Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for July 17, 2001

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           07/16/2001 - 07/17/2001

                              ** EVENT NUMBERS **

38142  38143  38144  38145  38146  

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38142       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: WATERFORD                REGION:  4  |NOTIFICATION DATE: 07/15/2001|
|    UNIT:  [3] [] []                 STATE:  LA |NOTIFICATION TIME: 23:32[EDT]|
|   RXTYPE: [3] CE                               |EVENT DATE:        07/15/2001|
+------------------------------------------------+EVENT TIME:        21:58[CDT]|
| NRC NOTIFIED BY:  RAY PELLEGRIN                |LAST UPDATE DATE:  07/16/2001|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          ALERT                 |CHUCK CAIN           R4      |
|10 CFR SECTION:                                 |TAD MARSH            NRR     |
|AAEC 50.72(a) (1) (i)    EMERGENCY DECLARED     |NADER MAMISH         IRO     |
|                                                |SAM COLLINS          NRR     |
|                                                |JIM MULLINS          EPA     |
|                                                |CANUPP               FEMA    |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|3     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| ALERT DECLARED DUE TO TOXIC GAS RELEASE NEAR PLANT SITE                      |
|                                                                              |
| The licensee declared an Alert (EAL EP-4-010 "Toxic Chemical Contingency")   |
| due to an anhydrous ammonia release at the Occidental Chemical facility      |
| located near the site.  The licensee reported that no ammonia has been       |
| detected onsite; however, personnel sheltering has been implemented. The     |
| release is ongoing and the chemical facility cannot estimate when the        |
| release will be secured. The NRC entered Monitoring at 0012EDT on 7/16/01.   |
|                                                                              |
| * * * UPDATE 0300EDT ON 7/16/01 FROM LICENSEE COMMUNICATOR TO S.SANDIN * *   |
| *                                                                            |
|                                                                              |
| The licensee terminated the Alert at 0200CDT after verifying that all        |
| exiting conditions were satisfied.  The licensee informed the NRC resident   |
| inspector and will inform state/local agencies.  The NRC exited Monitoring   |
| at 0315EDT on 7/16/01.  Notified FEMA(Canupp), DOE(Stambaugh),               |
| EPA-DOT(Loreck), USDA(Conley) and HHS-CDC(Cruz).                             |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38143       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: MCGUIRE                  REGION:  2  |NOTIFICATION DATE: 07/16/2001|
|    UNIT:  [] [2] []                 STATE:  NC |NOTIFICATION TIME: 11:20[EDT]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        07/16/2001|
+------------------------------------------------+EVENT TIME:        09:58[EDT]|
| NRC NOTIFIED BY:  BILL MASON                   |LAST UPDATE DATE:  07/16/2001|
|  HQ OPS OFFICER:  STEVE SANDIN                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |JAY HENSON           R2      |
|10 CFR SECTION:                                 |                             |
|ARPS 50.72(b)(2)(iv)(B)  RPS ACTUATION - CRITICA|                             |
|AESF 50.72(b)(3)(iv)(A)  VALID SPECIF SYS ACTUAT|                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     A/R        Y       100      Power Operation  |0        Hot Standby      |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AUTOMATIC REACTOR TRIP DURING MAINTENANCE                                    |
|                                                                              |
| "The channel 2 of the 2B streamline pressure was in test.  The channel 3 of  |
| the 2B streamline pressure was taken out of service (transmitter).  This     |
| resulted in meeting the logic for main streamline isolation (2/3).  This     |
| resulted in a reactor trip on overtemperature delta temperature.  Auxiliary  |
| feedwater autostarted due to decreasing steam generator water levels.  This  |
| event started as a result of preventative maintenance of steam generator     |
| pressure 2B channel 2."                                                      |
|                                                                              |
| All rods fully inserted.  Unit 2 is stable in mode 3 at 2235 psig and 556    |
| degrees F with decay heat removal bypassing the main streamline isolation    |
| valves to the main condenser.  Efforts are underway to restore main          |
| feedwater and secure the operating auxiliary feedwater pumps (both           |
| electrical and the turbine driven).  During the transient all three primary  |
| PORVs lifted and reseated while secondary safety valves also cycled.  There  |
