The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.
Event Notification Report for August 16, 2001
U.S. Nuclear Regulatory Commission
Operations Center
Event Reports For
08/15/2001 - 08/16/2001
** EVENT NUMBERS **
38206 38209 38210 38211
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38206 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PILGRIM REGION: 1 |NOTIFICATION DATE: 08/13/2001|
| UNIT: [1] [] [] STATE: MA |NOTIFICATION TIME: 21:31[EDT]|
| RXTYPE: [1] GE-3 |EVENT DATE: 08/13/2001|
+------------------------------------------------+EVENT TIME: 17:53[EDT]|
| NRC NOTIFIED BY: V. FALLACARA |LAST UPDATE DATE: 08/15/2001|
| HQ OPS OFFICER: JOHN MacKINNON +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |RONALD BELLAMY R1 |
|10 CFR SECTION: | |
|ARPS 50.72(b)(2)(iv)(B) RPS ACTUATION - CRITICA| |
|AESF 50.72(b)(3)(iv)(A) VALID SPECIF SYS ACTUAT| |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 A/R Y 100 Power Operation |0 Hot Shutdown |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| UNEXPECTED REACTOR SCRAM DURING LOGIC SYSTEM TESTING OF EMERGENCY BUS A5. |
| |
| Pilgrim Unit 1 scrammed from 100% during performance of Logic System Testing |
| of Emergency Bus A5. This is the first time that the Logic System Testing |
| of Emergency Bus A5 had been performed at power. The test is performed once |
| every 24 months and had just been rewritten to be performed at power. The |
| cause of the scram is under investigation at this time but the initiating |
| transient was the loss of Emergency Bus A5. All rods fully inserted into |
| the core. The plant is at 700 lbs. and a controlled depressurization is in |
| progress. Plans are to cool down to less than or equal to 150 lbs. and |
| repair the outboard RCIC steam isolation valve. |
| |
| Due to deenergization of Emergency Bus A5, Recirculation Pump A tripped and |
| there was a fast transfer of the swing bus (this was expected). The |
| licensee is looking into the transfer of the swing bus causing the trip of |
| Recirculation Pump B. Loss of both operating Recirculation Pumps at power |
| will cause a reactor scram. All systems operated properly. The |
| electrical grid is stable and all Emergency Core Cooling systems are fully |
| operable if needed. The Recirculation pumps will be restarted when the |
| differential temperature between the top and bottom head are within |
| specification. |
| |
| The NRC Resident Inspector was notified of this event by the licensee. |
| |
| **** UPDATE ON 08/14/01 AT 1338ET BY V. FALLACARA TAKEN BY MACKINNON **** |
| |
| This is a supplement report to detail additional information on the scram a |
| Pilgrim, Unit 1 on 08/13/01. |
| |
| Upon further evaluation of the event and the requirements of 10CFR50.72 and |
| NUREG-1022, Pilgrim is reporting the valid actuation of the following |
| containment isolation groups immediately following the scram: Group 2 |
| (Secondary Isolations), Group 6 (Reactor Water Cleanup), and Reactor |
| Building Isolation with initiation of Standby Gas Treatment Systems. These |
| are expected occurrences in a post-scram transient due to reactor water |
| level shrink below the Reactor Level Setpoint of + 12". |
| |
| Further plant response issues which are currently under investigation |
| include: |
| |
| Finalizing the cause of the "B" side RPS actuation. |
| Determining the cause of the loss of "B" Recirculation Pump. |
| Resolving a falsely pegged level indication on the "A" Reactor Water Level |
| Indication. |
| Determining the cause of the loss of 120 VAC bus Y-4. |
| |
| An event analysis team has been formed to drive out all of these issues. |
| R1DO (Ron Bellamy) notified. |
| |
| The NRC Resident Inspector was notified of this event by the licensee. |
| |
| ***** UPDATE FROM VINCENT FALLACARA TO LEIGH TROCINE RECEIVED AT 1420 ON |
| 08/15/01 ***** |
| |
| The following text is a portion of a facsimile received from the licensee: |
| |
| "This is a supplemental report to further clarify information initially |
| provided concerning logic system testing of the Division 1 Emergency Bus as |
| it related to the 08/13/01 automatic shutdown." |
| |
| "The initial information indicated that this was the first time this testing |
| had been performed at power and that the test had been rewritten to be |
| performed at power." |
| |
| "This initial information did not clearly describe the situation concerning |
| this testing. Emergency Bus Relay testing has been successfully performed |
| at power in the past. This test procedure was reformatted to delineate Tech |
| Spec required testing from non-Tech Spec required testing to reduce the |
| unnecessary Diesel Generator unavailability time. During reformatting, an |
| error was introduced which left out a needed prerequisite to successfully |
| complete the Tech Spec required testing of the A-EDG output breaker. This |
| is currently believed to be an initiating event that contributed to the |
| 08/13/01 automatic shutdown." |
| |
| "At this time, Pilgrim is in Cold Shutdown. The Events Analysis Team |
| continues to investigate previously identified plant issues related to this |
| shutdown." |
