The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.
Event Notification Report for July 13, 2001
U.S. Nuclear Regulatory Commission
Operations Center
Event Reports For
07/12/2001 - 07/13/2001
** EVENT NUMBERS **
38045 38123 38130 38131 38132 38133 38134 38135 38136
!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38045 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: COLUMBIA GENERATING STATIREGION: 4 |NOTIFICATION DATE: 06/01/2001|
| UNIT: [2] [] [] STATE: WA |NOTIFICATION TIME: 19:53[EDT]|
| RXTYPE: [2] GE-5 |EVENT DATE: 06/01/2001|
+------------------------------------------------+EVENT TIME: 14:02[PDT]|
| NRC NOTIFIED BY: MYRON BAIRD |LAST UPDATE DATE: 07/12/2001|
| HQ OPS OFFICER: FANGIE JONES +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |DALE POWERS R4 |
|10 CFR SECTION: | |
|AESF 50.72(b)(3)(iv)(A) VALID SPECIF SYS ACTUAT| |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2 N N 0 Refueling |0 Refueling |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| INADVERTENT LOSS OF POWER TO A SAFETY BUS |
| |
| "At 1402 PST, with Columbia Generating Station in Mode 5, a loss of 230 KV |
| offsite source (startup transformer) occurred. This resulted in a loss of |
| voltage to the Div 2 safety related bus (SM-8) which was automatically |
| reenergized by the 115 KV offsite source (backup transformer). All plant |
| systems and components responded as expected. No core alterations were in |
| progress. SM-8 was inoperable but energized at the time of the event due to |
| planned outage maintenance. There was no challenge to the plant shutdown |
| safety plan as a result of this loss of offsite power. The loss of power |
| was a result of a lightning strike offsite on the Bonneville Power |
| Administration (BPA) electrical grid. Restoration of the 230 KV source is |
| pending repairs to damage on the BPA grid. This notification is being made |
| pursuant to 10CFR50.72(b)(3)(iv)(B)(8). This is a valid actuation of an |
| Emergency AC electrical power system." |
| |
| The licensee notified the NRC Resident Inspector. |
| |
| * * * RETRACTION 1741 FROM SHERMAN TAKEN BY STRANSKY * * * |
| |
| "Columbia Generating Station hereby retracts a report made to the NRC |
| Operations Center on June 1st, 2001 at 1953 hours. Event Notification number |
| was 38045. The report was made pursuant to 10 CFR 50.72(b)(3)(iv)(B)(8) and |
| documented that a lightning strike resulted in a loss of a 230kV offsite |
| power line to a safety related electrical bus (SM-8) due to a startup |
| transformer tripping offline. At the time of the event, the plant was |
| already shut down in Mode 5. The safety related electrical bus was |
| automatically reenergized by the backup offsite 115 kV electrical source |
| through the backup transformer. |
| |
| "It was assumed at the time of the report that a loss of offsite power was |
| an actuation of an emergency AC power system. Upon further review, we have |
| concluded that an automatic bus transfer of offsite power is an alternate |
| normal power supply and not in the scope of NUREG-1022 as an actuation of an |
| emergency AC power source. Our licensing basis documents also refer to the |
| emergency diesel generators as the source of all emergency AC power." |
| |
| The NRC resident inspector will be informed of this retraction. Notified |
| R4DO (Cain). |
+------------------------------------------------------------------------------+
!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38123 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CLINTON REGION: 3 |NOTIFICATION DATE: 07/09/2001|
| UNIT: [1] [] [] STATE: IL |NOTIFICATION TIME: 13:07[EDT]|
| RXTYPE: [1] GE-6 |EVENT DATE: 07/09/2001|
+------------------------------------------------+EVENT TIME: 09:00[CDT]|
| NRC NOTIFIED BY: JAMIE BARTSCH |LAST UPDATE DATE: 07/13/2001|
| HQ OPS OFFICER: FANGIE JONES +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |DAVID HILLS R3 |
|10 CFR SECTION: | |
|AIND 50.72(b)(3)(v)(D) ACCIDENT MITIGATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| CONTROL ROOM VENTILATION SYSTEM DECLARED INOPERABLE |
| |
| The Division 2 Main Control Room Ventilation System was declared inoperable |
| at 0900 CDT on 7/9/2001 because it was not maintaining the required positive |
| pressure while running in the High Radiation Mode of operation. The system |
| was declared operable at 0913 CDT when the required positive pressure was |