| is no known primary-to-secondary tube leakage.  All emergency equipment is   |
| available, if needed.  The licensee informed the NRC resident inspector and  |
| does not plan a press release.                                               |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38144       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: VOGTLE                   REGION:  2  |NOTIFICATION DATE: 07/16/2001|
|    UNIT:  [1] [2] []                STATE:  GA |NOTIFICATION TIME: 14:51[EDT]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        07/16/2001|
+------------------------------------------------+EVENT TIME:        10:33[EDT]|
| NRC NOTIFIED BY:  DORMAN                       |LAST UPDATE DATE:  07/16/2001|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |JAY HENSON           R2      |
|10 CFR SECTION:                                 |                             |
|ACOM 50.72(b)(3)(xiii)   LOSS COMM/ASMT/RESPONSE|                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| PLANT HAD A MAJOR LOSS OF OFFSITE PUBLIC ALERTING SIREN SYSTEM               |
|                                                                              |
| While performing the weekly siren test, 35 of 47 sirens failed to respond.   |
| The weekly test was performed at 1033 EDT.  Preliminary investigation        |
| suggests a problem with the sirens electronic memory chip.  Troubleshooting  |
| and repairs are in progress.                                                 |
|                                                                              |
| The NRC Resident Inspector has been notified.                                |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   38145       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  NORTECH ENVIRONMENTAL                |NOTIFICATION DATE: 07/16/2001|
|LICENSEE:  NORTECH ENVIRONMENTAL                |NOTIFICATION TIME: 16:36[EDT]|
|    CITY:  FAIRBANKS                REGION:  4  |EVENT DATE:        07/16/2001|
|  COUNTY:                            STATE:  AK |EVENT TIME:        08:00[YDT]|
|LICENSE#:                        AGREEMENT:  N  |LAST UPDATE DATE:  07/16/2001|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |DAVID GRAVES         R4      |
|                                                |JOSEPHINE PICCONE    NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  CHEEK                        |                             |
|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|BAB1 20.2201(a)(1)(i)    LOST/STOLEN LNM>1000X  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| NORTECH ENVIRONMENTAL REPORTED THAT AN  X-RAY FLUORESCENCE DEVICE WAS STOLEN |
| FROM THEIR OFFICES                                                           |
|                                                                              |
| The device was stolen sometime this past weekend, but was just discovered    |
| this morning at 0800 YDT to be missing.  The device was a Niton XL model 309 |
| serial #U1002 containing 14 millicuries of cadmium-109 (serial #NR0853).     |
| This device was a hand held device used to analyze for lead in paint.  The   |
| local police and Niton have been notified.  The State will be notified.      |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   38146       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  TENNESSEE VALLEY AUTHORITY           |NOTIFICATION DATE: 07/16/2001|
|LICENSEE:  TENNESSEE VALLEY AUTHORITY           |NOTIFICATION TIME: 16:57[EDT]|
|    CITY:  MUSCLE SHOALS            REGION:  2  |EVENT DATE:        07/13/2001|
|  COUNTY:                            STATE:  AL |EVENT TIME:             [CDT]|
|LICENSE#:  01-06113-04           AGREEMENT:  Y  |LAST UPDATE DATE:  07/16/2001|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |JAY HENSON           R2      |
|                                                |JOSEPHINE PICCONE    NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  KNUETTEL / FLANIGAN          |                             |
|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NINF                     INFORMATION ONLY       |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| THE LICENSEE REPORTED THE RELEASE OF CONTAMINATED MATERIAL                   |
|                                                                              |
| On 7/13/01 two 30 gallon trash cans containing expendable contaminated lab   |
| items such as pipette tips, gloves, empty bottles, beakers, etc. were        |
| emptied into a dumpster.  These items were at very low levels and had been   |
| collected in the two trash cans since January.  The typical analysis that is |
| done in the laboratory is on nuclear plant effluent samples from which these |
| items received their contamination.  Only the items used to handle the       |
| effluent sample material were discarded in the two trash cans.  The material |
| itself was not disposed in these trash cans.  The dumpster was taken to the  |
| Hillsboro landfill in Lawrence County, AL this morning.                      |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Thursday, March 25, 2021