Skip to main content

Alert

Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for June 13, 2002

                         
                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           06/12/2002 - 06/13/2002

                              ** EVENT NUMBERS **

38972  38973  38974  38980  38981  38982  38983  38984  38986  38987  

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   38972       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  ARKANSAS DEPARTMENT OF HEALTH        |NOTIFICATION DATE:
06/07/2002|
|LICENSEE:  ALBEMARLE CORPORATION                |NOTIFICATION TIME: 17:07[EDT]|
|    CITY:  MAGNOLIA                 REGION:  4  |EVENT DATE:        06/06/2002|
|  COUNTY:                            STATE:  AR |EVENT TIME:             [CDT]|
|LICENSE#:  ARK-717-BP            AGREEMENT:  Y  |LAST UPDATE DATE:  06/07/2002|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |JOHN PELLET          R4      |
|                                                |THOMAS ESSIG         NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  JARED THOMPSON               |                             |
|  HQ OPS OFFICER:  FANGIE JONES                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT - SOURCE NOT ATTACHED TO SOURCE ROD                   |
|                                                                              |
| "On June 6, 2002 at 4:30 p.m. the Arkansas Department of Health was notified |
| by Albemarle Corporation in Magnolia, Arkansas that a fixed density gauge    |
| source had been damaged. Albemarle has Arkansas Radioactive Material License |
| ARK-717-BP-11-99. The device is a Ronan Engineering Company Model SA-15      |
| containing two 5 millicuries sources of Cesium-137. The device was locked    |
| out on June 3, 2002. On June 6, 2002 while the source housing was being      |
| adjusted it was noted that the source rod was in a different configuration.  |
| Radiation surveys were performed and it appeared that one of the 5           |
| millicuries sources was not attached to the source rod. The immediate area   |
| was secured and access has been restricted. Albemarle has contacted a        |
| consultant to assist in retrieval and packaging of the source for return to  |
| the manufacturer.                                                            |
|                                                                              |
| "The Department has sent two inspectors to the facility to investigate and   |
| assess the Incident on June 7, 2002. It appears that there may have been     |
| personnel radiation exposure due to this incident. This incident is under    |
| investigation."                                                              |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   38973       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  SC DIV OF HEALTH & ENV CONTROL       |NOTIFICATION DATE: 06/08/2002|
|LICENSEE:  ISOMEDIX CORPORATIONS                |NOTIFICATION TIME: 13:50[EDT]|
|    CITY:  SPARTANBURG              REGION:  2  |EVENT DATE:        06/07/2002|
|  COUNTY:                            STATE:  SC |EVENT TIME:        21:15[EDT]|
|LICENSE#:  267                   AGREEMENT:  Y  |LAST UPDATE DATE:  06/08/2002|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |BRIAN BONSER         R2      |
|                                                |THOMAS ESSIG         NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  JAMES PETERSON               |                             |
|  HQ OPS OFFICER:  FANGIE JONES                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT - EMPLOYEE DEATH DUE TO NONNUCLEAR ACCIDENT     
     |
|                                                                              |
| With the source in the stored position, an employee of Isomedix Operations,  |
| entered the sterilization chamber of the irradiator to try freeing some      |
| jammed product carriers.  The employee was killed when his head was caught   |
| between the carriers as they moved together.                                 |
|                                                                              |
| This report is made as a conservative measure as this was not nuclear        |
| related, but occurred at a licensee's facility.                              |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   38974       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  CALIFORNIA RADIATION CONTROL PRGM    |NOTIFICATION DATE:
06/10/2002|
|LICENSEE:  UCLA HARBOR MEDICAL CENTER           |NOTIFICATION TIME: 12:40[EDT]|
|    CITY:                           REGION:  4  |EVENT DATE:        06/10/2002|
|  COUNTY:  LOS ANGELAS               STATE:  CA |EVENT TIME:             [PDT]|
|LICENSE#:  0359-19               AGREEMENT:  Y  |LAST UPDATE DATE:  06/10/2002|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |ANTHONY GODY         R4      |