| restored. During the 13 minute period Division 2 was inoperable, Division 1 |
| Main Control Room Ventilation System was inoperable due to a scheduled |
| maintenance outage. Therefore, with both systems inoperable, a condition |
| existed which could have prevented the fulfillment of the safety function of |
| the Main Control Room Ventilation System needed to mitigate the consequences |
| of an accident. The cause of the perturbation in control room pressure is |
| being investigated. |
| |
| The licensee notified the NRC Resident Inspector. |
| |
| *** RETRACTION FROM STEVEN STRICKLAN RECEIVED BY LEIGH TROCINE AT 0451 EDT |
| ON 07/13/01 *** |
| |
| The licensee is retracting this event notification. The following text is a |
| portion of a facsimile received from the licensee: |
| |
| "On 07/09/01, at approximately 0900 [CDT], the Clinton Power Station (CPS) |
| experienced a transient situation where, for a period of 13 minutes, the |
| positive pressure in the Main Control Room (MCR) was compromised. Based on |
| this condition, an ENS notification (#38123) was made in accordance with the |
| requirements of 10CFR50.72(b)(3)(v), any event or condition that at the time |
| of discovery could have prevented the fulfillment of the safety function of |
| structures or systems that are needed to: |
| (A) shut down the reactor and maintain it in a safe shutdown condition; |
| (B) remove residual heat; |
| (C) control the release of radioactive material; or |
| (D) mitigate the consequences of an accident." |
| |
| "An evaluation of the conditions present at the time positive pressurization |
| of the MCR was temporarily interrupted has been performed. The evaluation |
| results indicated that the conditions that potentially existed during this |
| event were bounded by the design basis analysis performed for the [MCR]. |
| The calculated MCR operator thyroid dose for this event was determined to be |
| approximately 23.185 Rem, which is less than the USAR calculated dose of 25 |
| Rem. The USAR dose is calculated based on a 20-minute time delay in |
| starting the system in the high radiation mode. For this event, the high |
| radiation mode was already in operation. Whole body and Beta dose for this |
| event are not governing." |
| |
| "It [has] therefore been demonstrated that, in the event of a design basis |
| event, time dose impact of the condition as it existed would be bounded by |
| the current analyses of record. As such, the safety function would be |
| fulfilled, and the ENS notification is retracted." |
| |
| "Although it has been demonstrated that the safety function would be |
| fulfilled, the situation represented a condition prohibited by Technical |
| Specifications, and this event continues to be evaluated for reportability |
| as a Licensee Event Report under 10CFR50.73(a)(2)(i)(B)." |
| |
| The licensee notified the NRC resident inspector. The NRC operations center |
| notified the R3DO (Hills). |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38130 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: MONTICELLO REGION: 3 |NOTIFICATION DATE: 07/11/2001|
| UNIT: [1] [] [] STATE: MN |NOTIFICATION TIME: 23:01[EDT]|
| RXTYPE: [1] GE-3 |EVENT DATE: 07/11/2001|
+------------------------------------------------+EVENT TIME: 16:50[CDT]|
| NRC NOTIFIED BY: DAVID BARNETT |LAST UPDATE DATE: 07/12/2001|
| HQ OPS OFFICER: FANGIE JONES +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |DAVID HILLS R3 |
|10 CFR SECTION: | |
|ADEG 50.72(b)(3)(ii)(A) DEGRADED CONDITION | |
|AINC 50.72(b)(3)(v)(C) POT UNCNTRL RAD REL | |
|AIND 50.72(b)(3)(v)(D) ACCIDENT MITIGATION | |
|ASHU 50.72(b)(2)(i) PLANT S/D REQD BY TS | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |99 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| PRIMARY CONTAINMENT DECLARED INOPERABLE - TECH SPEC REQUIRED SHUTDOWN |
| |
| The licensee found a shipping restraint installed on a drywell-to-torus vent |
| pipe bellows, apparently in place since construction (about 30 years). This |
| device was discovered due to another licensee with similar containment |
| configuration notifying Monticello of their discovery. This device would |
| partially impede axial motion. The primary containment was declared |
| inoperable at 1650 CDT on 07/11/01, and removal was initiated. This is an |
| 8-hour report under 10CFR50.72(b)(3)(ii)(a) as a degraded condition and |
| 10CFR50.72(b)(3)(v)(c and d), control of radiation release and accident |
