The U.S. Nuclear Regulatory Commission is in the process of rescinding or revising guidance and policies posted on this webpage in accordance with Executive Order 14151 Ending Radical and Wasteful Government DEI Programs and Preferencing, and Executive Order 14168 Defending Women From Gender Ideology Extremism and Restoring Biological Truth to the Federal Government. In the interim, any previously issued diversity, equity, inclusion, or gender-related guidance on this webpage should be considered rescinded that is inconsistent with these Executive Orders.

Event Notification Report for December 13, 2001

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           12/12/2001 - 12/13/2001

                              ** EVENT NUMBERS **

38558  38559  
.
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38558       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CALLAWAY                 REGION:  4  |NOTIFICATION DATE: 12/12/2001|
|    UNIT:  [1] [] []                 STATE:  MO |NOTIFICATION TIME: 11:32[EST]|
|   RXTYPE: [1] W-4-LP                           |EVENT DATE:        12/12/2001|
+------------------------------------------------+EVENT TIME:        08:20[CST]|
| NRC NOTIFIED BY:  STEVEN AUFDEMBERGE           |LAST UPDATE DATE:  12/12/2001|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |GREG PICK            R4      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION REGARDING NPDES PERMIT VIOLATION                        |
|                                                                              |
| "This 4-hour call is being made to the NRC based on the requirements of      |
| 10CFR50.72(b)(2)(xi). A written report was submitted to the Missouri         |
| Department of Natural Resources concerning the discharge of plant processed  |
| water to a storm water runoff outfall inconsistent with the terms and        |
| conditions of Callaway Plant's NPDES permit. This written report was         |
| submitted on December 12, 2001, and addresses a discharge of water from the  |
| plant circulating water system that occurred on December 7, 2001.            |
|                                                                              |
| "On December 12, 2001, the Missouri Department of Natural Resources (Mo.     |
| DNR) was notified that a discharge of plant processed water from our         |
| circulating water system, occurred. This event occurred on December 7, 2001  |
| and was the result of a minor leak that developed at a caulked construction  |
| joint in our cooling tower basin.                                            |
|                                                                              |
| "This event resulted in a notification to the Mo. DNR on 12/12/01. It was    |
| concluded this event is reportable per 10CFR50.72(b)(2)(xi) since it         |
| represents a notification to a government agency relating to the protection  |
| of the environment."                                                         |
|                                                                              |
| The NRC Resident Inspector was notified of this event by the licensee.       |
+------------------------------------------------------------------------------+
.
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38559       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: RIVER BEND               REGION:  4  |NOTIFICATION DATE: 12/12/2001|
|    UNIT:  [1] [] []                 STATE:  LA |NOTIFICATION TIME: 15:58[EST]|
|   RXTYPE: [1] GE-6                             |EVENT DATE:        10/15/2001|
+------------------------------------------------+EVENT TIME:        00:01[CST]|
| NRC NOTIFIED BY:  DAVID CLYMER                 |LAST UPDATE DATE:  12/12/2001|
|  HQ OPS OFFICER:  LEIGH TROCINE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |GREG PICK            R4      |
|10 CFR SECTION:                                 |                             |
|AINV 50.73(a)(1)         INVALID SPECIF SYSTEM A|                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE  
|
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       80       Power Operation  |80       Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| ISOLATION OF DIVISION I CONTAINMENT ISOLATION VALVES DUE TO THE
UNEXPECTED   |
| TRIP OF THE FEEDER BREAKER FOR A NON-SAFETY 480-VOLT AC SWITCHGEAR 
(60-Day  |
| Report)                                                                      |
|                                                                              |
| The following text is a portion of a facsimile received from the licensee:   |
|                                                                              |
| "On October 15, 2001, at approximately 12:01 a.m., with the plant at         |
| approximately 80% power, an isolation of Division I containment isolation    |
| valves occurred.  This event was caused by the unexpected trip of the feeder |
| breaker for one of the plant's non-safety 480-volt AC switchgears.  In       |
| addition, five manual breakers on the same switchgear opened.  This          |
| deenergized the normal power supply to the Division I reactor protection     |
| system (RPS), which caused the actuation of Division I containment isolation |
| valves.  This event is being reported in accordance with the 60-day          |
| telephone notification provision in 10CFR50.73(a)(2)(iv)(A) as an invalid    |
| general containment isolation signal."                                       |
|                                                                              |
| "Division I containment isolation valves automatically closed, and the       |
| Division I annulus mixing and standby gas treatment systems received an      |
| automatic start signal.  Consistent with plant design, isolation of the      |
| annulus pressure control system subsequently caused the Division II annulus  |
| mixing and standby gas treatment systems to start.  However, the Division II |
| annulus mixing fan breaker tripped open after receiving a close signal.      |
| Both divisions of the fuel building charcoal filter trains started.  The     |
| Division I containment atmosphere hydrogen analyzer automatically started."  |
|                                                                              |
| "After an initial assessment, operators implemented abnormal operating       |
| procedures and restored systems in containment to their normal alignment.    |
| Plant operation was not interrupted.  Except for the trip of the Division II |
| annulus mixing fan, all plant systems responded as designed to the event.    |
| The fan trip is being addressed within the stations corrective action        |
| program."                                                                    |
|                                                                              |
| "The investigation of the spurious breaker trips is still in progress.       |
| Tests completed thus far have not determined the cause of the trip, and      |
| switchgear inspections performed during a brief plant outage in the interim  |
| found no hardware deficiencies.  The Division I RPS system remains powered   |
| from its alternate source, which will prevent its loss should the switchgear |
| again be de-energized.  The switchgear has been instrumented in order to     |
| collect transient data in the event the trips recur."                        |
|                                                                              |
| The licensee notified the NRC resident inspector.                            |
+------------------------------------------------------------------------------+
.


Page Last Reviewed/Updated Wednesday, March 24, 2021