The U.S. Nuclear Regulatory Commission is in the process of rescinding or revising guidance and policies posted on this webpage in accordance with Executive Order 14151 Ending Radical and Wasteful Government DEI Programs and Preferencing, and Executive Order 14168 Defending Women From Gender Ideology Extremism and Restoring Biological Truth to the Federal Government. In the interim, any previously issued diversity, equity, inclusion, or gender-related guidance on this webpage should be considered rescinded that is inconsistent with these Executive Orders.

Event Notification Report for April 1, 2002

                         
                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           03/29/2002 - 04/01/2002

                              ** EVENT NUMBERS **

38816  38817  38818  

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   38816       |
+------------------------------------------------------------------------------+
                         
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  NC DIV OF RADIATION PROTECTION       |NOTIFICATION DATE: 03/28/2002|
|LICENSEE:  THOMPSON-ARTHUR DIVISION APAC-CAROLIN|NOTIFICATION TIME:
23:00[EST]|
|    CITY:  GREENSBORO               REGION:  2  |EVENT DATE:        03/28/2002|
|  COUNTY:                            STATE:  NC |EVENT TIME:             [EST]|
|LICENSE#:  041-039               AGREEMENT:  Y  |LAST UPDATE DATE:  03/31/2002|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |CAROLYN EVANS        R2      |
|                                                |PATRICIA HOLAHAN     NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  LEE COX                      |                             |
|  HQ OPS OFFICER:  STEVE SANDIN                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT INVOLVING A STOLEN TROXLER MOISTURE DENSITY
GAUGE     |
|                                                                              |
| The following is the text from a NC Department of Environment and Natural    |
| Resources News Release:                                                      |
|                                                                              |
| "A truck stolen about 4:30 this afternoon in Forsyth County was transporting |
| an instrument containing eight millicuries of Cesium-137, a radioactive      |
| material that is a potential health and safety risk if handled improperly or |
| broken open.                                                                 |
|                                                                              |
| "The truck is a white Ford F150. The instrument is a Troxler brand portable  |
| moisture density gauge model 4640B.  It is yellow and has a stainless steel  |
| handle with a radiation symbol protruding from a heavy base.  It is about    |
| 20-30 pounds and 24x12x14 inches. Its serial number is 1996. The gauge was   |
| in a yellow box 24x12 inches and marked as containing radioactive material.  |
| The box should be locked and chained to the truck.                           |
|                                                                              |
| "The gauge uses radioactive materials to test conditions of soil and asphalt |
| during construction.  Any health risk would occur only if a person were      |
| directly exposed to the sealed radioactive source inside the instrument.     |
|                                                                              |
| "Employees of Thompson-Arthur Division APAC-Carolina, Inc., a paving company |
| in Greensboro, left the truck unattended. The company's license with the     |
| state Division of Radiation Protection requires that the instrument not be   |
| left unsecured.                                                              |
|                                                                              |
| "Anyone who believes he or she has found the truck, box or gauge should stay |
| at least ten feet away and contact the local sheriffs office, police         |
| department or state highway patrol immediately."                             |
|                                                                              |
| NC Incident No. 02-12.                                                       |
|                                                                              |
| * * * UPDATED AT 0012 EST ON 3/31/02 BY LEE COX TO FANGIE JONES * * *        |
|                                                                              |
| The truck has been recovered by the Sheriff's department and will be picked  |
| up by the North Carolina Division of Radiation Protection until the licensee |
| can take possesstion.  The gauge in it's storage box was recovered           |
| separately.  The gauge and box appear undamaged and a survey will be         |
| conducted  when the North Carolina Division of Radiation Protection arrives  |
| on scene.  An additional report willl be sent later in the week.             |
|                                                                              |
| The R2DO (Carolyn Evans) and NMSS EO (Patricia Holahan) were notified.       |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38817       |
+------------------------------------------------------------------------------+
                         