| mitigation. |
| |
| The licensee initiated a required shutdown at 2050 CDT on 07/11/01 per |
| Technical Specification 3.7.A.2.a, as a result of declaring primary |
| containment inoperable because the drywell-to-torus vent pipe bellows |
| shipping installation attachments were still installed. This is a 4-hour |
| report under 10CFR50.72(b)(2)(i), technical specification required |
| shutdown. |
| |
| The licensee notified the NRC resident inspector and intends to notify state |
| and local agencies. |
| |
| ***** UPDATE FROM DAVE BARNETT RECEIVED BY LEIGH TROCINE AT 0039 EDT ON |
| 07/12/01 ***** |
| |
| The four shipping fasteners have been removed from each of the eight |
| drywell-to-torus vent pipe bellows, and primary containment was declared |
| operable at 2304 CDT on 07/11/01. The technical specification required |
| shutdown was terminated while the reactor was at 90% power. The licensee |
| currently plans to restore reactor power to 100%. |
| |
| The licensee plans to notify the NRC resident inspector as well as the |
| applicable state and county agencies. The NRC operations officer notified |
| the R3DO (Hills). |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38131 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PERRY REGION: 3 |NOTIFICATION DATE: 07/12/2001|
| UNIT: [1] [] [] STATE: OH |NOTIFICATION TIME: 00:29[EDT]|
| RXTYPE: [1] GE-6 |EVENT DATE: 07/11/2001|
+------------------------------------------------+EVENT TIME: 22:27[EDT]|
| NRC NOTIFIED BY: FREDERICK W. SMITH |LAST UPDATE DATE: 07/12/2001|
| HQ OPS OFFICER: LEIGH TROCINE +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |DAVID HILLS R3 |
|10 CFR SECTION: |TAD MARSH NRR |
|ACCS 50.72(b)(2)(iv)(A) ECCS INJECTION | |
|ARPS 50.72(b)(2)(iv)(B) RPS ACTUATION - CRITICA| |
|AESF 50.72(b)(3)(iv)(A) VALID SPECIF SYS ACTUAT| |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 A/R Y 100 Power Operation |0 Hot Shutdown |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| AUTOMATIC REACTOR SCRAM, HPCS/RCIC SYSTEM INJECTION, AND FULL |
| BALANCE-OF-PLANT ISOLATION FOLLOWING AN UNSPECIFIED, INTERNAL, ELECTRICAL |
| TRANSIENT |
| |
| An unspecified, internal, electrical transient affected balance-of-plant |
| (BOP) systems and resulted in a feedwater control circuitry problem. |
| Following this electrical transient, the reactor automatically scrammed from |
| 100% power when reactor vessel water level reached level 3 (178 inches |
| narrow range). All control rods fully inserted. When reactor vessel water |
| level decreased to level 2 (approximately 120 inches narrow range), the high |
| pressure core spray (HPCS) and reactor core isolation cooling (RCIC) systems |
| automatically initiated and injected into the reactor pressure vessel (RPV). |
| A BOP isolation signal was also received on level 2, and a full BOP |
| isolation occurred. In addition, the Division 3 emergency diesel generator |
| (EDG) automatically started on level 2 (in support of HPCS). The EDG did |
| not load, nor was it required to. The lowest reactor vessel water level |
| received was 107 inches narrow range. This was reported to be well above |
| the top of the active full, which is at 0 inches wide range. |
| |
| The licensee stated that all safety systems functioned as required. The |
| extent and cause of the electrical transient are currently under |
| investigation. It was reported that the cause may be related to a possible |
| auctioneered power supply failure which affected BOP systems and the |
| feedwater system control circuitry. |
| |
| The unit is currently in Mode 3 (Hot Shutdown). The RCIC system and the |
| main turbine bypass valves are being utilized for reactor water level |
| control and RPV pressure control, respectively. The main steam isolation |
| valves are open, and the condenser is available as a heat sink. HPCS has |
| been placed in standby. (The quantity of water injected was not available |
| at the time of this event notification.) The full BOP isolation has been |
| reset, and the Division 3 EDG is still running (unloaded). (The licensee |
| needs to load the EDG for 1 hour before securing it.) Containment |
| parameters were reported to be normal, and there were no challenges to |
| offsite power. All emergency core cooling systems and engineered safety |
| feature systems are currently available. The feedwater system remains |
| unavailable pending resolution of the transient's root cause. |
| |
