                                                                              |
| "On May 19, 2002, at 0916, a sea turtle previously rescued at CR#3 intake    |
| area was identified by FPC Mariculture staff as Green Sea Turtle.  This is   |
| the 71st live sea turtle rescue at the Crystal River Energy Complex in this  |
| biennial period.  This is Reportable as a 4-Hour Report under 10 CFR         |
| 50.72(b)(2)(xi) as this event is related to the protection of the            |
| environment for which a notification to other government agencies (National  |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation          |
| Commission) has been or will be made.  This is an update to event 38602."    |
|                                                                              |
| The licensee plans to notify the National Marine Fisheries Service and       |
| Florida Fish and Wildlife Conservation Commission and the NRC resident       |
| inspector.  The NRC operations officer notified the R2DO (Paul               |
| Fredrickson).                                                                |
|                                                                              |
| * * * UPDATE 1816 EDT ON 5/28/02 FROM BERRY FOSTER TO S. SANDIN * * *        |
|                                                                              |
| "On May 28, 2002 at 1700, a sea turtle previously rescued at CR#3 intake     |
| area was identified by FPC Mariculture staff as a Green Sea Turtle. This is  |
| the 72nd live sea turtle rescue at the Crystal River Energy Complex in this  |
| biennial period. The turtle is being transported to the Clearwater Marine    |
| Science Center. This is Reportable as a 4-Hour Report under 10 CFR 50.72 (b) |
| (2) (xi) as this event is related to the protection of the environment for   |
| which a notification to other government agencies (National Marine Fisheries |
| Service and Florida Fish and Wildlife Conservation Commission) has been or   |
| will be made. This is an update to event 38602."                             |
|                                                                              |
| The licensee will inform the NRC Resident Inspector.  Notified               |
| R2DO(Landis).                                                                |
|                                                                              |
| * * * UPDATE 1602 EDT ON 5/31/02 FROM BILL BANDHAUER TO MIKE NORRIS * * *    |
|                                                                              |
| "On May 30, 2002 at 1323, a sea turtle previously rescued at CR#3 intake     |
| area was identified by FPC Mariculture staff as a Kemp's Ridley Sea Turtle.  |
| This is the 72nd live sea turtle rescue at the Crystal River Energy Complex  |
| in this biennial period. (Note: The sequential numbering of the live sea     |
| turtle takes has been modified to reflect the actual live sea turtle takes,  |
| On 4/02/02, a live rescue of two turtles was reported, however, one of the   |
| turtles died and was reclassified as a non-causal mortality, which is        |
| non-reportable). This event is Reportable as a 4-Hour Report under 10 CFR    |
| 50.72(b) (2) (xi) as this event is related to the protection of the          |
| environment for which a notification to other government agencies (National  |
| Marine Fisheries Service and Florida Fish and Wildlife Conservation          |
| Commission) has been or will be made. This is an update to event 38602."     |
|                                                                              |
| The NRC Resident Inspector has been notified.  Notified R2DO (Landis).       |
|                                                                              |
| *****UPDATE AT 13:58 EDT ON 7/18/02 FROM SWEENEY TO LAURA*****               |
|                                                                              |
| An offsite notification to the State regarding a green sea turtle that was   |
| rescued from the CR#3 intake area by the FPC Mariculture staff.              |
|                                                                              |
| The NRC resident inspector was notified.  Notified R2DO (C. Payne).          |
|                                                                              |
| * * * UPDATE 1126 EDT ON 8/1/02 FROM BILL BANDHAUER TO FANGIE JONES * * *    |
|                                                                              |
| "At 0915 on August 1,2002, a dead sea turtle recovered at the CR#3 intake    |
| area was identified by FPC Mariculture staff as a Kemps Ridley Turtle. FPC   |
| determined that the cause of death was non-causally related to the operation |
| of CR3. This is the 7th dead Kemps Ridley Turtle recovery at the Crystal     |
| River Energy Complex in this biennial period. The threshold for reporting    |
| non-causal sea turtle deaths is 6 in a biennial period. This event is        |
| Reportable as a 4-Hour Report under 10 CFR 50.72 (b) (2) (xi) as this event  |
| is related to the protection of the environment for which a notification to  |
| other government agencies (National Marine Fisheries Service and Florida     |
| Fish and Wildlife Conservation Commission) will be made. This is an update   |
| to event 38602."                                                             |
|                                                                              |
| The licensee intends to notify the NRC Resident Inspector.  The R2DO (Mike   |
| Ernstes) has been notified.                                                  |
+------------------------------------------------------------------------------+
.