|                                                |FRED BROWN           NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  ROBERT GREGER                |                             |
|  HQ OPS OFFICER:  RICH LAURA                   |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT OF MEDICAL MISADMINISTRATION                          |
|                                                                              |
| "Patient who was suppose to receive 32 millicuries I-131 was given 120       |
| millicuries I-131.  As patient's thyroid was to be ablated anyway, no ill    |
| effects to patient.  The doctor gave her the wrong dose."                    |
|                                                                              |
| The cause of the misadministration is being reviewed at the time of the      |
| report.                                                                      |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Other Nuclear Material                           |Event Number:   38980       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  US ARMY                              |NOTIFICATION DATE: 06/12/2002|
|LICENSEE:  US ARMY                              |NOTIFICATION TIME: 09:28[EDT]|
|    CITY:  ABERDEEN                 REGION:  1  |EVENT DATE:        06/11/2002|
|  COUNTY:                            STATE:  MD |EVENT TIME:             [EDT]|
|LICENSE#:  19-30563-01           AGREEMENT:  Y  |LAST UPDATE DATE:  06/12/2002|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |LAWRENCE DOERFLEIN   R1      |
|                                                |DON COOL             NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  JOYCE KUYKENDALL             |                             |
|  HQ OPS OFFICER:  LEIGH TROCINE                |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|BLO1 20.2201(a)(1)(i)    LOST/STOLEN LNM>1000X  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| LOSS OF ONE CHEMICAL DETECTOR AT A TRAINING SITE IN SEOMOUL CITY, SOUTH    
 |
| KOREA                                                                        |
|                                                                              |
| A chemical detector containing 300 microcuries of americium-241 was lost at  |
| the site of a training activity in Seomoul City, South Korea.  An            |
| investigation is currently ongoing.  The detector was verified to be missing |
| on 06/11/02.                                                                 |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Other Nuclear Material                           |Event Number:   38981       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  US ARMY                              |NOTIFICATION DATE: 06/12/2002|
|LICENSEE:  US ARMY                              |NOTIFICATION TIME: 09:28[EDT]|
|    CITY:  ABERDEEN                 REGION:  1  |EVENT DATE:        06/12/2002|
|  COUNTY:                            STATE:  MD |EVENT TIME:             [EDT]|
|LICENSE#:                        AGREEMENT:  Y  |LAST UPDATE DATE:  06/12/2002|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |LAWRENCE DOERFLEIN   R1      |
|                                                |ANTHONY GODY         R4      |
+------------------------------------------------+DON COOL             NMSS    |
| NRC NOTIFIED BY:  JOYCE KUYKENDALL             |                             |
|  HQ OPS OFFICER:  LEIGH TROCINE                |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|BLO2 20.2201(a)(1)(ii)   LOST/STOLEN LNM>10X    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| LOSS OF FOUR DETECTORS AT FORT HOOD, TEXAS                                   |
|                                                                              |
| Four detectors each containing 15 millicuries of nickel-63 were lost at Fort |
| Hood, Texas.  On 05/29/02, Fort Hood received the report that the detectors  |
| might be missing.  Apparently, they were misplaced during preparations to    |
| send them to a maintenance shop for wipe testing.  The detectors were        |
| verified to be missing on 06/05/02, and Fort Hood notified Aberdeen on       |
| 06/11/02.                                                                    |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38982       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: DUANE ARNOLD             REGION:  3  |NOTIFICATION DATE: 06/12/2002|
|    UNIT:  [1] [] []                 STATE:  IA |NOTIFICATION TIME: 14:03[EDT]|
|   RXTYPE: [1] GE-4                             |EVENT DATE:        06/12/2002|
+------------------------------------------------+EVENT TIME:        11:38[CDT]|
| NRC NOTIFIED BY:  MIKE DAVIS                   |LAST UPDATE DATE:  06/12/2002|