| The licensee notified the NRC resident inspector (who was in the control |
| room at the time of this event notification). |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38132 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: LIMERICK REGION: 1 |NOTIFICATION DATE: 07/12/2001|
| UNIT: [1] [] [] STATE: PA |NOTIFICATION TIME: 05:21[EDT]|
| RXTYPE: [1] GE-4,[2] GE-4 |EVENT DATE: 07/11/2001|
+------------------------------------------------+EVENT TIME: 23:30[EDT]|
| NRC NOTIFIED BY: GENE MICHELSON |LAST UPDATE DATE: 07/12/2001|
| HQ OPS OFFICER: LEIGH TROCINE +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |ANTHONY DIMITRIADIS R1 |
|10 CFR SECTION: | |
|AINA 50.72(b)(3)(v)(A) POT UNABLE TO SAFE SD | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| DISCOVERY OF AN EXCESSIVE ACCUMULATION OF WATER IN TWO UNDERGROUND FUEL OIL |
| STORAGE TANKS |
| |
| The following text is a portion of a facsimile received from the licensee: |
| |
| "[An] excessive accumulation of water [was] discovered in both [the] D11 and |
| D12 underground fuel oil storage tanks. [There was 33 inches of water in |
| D11 and 22.5 inches of water in D12.] This event would prevent both diesel |
| generators from fulfilling their required safety function. [Technical |
| Specification 3.8.1.1, Actions 'b' and 'e,' were] entered, and reportability |
| manual event SAF 1.8 [was also] entered." |
| |
| "Actions Taken: Water has been removed from both [the] D11 and D12 |
| underground fuel oil storage tanks. [The licensee is] currently performing |
| [an] operability determination." |
| |
| The licensee stated that the unit is remains in the 72-hour limiting |
| condition for operation due to the ongoing operability determination. |
| |
| The licensee notified the NRC resident inspector. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38133 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: TURKEY POINT REGION: 2 |NOTIFICATION DATE: 07/12/2001|
| UNIT: [3] [4] [] STATE: FL |NOTIFICATION TIME: 14:21[EDT]|
| RXTYPE: [3] W-3-LP,[4] W-3-LP |EVENT DATE: 07/12/2001|
+------------------------------------------------+EVENT TIME: 10:45[EDT]|
| NRC NOTIFIED BY: CRAIG MOWREY |LAST UPDATE DATE: 07/12/2001|
| HQ OPS OFFICER: BOB STRANSKY +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |PAUL FREDRICKSON R2 |
|10 CFR SECTION: | |
|AUNA 50.72(b)(3)(ii)(B) UNANALYZED CONDITION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|3 N Y 100 Power Operation |100 Power Operation |
|4 N Y 100 Power Operation |100 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| UNITS IN POTENTIALLY UNANALYZED CONDITION |
| |
| "On July 12, 2001, Turkey Point determined that a previous failed |
| surveillance may have constituted an unanalyzed condition that significantly |
| degraded plant safety. On June 8, 2001, flow damper D-21 was discovered |
| mispositioned. Damper D-21 controls the amount of recirculation flow in the |
| Control Room Ventilation System (CRVS), when the system is in the emergency |
| (recirculation) mode. |
| |
| "The CRVS is designed such that when it shifts to recirculation mode, the |
| Train B emergency supply fan starts. It draws in a nominal 250 cfm of |
| outside intake air flow, and a nominal 750 cfm of recirculation air flow, |
| for a total of 1000 cfm of flow through the HEPA and charcoal filters. If |
| the Train B fan does not start, the resulting low recirculation flow (less |
| than or equal to 100 cfm) will cause the Train A fan to start. |
| |
| "During the surveillance it was found that, with the damper open too far, |
| the recirculation flow stayed so high (about 250 cfm), that even with no |
| supply fan running, the Train A fan did not receive a low flow start signal. |
| The recirculation flow came from the three running Air Handling Units. As a |
| result, a single failure of the Train B emergency supply fan could have |
| caused a loss of emergency supply air forced flow. |
| |
| "As a result of no forced flow, the outside intake air flow would be |
| reduced, and the recirculation flow from the Air Handling Units would stay |
| at about 250 cfm, as measured. By itself, this situation does not |
| significantly degrade plant safety. If there were no outside air drawn in, |
| the dose to the Control Room operators would be minimal. However, with no |
| filtered outside intake air, Turkey Point cannot assure that the Control |
| Room envelope would be pressurized, the unfiltered inleakage of outside air |
