Skip to main content

The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.

Event Notification Report for September 18, 2001

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           09/17/2001 - 09/18/2001

                              ** EVENT NUMBERS **

38233  38291  

!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38233       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: COLUMBIA GENERATING STATIREGION:  4  |NOTIFICATION DATE: 08/24/2001|
|    UNIT:  [2] [] []                 STATE:  WA |NOTIFICATION TIME: 17:05[EDT]|
|   RXTYPE: [2] GE-5                             |EVENT DATE:        08/24/2001|
+------------------------------------------------+EVENT TIME:        13:05[PDT]|
| NRC NOTIFIED BY:  FISHER                       |LAST UPDATE DATE:  09/17/2001|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |BILL JONES           R4      |
|10 CFR SECTION:                                 |                             |
|DDDD 73.71               UNSPECIFIED PARAGRAPH  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| SAFEGUARDS SYSTEM DEGRADATION RELATED TO AREA BOUNDARY                       |
|                                                                              |
| IMMEDIATE COMPENSATORY MEASURES TAKEN UPON TO DISCOVERY                      |
|                                                                              |
| THE NRC RESIDENT INSPECTOR WILL BE NOTIFIED                                  |
|                                                                              |
| CONTACT THE HEADQUARTERS OPERATION CENTER FOR ADDITIONAL DETAILS.            |
|                                                                              |
| * * * RETRACTED AT 1407 EDT ON 9/17/2001 BY MICHAEL FERRY TO FANGIE JONES *  |
| * *                                                                          |
|                                                                              |
| The licensee retracted this notification after further review of the event   |
| particulars.  The licensee notified the NRC Resident Inspector.  The R4DO    |
| (John Pellet) has been notified.                                             |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38291       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CALLAWAY                 REGION:  4  |NOTIFICATION DATE: 09/17/2001|
|    UNIT:  [1] [] []                 STATE:  MO |NOTIFICATION TIME: 19:05[EDT]|
|   RXTYPE: [1] W-4-LP                           |EVENT DATE:        09/17/2001|
+------------------------------------------------+EVENT TIME:        12:05[CDT]|
| NRC NOTIFIED BY:  B. BREDMAN                   |LAST UPDATE DATE:  09/17/2001|
|  HQ OPS OFFICER:  JOHN MacKINNON               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |JOHN PELLET          R4      |
|10 CFR SECTION:                                 |                             |
|AESF 50.72(b)(3)(iv)(A)  VALID SPECIF SYS ACTUAT|                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| LOSS OF NON-SAFETY RELATED 125 VOLT DC BUS RESULTED IN BOTH MOTOR DRIVEN     |
| AUXILIARY FEEDWATER PUMPS  STARTING.                                         |
|                                                                              |
|                                                                              |
| During routine scheduled maintenance activities, power was lost to a         |
| non-safety related 125 volt DC bus.  Loss of power to the bus resulted in    |
| loss of oil pressure indication on 1 of 2 channels on both main feedwater    |
| pumps, which in turn resulted in the actuation of both motor driven          |
| auxiliary feedwater pumps.  The motor driven auxiliary feedwater pumps ran   |
| for approximately 3 minutes. Reactor power increased but no over power event |
| occurred.                                                                    |
| Power has been restored to the non-safety related 125 volt bus and the motor |
| driven auxiliary feedwater pumps have been secured.                          |
|                                                                              |
| The licensee is looking into that maybe when cross connecting the 125 volt   |
| DC buses that one of the two fuse disconnect switches might have had a blown |
| fuse which would have resulted in the above event.                           |
|                                                                              |
| The NRC Resident Inspector was notified of this event by the licensee.       |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Thursday, March 25, 2021