|  HQ OPS OFFICER:  RICH LAURA                   +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |KENNETH RIEMER       R3      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       93.6     Power Operation  |93.6     Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION AT DUANE ARNOLD DUE TO A SMALL OIL SPILL                |
|                                                                              |
| "Notified Iowa DNR, Linn County Sheriff, and the US National Coast Guard     |
| National Response Center of a reportable spill of petroleum oil into the     |
| Cedar River (sheen on the river) per applicable reporting procedures. While  |
| performing river water supply pit cleaning, the cleaning pump leaked about 1 |
| pint of oil into the Cedar River. The pump has been removed from the river." |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38983       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: COOK                     REGION:  3  |NOTIFICATION DATE: 06/12/2002|
|    UNIT:  [1] [2] []                STATE:  MI |NOTIFICATION TIME: 14:17[EDT]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        06/12/2002|
+------------------------------------------------+EVENT TIME:        14:05[EDT]|
| NRC NOTIFIED BY:  T. BURRIS                    |LAST UPDATE DATE:  06/13/2002|
|  HQ OPS OFFICER:  RICH LAURA                   +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          ALERT                 |JAMES CALDWELL       R3      |
|10 CFR SECTION:                                 |JON JOHNSON          NRR     |
|AAEC 50.72(a) (1) (i)    EMERGENCY DECLARED     |TERENCE REIS         NRR     |
|                                                |DON MARKSBERRY       RCT     |
|                                                |TIM MCGINTY          DIRO    |
|                                                |RICHARD WESSMAN      DIRO    |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       69       Power Operation  |69       Power Operation  |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| ALERT DECLARED AT DC COOK DUE TO FIRE IN SWITCHYARD                          |
|                                                                              |
| The licensee reported an explosion and subsequent fire that occurred in the  |
| station's 345-kV electrical switchyard.  Neither reactor plant was directly  |
| affected by the event and both remained at power.  The licensee declared an  |
| Alert at 1405 based on the switchyard fire potentially affecting safety      |
| related equipment such as the reserve power to safety-related electrical     |
| buses. Several switchyard breakers tripped open at 1345 placing the units in |
| TS 3.0.5.  One injury was reported.  Planned maintenance was in progress in  |
| the switchyard at the time of the event.                                     |
|                                                                              |
| The NRC entered the Monitoring Phase of Normal Mode at 1447 EDT on           |
| 06/12/02.                                                                    |
|                                                                              |
| Notified the Chairman's office (Mike Tschiltz), USDA (K. Barrett), EPA NRC   |
| (Ms. Edwards), EPA EOC (T. Tanner), DOE (T. Yates), FEMA (C. Cleveland), HHS |
| (Carol Cleveland), and OHS (D. Edwards).                                     |
|                                                                              |
| ***** UPDATE AT 1730 EDT ON 06/12/02 *****                                   |
|                                                                              |
| A Commissioners' assistants briefing was held at 1730 EDT.  Participants     |
| included:  NRR (J. Johnson, S. Collins), DIRO (R. Wessman), EDO (H. Nieh),   |
| HQ PAO (W. Beecher), OSATP (P. Lohaus), IP (J. Dunn-Lee), CA (L. Gerke),     |
| SECY (A. Bates), Comm. Meserve (M. Tschiltz), Comm. Dicus (Kerri Kavanaugh), |
| Comm. Merrifield (J. Thoma), and Comm. Diaz (D. Simpkins).                   |
|                                                                              |
| ***** UPDATE FROM JIM KOBYRA TO LEIGH TROCINE AT 2354 EDT ON 06/12/02 *****  |
|                                                                              |
| At 2157, the licensee declared the Unit 2 east essential service water pump  |
| operable, and Unit 2 exited Technical Specification 3.0.5 at that time.      |
| Unit 1 exited Technical Specification 3.0.5 approximately 5 minutes earlier. |
| At 2347, both units exited Technical Specification 3.8.1.1 when the licensee |
| restored transformer 4 to serve the Unit 2 reserve auxiliary transformers    |
| and isolated it from Unit 1 (which is being fed by transformer 5).  As a     |