!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Other Nuclear Material                           |Event Number:   39089       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  US ARMY                              |NOTIFICATION DATE: 07/25/2002|
|LICENSEE:  US ARMY                              |NOTIFICATION TIME: 10:40[EDT]|
|    CITY:  FT. LEE                  REGION:  2  |EVENT DATE:        07/25/2002|
|  COUNTY:                            STATE:  VA |EVENT TIME:             [EDT]|
|LICENSE#:  BML12-00722-0         AGREEMENT:  N  |LAST UPDATE DATE:  08/01/2002|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |MARK LESSER          R2      |
|                                                |CHRIS MILLER         R3      |
+------------------------------------------------+JOHN HICKEY          NMSS    |
| NRC NOTIFIED BY:  KELLY CROOKS                 |                             |
|  HQ OPS OFFICER:  MIKE NORRIS                  |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|ICON 30.50(b)(1)         UNPLANNED CONTAMINATION|                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| UNPLANNED CONTAMINATION RESTRICTING ACCESS >24 HOURS                         |
|                                                                              |
| The ARMY is conducting an investigation as to the disposal of 75 to 100      |
| Pm-147 target sights.  Each sight was originally 3  millicuries with a       |
| manufacture date of approximately 1975.  The ARMY is restricting access into |
| a building where these gun sights were disposed of in 1997.                  |
|                                                                              |
| * * * UPDATE ON 8/01/02 @ 1513 BY CROOKS TO GOULD * * *  EVENT RETRACTION    |
|                                                                              |
| A wipe test was performed at the area in question and from the 18 wipes      |
| taken 16 were clean and one measured 5 dpm and a second measured 6 dpm.      |
| Therefore the licensee is retracting this event since there was no           |
| contamination present.                                                       |
|                                                                              |
| Notified Reg 2 RDO(Ernstes), Reg 3 RDO(Burgess) and NMSS(Hickey)             |
+------------------------------------------------------------------------------+
.
!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   39099       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SUMMER                   REGION:  2  |NOTIFICATION DATE: 07/27/2002|
|    UNIT:  [1] [] []                 STATE:  SC |NOTIFICATION TIME: 13:36[EDT]|
|   RXTYPE: [1] W-3-LP                           |EVENT DATE:        07/27/2002|
+------------------------------------------------+EVENT TIME:        01:10[EDT]|
| NRC NOTIFIED BY:  JIM TURKETT                  |LAST UPDATE DATE:  08/01/2002|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |MARK LESSER          R2      |
|10 CFR SECTION:                                 |                             |
|NINF                     INFORMATION ONLY       |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| INFORMATION CALL THAT INVOLVES LOCAL AUTHORITIES AND POSSIBLE MEDIA         
|
| ATTENTION                                                                    |
|                                                                              |
| The licensee's security personnel discovered a stub end of a hand rolled     |
| cigarette of questionable material in the room above diesel generator 'A.'   |
| It appeared old and had no odor.  Fairfield County Sheriff's Department was  |
| contacted and they dispatched a unit.  They potentially identified the       |
| contents as marijuana and took custody of the cigarette.  They will submit   |
| it to the South Carolina State Law Enforcement Division for analysis.  The   |
| analysis will take about a week or more and followup notification will be    |
| made if needed.  This notification was made due to Fairfield County          |
| involvement and possible media coverage.  There is no impact on plant        |
| operation.                                                                   |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
|                                                                              |
| * * * UPDATE ON 8/01/02 @ 1403 BY TURKETT TO GOULD * * * EVENT RETRACTION    |
|                                                                              |
| The analysis determined that the material found in the hand rolled cigarette |
| was not marijuana, therefore the licensee is retracting this event.          |
|                                                                              |
| The NRC Resident Inspector will be notified.                                 |
+------------------------------------------------------------------------------+
.
