Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for July 6, 2001

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           07/05/2001 - 07/06/2001

                              ** EVENT NUMBERS **

38115  38116  38117  38118  38119  

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   38115       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  U. S. CUSTOMS SERVICE                |NOTIFICATION DATE: 07/05/2001|
|LICENSEE:  UNKNOWN                              |NOTIFICATION TIME: 08:50[EDT]|
|    CITY:  MIAMI                    REGION:  2  |EVENT DATE:        07/03/2001|
|  COUNTY:  DADE                      STATE:  FL |EVENT TIME:        12:30[EDT]|
|LICENSE#:                        AGREEMENT:  Y  |LAST UPDATE DATE:  07/05/2001|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |EDWARD MCALPINE      R2      |
|                                                |FRED BROWN           NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  CHRIS WHITENTON              |                             |
|  HQ OPS OFFICER:  STEVE SANDIN                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NINF                     INFORMATION ONLY       |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| UNMARKED LICENSED RAD MATERIAL RECEIVED AT PORT OF ENTRY                     |
|                                                                              |
| A closed intermodal container shipped by Alcan of Kingston, Jamaica to CPN   |
| International in California was off loaded and inspected at the Port of      |
| Entry in Miami, FL.  U.S. Customs alerted local Hazmat personnel after       |
| receiving alarms on personnel monitors.  Hazmat surveyed both the exterior   |
| and interior of the container and found readings of approximately 1 mr/hr    |
| and 8 mr/hr, respectively.   A followup investigation determined that the    |
| container had unmarked density detectors used in mining operations. The      |
| shipment has been quarantined and will be returned to the shipper.  The      |
| National Response Center was informed of this incident by U.S. Customs on    |
| 7/3/01 (report #571693).                                                     |
|                                                                              |
| Contact the Headquarters Operations Officer for contact telephone number.    |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38116       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: DRESDEN                  REGION:  3  |NOTIFICATION DATE: 07/05/2001|
|    UNIT:  [] [] [3]                 STATE:  IL |NOTIFICATION TIME: 12:15[EDT]|
|   RXTYPE: [1] GE-1,[2] GE-3,[3] GE-3           |EVENT DATE:        07/05/2001|
+------------------------------------------------+EVENT TIME:        10:19[CDT]|
| NRC NOTIFIED BY:  BORING                       |LAST UPDATE DATE:  07/05/2001|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          ALERT                 |ROGER LANKSBURY      R3      |
|10 CFR SECTION:                                 |TAD MARSH            EO      |
|AAEC 50.72(a) (1) (i)    EMERGENCY DECLARED     |CALDWELL             FEMA    |
|ARPS 50.72(b)(2)(iv)(B)  RPS ACTUATION - CRITICA|                             |
|AESF 50.72(b)(3)(iv)(A)  VALID SPECIF SYS ACTUAT|                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|                                                   |                          |
|3     M/R        Y       100      Power Operation  |0        Hot Shutdown     |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| THE REACTOR WAS MANUALLY SCRAMMED FROM 100% POWER DUE TO HIGH DRYWELL        |
| PRESSURE                                                                     |
|                                                                              |
| The plant entered an Alert @ 1019CDT due to drywell pressure rising above    |
| the ECCS setpoint(2 psig).  The reactor was manually scrammed at 1006 and    |
| drywell pressure peaked at 2.3 psig.  All rods fully inserted and no safety  |
| relief valves lifted.  ECCS functioned as required, but no injection         |
| initiated.  Drywell pressure is currently 2.1 psig and slowly trending       |
| down.                                                                        |
|                                                                              |
| The NRC Resident Inspector was notified along with state ,local and other    |
| Government agencies. Other agencies notified by NRC:  Tanner(EPA),           |
| Young(DOE), Conley( USDA), Gray(HHS), Robertson(DOT), and Watson(USSS).      |
|                                                                              |
| NRC entered the monitoring mode at 1209 EDT.                                 |
|                                                                              |
| * * * UPDATE @ 1300EDT COMMISSIONERS ASSISTANT'S BRIEFING * * *              |
|                                                                              |
| Wessman(IRO), Borchardt(NRR), Gagner(PAO), Combs(SP), Hauber(IP),            |
| Madden(CO), Bergman(EDO), Paperiello(DEDMRS), Tschiltz(Chairman Assist.),    |
| Hiltz(Commissioner Dicus), Beall(Commissioner McGaffigan) Thoma(Commissioner |
| Merrifield), Dyer(Reg 3 Briefer), and Gamberoni(Secy)                        |
|                                                                              |
| Monitoring mode was terminated at 1737 EDT.                                  |
|                                                                              |
| * * * UPDATE AT 1757 ON 7/05/01 BY MOHR TO GOULD * * *                       |
|                                                                              |
| Subsequent to earlier notification, information has been obtained that       |
| verifies the cause of the high drywell pressure was due to a loss of         |
| containment cooling.  A redundant cooling water train was placed in service  |
| and the drywell temperature and pressure have been trending down to normal   |
| ranges.  The drywell sump was pumped and confirmed that RCS leak rates have  |
| not increased.  Drywell radiation levels were verified to be normal.         |