| result, the licensee terminated the Alert and exited the Emergency Plan at   |
| 2354 EDT on 06/12/02.                                                        |
|                                                                              |
| The licensee plans to notify the NRC resident inspectors, State of Michigan, |
| and Berrien County.                                                          |
|                                                                              |
| The NRC exited the Monitoring Phase of Normal Mode at 2355 on 06/12/02.      |
|                                                                              |
| The NRC operations center notified the R3DO (Jim Creed), NRR EO (Bill        |
| Bateman), DIRO (Tim McGinty), PAO (Bill Beecher), EDO (Ho Nieh), Chairman's  |
| office (Mike Tschiltz), USDA (Lori Thomas and Kathleen Barrett), EPA via the |
| National Response Center (Ms. Arsenault), DOE (Odell Bartlett), FEMA (Al     |
| Austin), HHS (Karen Cleveland), and OHS (Ron Brahm).                         |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38984       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: COOK                     REGION:  3  |NOTIFICATION DATE: 06/12/2002|
|    UNIT:  [1] [2] []                STATE:  MI |NOTIFICATION TIME: 16:24[EDT]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        06/12/2002|
+------------------------------------------------+EVENT TIME:        15:34[EDT]|
| NRC NOTIFIED BY:  RICK JERVEY                  |LAST UPDATE DATE:  06/12/2002|
|  HQ OPS OFFICER:  RICH LAURA                   +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |TIM MCGINTY          IRO     |
|10 CFR SECTION:                                 |JIM CALDWELL         R3      |
|APRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       69       Power Operation  |69       Power Operation  |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION DUE TO OIL SPILL                                        |
|                                                                              |
| Licensee notified the Michigan Department of Environmental Quality of a      |
| spill of greater than 5 gallons of oil due to a switchyard breaker explosion |
| and fire.                                                                    |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Fuel Cycle Facility                              |Event Number:   38986       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PADUCAH GASEOUS DIFFUSION PLANT      |NOTIFICATION DATE: 06/12/2002|
|   RXTYPE: URANIUM ENRICHMENT FACILITY          |NOTIFICATION TIME: 21:53[EDT]|
| COMMENTS: 2 DEMOCRACY CENTER                   |EVENT DATE:        06/12/2002|
|           6903 ROCKLEDGE DRIVE                 |EVENT TIME:        06:30[CDT]|
|           BETHESDA, MD 20817    (301)564-3200  |LAST UPDATE DATE:  06/12/2002|
|    CITY:  PADUCAH                  REGION:  3  +-----------------------------+
|  COUNTY:  McCRACKEN                 STATE:  KY |PERSON          ORGANIZATION |
|LICENSE#:  GDP-1                 AGREEMENT:  Y  |JAMES CREED          R3      |
|  DOCKET:  0707001                              |LARRY CAMPER         NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  K. BEASLEY                   |                             |
|  HQ OPS OFFICER:  RICH LAURA                   |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NBNL                     RESPONSE-BULLETIN      |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 24 HOUR BULLETIN 91-01 REPORT AT PADUCAH                                     |
|                                                                              |
| "At 0820 CDT, on 6-12-02 the Plant Shift Superintendent was notified of an   |
| NCS violation that had occurred in the C-335 process building. The           |
| calibrated AQ-NCS pressure chart recorders for C and E surge drum banks had  |
| previously failed. As a result of this failure the shiftly pressure checks   |
| were performed using non AQ-NCS pressure instrumentation and therefore were  |
| not valid. The purpose of the pressure check is to identify if wet air       |
| inleakage has begun on surge drum bank. An alternate AQ-NCS pressure         |
| instrument has now been connected to the system and follow-up pressure       |
| readings have been taken. The pressure readings indicate there has been no   |
| wet air inleakage. The required checks have been restarted. Double           |
| contingency has been restored.                                               |
|                                                                              |
| "This is an event is which a violation of the double contingency principle   |
| occurred and where double contingency was re-established within four hours   |
| of the initial observation of the event. The NRC Resident Inspector has been |