| |
| The licensee plans to notify the NRC resident inspector. The NRC operations |
| officer notified the R1DO (Bellamy). |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38209 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: TURKEY POINT REGION: 2 |NOTIFICATION DATE: 08/15/2001|
| UNIT: [3] [] [] STATE: FL |NOTIFICATION TIME: 06:30[EDT]|
| RXTYPE: [3] W-3-LP,[4] W-3-LP |EVENT DATE: 08/15/2001|
+------------------------------------------------+EVENT TIME: 04:49[EDT]|
| NRC NOTIFIED BY: JIM HICKEY |LAST UPDATE DATE: 08/15/2001|
| HQ OPS OFFICER: STEVE SANDIN +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |CHARLIE PAYNE R2 |
|10 CFR SECTION: | |
|ARPS 50.72(b)(2)(iv)(B) RPS ACTUATION - CRITICA| |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|3 M/R Y 15 Power Operation |0 Hot Standby |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| UNIT 3 WAS MANUALLY TRIPPED DURING A LOAD REDUCTION DUE TO A LOSS OF |
| CONDENSER VACUUM. |
| |
| "During a Unit 3 load reduction, a manual reactor trip was initiated. Plant |
| documents provide guidance for manually tripping the reactor. |
| |
| "If reactor power is greater than 10% and condenser vacuum decreases below |
| 24.5" Hg with generator load less than 531 MWe, then the reactor is manually |
| tripped. |
| |
| "The balance-of-plant operator noted condenser vacuum at 24.2" Hg with |
| reactor power at 15% and generator load at 30 MWe. The Unit RCO with SRO |
| concurrence manually tripped the reactor. |
| |
| "Systems which did not function as required: |
| |
| a. N-35 Intermediate Range; High Level Trip did not clear as expected. |
| b. N-36 Intermediate Range; Spiking indication following reactor trip. |
| c. Rod Position Indicator E-9 indicates mid-scale approximately 117 steps |
| (Rod Bottom light on)." |
| |
| The licensee has the cause for the loss of condenser vacuum under |
| investigation. The licensee will inform the NRC resident inspector. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38210 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: FERMI REGION: 3 |NOTIFICATION DATE: 08/15/2001|
| UNIT: [2] [] [] STATE: MI |NOTIFICATION TIME: 12:04[EDT]|
| RXTYPE: [2] GE-4 |EVENT DATE: 08/14/2001|
+------------------------------------------------+EVENT TIME: 16:44[EDT]|
| NRC NOTIFIED BY: GREG MILLER |LAST UPDATE DATE: 08/15/2001|
| HQ OPS OFFICER: LEIGH TROCINE +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |THOMAS KOZAK R3 |
|10 CFR SECTION: | |
|HFIT 26.73 FITNESS FOR DUTY | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| POSITIVE, FOR-CAUSE, FITNESS-FOR-DUTY TEST |
| |
| The following text is a portion of a facsimile received from the licensee: |
| |
| "On August 14, 2001, at 1655 hours, a [non-licensed contract] supervisor |
| tested positive for an illegal substance as a result of a for-cause test. |
| Access to the protected area was suspended at 1659 hours on August 14, 2001. |
| A review of the individual's work activities was performed, and no deficient |
| work practices which could impact safety-related equipment/systems were |
| identified. The employee has been denied further access to the Fermi Energy |
| Center." |
| |
| Call the NRC operations officer for additional details. |
| |
| The licensee notified the NRC resident inspector and NRC Region 3 office |
| (Gary Pirtle). |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38211 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PEACH BOTTOM REGION: 1 |NOTIFICATION DATE: 08/15/2001|
| UNIT: [2] [3] [] STATE: PA |NOTIFICATION TIME: 13:12[EDT]|
| RXTYPE: [2] GE-4,[3] GE-4 |EVENT DATE: 08/15/2001|
+------------------------------------------------+EVENT TIME: 05:50[EDT]|
| NRC NOTIFIED BY: BREIDENBAUGH |LAST UPDATE DATE: 08/15/2001|
| HQ OPS OFFICER: LEIGH TROCINE +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |RONALD BELLAMY R1 |
|10 CFR SECTION: | |
|ACOM 50.72(b)(3)(xiii) LOSS COMM/ASMT/RESPONSE| |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2 N Y 100 Power Operation |100 Power Operation |
|3 N Y 82 Power Operation |82 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| UNEXPECTED LOSS OF POWER TO THE TECHNICAL SUPPORT CENTER |
| |
| The following text is a portion of a facsimile received from the licensee: |
| |
| "An unexpected electrical breaker trip has caused a loss of power to the |
| Technical Support Center (TSC). On 08/15/01 at 0550, the Main Control Room |
| was notified that the TSC, which is located in a building adjacent to the |
| protected area, was without power." |
| |
| "Subsequent investigation revealed that the feed breakers supplying power to |
| the affected bus had tripped. Further investigation is in progress to |
| identify and repair any deficiencies. In accordance with station |
| procedures, contingency actions are in place should an event occur which |
| required the use of the TSC. Communication remains available from the |
| TSC." |
| |
| The licensee notified the NRC resident inspector. |
+------------------------------------------------------------------------------+
Page Last Reviewed/Updated Thursday, March 25, 2021
Page Last Reviewed/Updated Thursday, March 25, 2021