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   39102       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: MAINE YANKEE             REGION:  1  |NOTIFICATION DATE: 08/01/2002|
|    UNIT:  [1] [] []                 STATE:  ME |NOTIFICATION TIME: 13:50[EDT]|
|   RXTYPE: [1] CE                               |EVENT DATE:        07/09/2002|
+------------------------------------------------+EVENT TIME:        14:00[EDT]|
| NRC NOTIFIED BY:  HEBERT/RIVARD                |LAST UPDATE DATE:  08/01/2002|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |J. BRADLEY FEWELL    R1      |
|10 CFR SECTION:                                 |JOHN HICKEY          NMSS    |
|BLO2 20.2201(a)(1)(ii)   LOST/STOLEN LNM>10X    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Decommissioned   |0        Decommissioned   |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| THE LICENSEE REPORTED A LOSS OF LICENSED MATERIAL                            |
|                                                                              |
| During preparation activities for the removal of the reactor vessel, site    |
| personnel detached a vessel external neutron flux dosimeter assembly from    |
| the vessel and released the dosimeter assembly to the sump area below the    |
| vessel for future recovery and disposal. The neutron flux dosimeter was used |
| during plant operation to measure neutron fluence to the immediate adjacent  |
| outside wall of the reactor vessel.  Subsequently, site personnel were       |
| provided access to the area for retrieval and disposal of the dosimeter      |
| capsules.  One of the dosimeter capsules apparently had become dislodged     |
| from the assembly during the earlier release and personnel were unable to    |
| locate the dislodged capsule. The dosimeter contains small quantities of     |
| dosimetry material including Neptunium 237 (6.46 microcuries) and Uranium    |
| 238 (.009 microcuries).  Subsequent limited inspections have been            |
| unsuccessful in locating this capsule.  The constrained annulus area between |
| the reactor vessel and adjacent neutron shield tank and storage of           |
| radioactive material and bagged asbestos in the reactor vessel sump area     |
| continues to limit area for a thorough inspection.   Additional inspection   |
| of the area is scheduled for January of 2003.                                |
|                                                                              |
| Maine Yankee is reporting the loss of licensed material in accordance with   |
| 10 CFR 20.2201(b). The licensed material was lost in a restricted area and   |
| the Neptunium 237 material is of a quantity greater than 10 times the        |
| quantity specified in appendix C to Part 20. The missing dosimeter capsule   |
| surface dose rate is estimated to be around 1000 cpm and therefore of        |
| minimal exposure to workers in this radiation control area.                  |
+------------------------------------------------------------------------------+
.
+------------------------------------------------------------------------------+
|Fuel Cycle Facility                              |Event Number:   39103       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PORTSMOUTH GASEOUS DIFFUSION PLANT   |NOTIFICATION DATE:
08/01/2002|
|   RXTYPE: URANIUM ENRICHMENT FACILITY          |NOTIFICATION TIME: 16:16[EDT]|
| COMMENTS: 2 DEMOCRACY CENTER                   |EVENT DATE:        08/01/2002|
|           6903 ROCKLEDGE DRIVE                 |EVENT TIME:        12:54[EDT]|
|           BETHESDA, MD 20817    (301)564-3200  |LAST UPDATE DATE:  08/01/2002|
|    CITY:  PIKETON                  REGION:  3  +-----------------------------+
|  COUNTY:  PIKE                      STATE:  OH |PERSON          ORGANIZATION |
|LICENSE#:  GDP-2                 AGREEMENT:  N  |BRUCE BURGESS        R3      |
|  DOCKET:  0707002                              |FRED BROWN           NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  MICHAEL RITCHIE              |                             |
|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|KPRE PART 70 APP A (2)   OFFSITE NOTIFICATION/NE|                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| CERTIFICATE HOLDER REPORTED TO THE STATE THAT IT EXCEEDED ITS OPACITY      
 |
| LIMITS                                                                       |
|                                                                              |
| On 8/01/02 at 1254 the "A" side of #1 precipitator at the X-600 Steam Plant  |
| experienced problems after being energized while placing #1 boiler in        |
| service.  The precipitators were energized at 1230 and had readings of 20.8% |
| at 1254 and 31.9% at 1300.  This resulted in the exceedance of the opacity   |
| limit of 20% twice in one hour.                                              |
|                                                                              |
|                                                                              |
| At 1543 the Plant Shift Superintendent notified the Ohio EPA of the X-600    |
| Steam Plant opacity exceedance.   UE2-RA-RE1030,  App. D, section P requires |
| a 4 hour NRC event when other government agencies are notified.              |
+------------------------------------------------------------------------------+