| notified of this event.                                                      |
|                                                                              |
| "SAFETY SIGNIFICANCE OF EVENTS:  Although pressure readings were taken on a  |
| shiftly basis, these readings were not valid because the instrumentation     |
| used was not AQ-NCS. Therefore double contingency was not maintained.        |
|                                                                              |
| "POTENTIAL CRITICALITY PATHWAYS INVOLVED: In order for a criticality to be   |
| possible a surge drum would have to contain a critical mass of UO2F2 in an   |
| unfavorable geometry, wet air inleakage would need to occur, and the uranium |
| mass would have to be sufficiently moderated.                                |
|                                                                              |
| "CONTROLLED PARAMETERS: Double contingency is maintained by implementing two |
| controls on moderation.                                                      |
|                                                                              |
| "NUCLEAR CRITICALITY Y SAFETY CONTROL(S): The first leg of double            |
| contingency is based on maintaining the integrity of the surge drum system   |
| against wet air inleakage. This integrity is assured by an SRI for the       |
| unlikely breach of the surge drum system.  Structural integrity of the drum  |
| is intact, therefore this SRI is maintained. The second leg of double        |
| contingency is based on the performance of the shiftly pressure checks of an |
| AQ-NCS instrument as an indication of wet air inleakage. The required checks |
| were performed using an uncalibrated instrument. Since an uncalibrated       |
| instrument was used, the shiftly checks were invalid resulting in a loss of  |
| this control. Since there are two controls on one parameter, double          |
| contingency was not maintained.                                              |
|                                                                              |
| "CORRECTIVE ACTIONS: 1) Isolate the affected surge drum banks until the      |
| original pressure indication equipment is repaired. The drums were isolated  |
| at 1025 CDT on 6-12-02.  2) Connect AQ-NCS pressure indication equipment and |
| monitor in accordance with procedure CP4-CO-CN6069 until the original        |
| pressure indication equipment is repaired. An alternate AQ-NCS approved      |
| instrument was connected, and readings were taken at 1040 CDT on 6-12-02."   |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38987       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CALVERT CLIFFS           REGION:  1  |NOTIFICATION DATE: 06/13/2002|
|    UNIT:  [1] [2] []                STATE:  MD |NOTIFICATION TIME: 00:57[EDT]|
|   RXTYPE: [1] CE,[2] CE                        |EVENT DATE:        06/12/2002|
+------------------------------------------------+EVENT TIME:        23:41[EDT]|
| NRC NOTIFIED BY:  BRUCE SHICK                  |LAST UPDATE DATE:  06/13/2002|
|  HQ OPS OFFICER:  LEIGH TROCINE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |LAWRENCE DOERFLEIN   R1      |
|10 CFR SECTION:                                 |FEMA, DOE, USDA, HHS FAX     |
|APRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |EPA, DOT (via NRC)   FAX     |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Cold Shutdown    |0        Cold Shutdown    |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION REGARDING A RELEASE OF RAW SEWAGE TO THE
CHESAPEAKE     |
| BAY                                                                          |
|                                                                              |
| The licensee reported that an air leak caused a level detector in a large    |
| inlet pumping well to fail low.  As a result, the sump pumps stopped and did |
| not restart when actual level reached the high level setpoint.  The inlet    |
| sump of the onsite sewage treatment plant subsequently overflowed, and raw   |
| sewage was released to the Chesapeake Bay.                                   |
|                                                                              |
| The licensee estimates that the quantity of raw sewage involved was between  |
| 2,500 and 7,200 gallons.  Additional calculations are currently being        |
| performed.  The level detector malfunctioned has since been repaired.        |
|                                                                              |
| The licensee notified the NRC resident inspector and local county and plans  |
| to notify the Maryland Department of Environmental Protection.               |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Wednesday, March 24, 2021

Page Last Reviewed/Updated Wednesday, March 24, 2021