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SUSQUEHANNA              REGION:  1  |NOTIFICATION DATE: 03/30/2002|
|    UNIT:  [1] [2] []                STATE:  PA |NOTIFICATION TIME: 03:12[EST]|
|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        03/29/2002|
+------------------------------------------------+EVENT TIME:        23:40[EST]|
| NRC NOTIFIED BY:  ROBERT BEOSCH                |LAST UPDATE DATE:  03/30/2002|
|  HQ OPS OFFICER:  LEIGH TROCINE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |WILLIAM RULAND       R1      |
|10 CFR SECTION:                                 |                             |
|AIND 50.72(b)(3)(v)(D)   ACCIDENT MITIGATION    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Refueling        |0        Refueling        |
|2     N          Y       24       Power Operation  |24       Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| TECHNICAL SPECIFICATION 3.0.3 ENTRY DUE TO LOW SERVICE WATER SUCTION        
|
| PRESSURE AND THE SUBSEQUENT LOSS OF CHILLERS FOR THE CONTROL ROOM
EMERGENCY  |
| OUTSIDE AIR SUPPLY (CREOAS) AND CONTROL ROOM FLOOR COOLING                   |
|                                                                              |
| The following text is a portion of a facsimile received from the licensee:   |
|                                                                              |
| "Unit 1 was in Mode 5, day 28 of a refuel and inspection outage.  Unit 2 was |
| in Mode 1, 24% power for scheduled maintenance work requiring River Water    |
| Makeup to both units' cooling towers [to be] out of service."                |
|                                                                              |
| "At 2340 hours, Unit 1 began to experience low suction pressure to the 'C'   |
| Service Water pump, the only pump in service at the time.  Service Water     |
| takes suction from the Unit 1 Cooling Tower, and this condition resulted in  |
| low system discharge pressure and flow.  Service Water is the normal cooling |
| source for Units 1 [and] 2 Control Structure [Heating Ventilation and Air    |
| Conditioning (HVAC)].  The 'A' Control Structure chiller tripped, and the    |
| 'B' Control Structure chiller failed to start due to the low flow condition  |
| on service water.  With both chillers tripped and unavailable for CREOAS and |
| Control Room Floor Cooling, [the Limiting Condition for Operation (LCO) for  |
| Technical Specification] 3.0.3 was entered on Unit 2.  This represented a    |
| Loss of Safety Function for Accident Mitigation and requires an [8-hour] ENS |
| notification in accordance with 10CFR50.72(b)(3)(v)."                        |
|                                                                              |
| "The Control Structure chillers were realigned to Emergency Service Water    |
| (ESW), its backup emergency cooling source.  The 'A' Chiller failed to       |
| re-start, but the 'B' Chiller was successfully placed in service.  LCO 3.0.3 |
| was able to be exited on Unit 2 at 0012 hours on 3/30/02."                   |
|                                                                              |
| "An investigation is ongoing into why the 'A' Control Structure failed to    |
| re-start and the cause of the low suction pressure on Service Water."        |
|                                                                              |
| The licensee stated that all systems functioned as required.                 |
|                                                                              |
| The licensee notified the NRC resident inspector.                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38818       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SUSQUEHANNA              REGION:  1  |NOTIFICATION DATE: 03/31/2002|
|    UNIT:  [1] [2] []                STATE:  PA |NOTIFICATION TIME: 05:32[EST]|
|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        03/31/2002|
+------------------------------------------------+EVENT TIME:        04:10[EST]|
| NRC NOTIFIED BY:  GORDON ROBINSON              |LAST UPDATE DATE:  03/31/2002|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |WILLIAM RULAND       R1      |
|10 CFR SECTION:                                 |                             |
|AINA 50.72(b)(3)(v)(A)   POT UNABLE TO SAFE SD  |                             |
|AINB 50.72(b)(3)(v)(B)   POT RHR INOP           |                             |
|AINC 50.72(b)(3)(v)(C)   POT UNCNTRL RAD REL    |                             |
|AIND 50.72(b)(3)(v)(D)   ACCIDENT MITIGATION    |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Cold Shutdown    |0        Cold Shutdown    |
|2     N          Y       87       Power Operation  |87       Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| DIESEL GENERATORS DECLARED INOPERABLE FOR SHORT TIME PERIOD                  |
|                                                                              |
| "During performance of 24 month Division 1 Diesel Generator LOCA/LOOP        |
| surveillance testing, two pump start timers failed to meet the required      |
| acceptance criteria. The A RHR Pump timer actuated at 3.72 seconds           |
| (criteria: 2.7 sec. to 3.6 sec) and the C ESW Pump timer actuated at 39.24   |
| seconds (criteria: 39.6 sec. to 48.4 sec). With failure of the timers proper |
| loading on the Diesel Generators is not assured, and they ['A' and 'C'] were |
| declared inoperable until the associated pump control breakers were opened.  |
| The Susquehanna safety analysis requires three operable Diesel Generators to |
| safely shutdown the plant. Therefore with only two operable Diesel           |
| Generators, the condition requires an 8 hr ENS notification in accordance    |
| with 10CFR50.72(b)(3)(v) and (vi)."                                          |
|                                                                              |
| With Unit 1 shutdown the 'A' RHR pump is not needed, but the 'C' ESW pump    |
| does need to be operable resulting in part of the 8 hour report.             |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+