| may be sufficient to increase the dose to operators." |
| |
| The NRC resident inspector has been informed of this notification by the |
| licensee. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 38134 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CALVERT CLIFFS REGION: 1 |NOTIFICATION DATE: 07/12/2001|
| UNIT: [1] [2] [] STATE: MD |NOTIFICATION TIME: 16:17[EDT]|
| RXTYPE: [1] CE,[2] CE |EVENT DATE: 07/12/2001|
+------------------------------------------------+EVENT TIME: 16:17[EDT]|
| NRC NOTIFIED BY: DROWN |LAST UPDATE DATE: 07/12/2001|
| HQ OPS OFFICER: BOB STRANSKY +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: NON EMERGENCY |ANTHONY DIMITRIADIS R1 |
|10 CFR SECTION: | |
|APRE 50.72(b)(2)(xi) OFFSITE NOTIFICATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
|2 N Y 100 Power Operation |100 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION |
| |
| The licensee will be notifying the Maryland Department of the Environment |
| (MDE) regarding positive test results for coliform bacteria in drinking |
| water samples taken from the educational center. The NRC resident inspector |
| has been informed of this notification. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|General Information or Other |Event Number: 38135 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: OR DEPT OF HEALTH RAD PROTECTION |NOTIFICATION DATE: 07/12/2001|
|LICENSEE: KLB CONSTRUCTION |NOTIFICATION TIME: 17:58[EDT]|
| CITY: ISSAQUAH REGION: 4 |EVENT DATE: 07/12/2001|
| COUNTY: STATE: WA |EVENT TIME: [PDT]|
|LICENSE#: ORE-90865 AGREEMENT: Y |LAST UPDATE DATE: 07/12/2001|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |CHUCK CAIN R4 |
| |JOSEPHINE PICCONE NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: KEVIN SEIBERT | |
| HQ OPS OFFICER: BOB STRANSKY | |
+------------------------------------------------+ |
|EMERGENCY CLASS: NON EMERGENCY | |
|10 CFR SECTION: | |
|NAGR AGREEMENT STATE | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT |
| |
| A Troxler Model 3430 gauge (S/N 28872) was stolen from a storage building in |
| Issaquah, WA. The gauge had been transported to a work site in WA and placed |
| into a locked storage building. The local police department has been |
| notified (Case #01-05791). The licensee is offering a reward for the return |
| of the gauge. |
| |
| [See related report 38136] |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|General Information or Other |Event Number: 38136 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: WA DIVISION OF RADIATION PROTECTION |NOTIFICATION DATE: 07/12/2001|
|LICENSEE: KLB CONSTRUCTION |NOTIFICATION TIME: 18:33[EDT]|
| CITY: ISSAQUAH REGION: 4 |EVENT DATE: 07/12/2001|
| COUNTY: STATE: WA |EVENT TIME: [PDT]|
|LICENSE#: ORE-90865 AGREEMENT: Y |LAST UPDATE DATE: 07/12/2001|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |CHUCK CAIN R4 |
| |JOSEPHINE PICCONE NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: TERRY FRAZEE (EMAIL) | |
| HQ OPS OFFICER: BOB STRANSKY | |
+------------------------------------------------+ |
|EMERGENCY CLASS: NON EMERGENCY | |
|10 CFR SECTION: | |
|NAGR AGREEMENT STATE | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT |
| |
| "The Oregon licensee reported that a Troxler model 3430 portable gauge, |
| serial number 28872, containing 10 mCi of cesium-137 and 50 mCi of |
| americium-241 was stolen from a locked cargotainer at a work site in |
| Washington state. The Oregon Licensee had transported the portable gauge to |
| the work site of a Washington licensee in order to complete a sales |
| transaction. The licensee's employee arrived at approximately 5:30 PM on |
| July 11. Since no one from the Washington licensee was available on site to |
| take possession of the gauge, the licensee's employee locked it in a work |
| site cargotainer. The yellow transport box was reported to be locked. When |
| the licensee's employee came back around 7:00 AM on July 12, the locks had |
| been broken and the gauge and several tools had been stolen. The theft was |
| reported to the City of Issaquah Police. The Washington Radiation control |
| Program has been in contact with the Oregon Radiation control Program to |
| coordinate follow-up." |
| |
| [See related report 38135] |
+------------------------------------------------------------------------------+
Page Last Reviewed/Updated Thursday, March 25, 2021
Page Last Reviewed/Updated Thursday, March 25, 2021