| Additionally, drywell atmosphere samples were normal.  Drywell pressure is   |
| currently .37 PSIG.  The plant has been stabilized in accordance with        |
| procedures and equipment repairs are being made.  Plans are being developed  |
| for unit return to service.                                                  |
|                                                                              |
| The Alert was terminated at 1602 CDT.                                        |
|                                                                              |
| The NRC Resident Inspector and State have been informed.                     |
|                                                                              |
| * * * UPDATE AT 1825 ON 7/5/01 BY MOHR  TO GOULD * * *                       |
|                                                                              |
| The plant also had groups 2 and 3 isolations, low pressure and high pressure |
| ECCS initiation signals and Unit 3 and 2/3 swing emergency diesel generator  |
| auto starts.                                                                 |
|                                                                              |
| The NRC Resident Inspector was informed.                                     |
|                                                                              |
| * * *  UPDATE 1900 ON 7/05/91 MODIFIED COMMISSIONER ASSISTANT'S BRIEFING * * |
| *                                                                            |
|                                                                              |
| Dyer(REG3), Marsh(NRR), Tschiltz(Chairman's Assistants), Thoma(Commissioner  |
| Merrifield's Assistant), and Hiltz(Commissioner Dicus' Assistant)            |
|                                                                              |
| Agencies notified by the NRC:  Cegielski(FEMA), Poppell(EPA), Morrone(DOE),  |
| Conley(USDA), Robertson(DOT), Farrow-Collier(CDC).  Notified Beckner(EO),    |
| Wessman(IRO), Hayden(PA) and Vegel(REG 3 RDO).                               |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38117       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CALVERT CLIFFS           REGION:  1  |NOTIFICATION DATE: 07/05/2001|
|    UNIT:  [1] [2] []                STATE:  MD |NOTIFICATION TIME: 12:30[EDT]|
|   RXTYPE: [1] CE,[2] CE                        |EVENT DATE:        07/05/2001|
+------------------------------------------------+EVENT TIME:        09:00[EDT]|
| NRC NOTIFIED BY:  ROBERT MARTIN                |LAST UPDATE DATE:  07/05/2001|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |LAWRENCE DOERFLEIN   R1      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION TO MARYLAND DEPARTMENT OF ENVIRONMENT                   |
|                                                                              |
| The licensee notified the Maryland Department of Environment due to a        |
| positive coliform count in the drinking water at the educational center.     |
| The licensee notified the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   38118       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  TEXAS DEPARTMENT OF HEALTH           |NOTIFICATION DATE: 07/05/2001|
|LICENSEE:  ALPHA TESTING INC                    |NOTIFICATION TIME: 14:50[EDT]|
|    CITY:  DALLAS                   REGION:  4  |EVENT DATE:        06/25/2001|
|  COUNTY:                            STATE:  TX |EVENT TIME:        06:20[CDT]|
|LICENSE#:  L03411-000            AGREEMENT:  Y  |LAST UPDATE DATE:  07/05/2001|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |LINDA HOWELL         R4      |
|                                                |DON COOL             NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  OGDEN (by fax)               |                             |
|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          NON EMERGENCY         |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| STOLEN HUMBOLDT HS-5001P NUCLEAR DENSITY GAUGE                               |
|                                                                              |
| A Humboldt Manufacturing Model HS-5001 P, Serial No. 30, containing 10       |
| millicurie Cs-137, Serial No. 400SGF; and 40 millicurie Am-241/Be, Serial    |
| No. NJ00026 was stolen.  Initial information indicates that the gauge was in |
| the bed of a company pickup truck secured by bungee cords in the gauge's     |
| locked transit case when the driver stopped at a convenience store, located  |
| at 104 Kaufman Street, Rockwall, Texas. at approximately 6:15 a.m. on June   |
| 25, 2001.  The operator/driver noticed the gauge was missing when he         |
| returned to his truck which was parked immediately in front of the store's   |
| front doors.   He has estimated that he was in the store for approximately 5 |
| minutes.   A police report has been filed with the Rockwall, Texas Police    |
| Department.   A copy of this report is currently not available. The gauge    |
| was enroute to a jobsite when stolen.  The owner of the stolen gauge is a    |
| Texas Licensee, L03411-000 (Alpha Testing, Inc.. 2209 Wisconsin Street,      |
| Suite 100 Dallas, Texas 75229).                                              |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   38119       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: FERMI                    REGION:  3  |NOTIFICATION DATE: 07/05/2001|
|    UNIT:  [2] [] []                 STATE:  MI |NOTIFICATION TIME: 16:03[EDT]|
|   RXTYPE: [2] GE-4                             |EVENT DATE:        07/05/2001|
+------------------------------------------------+EVENT TIME:        10:00[EDT]|
| NRC NOTIFIED BY:  COSEI                        |LAST UPDATE DATE:  07/05/2001|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          NON EMERGENCY         |ROGER LANKSBURY      R3      |
|10 CFR SECTION:                                 |                             |
|AINA 50.72(b)(3)(v)(A)   POT UNABLE TO SAFE SD  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| NON-CONSERVATIVE ANALYSIS FOR OPRM SCRAM SETPOINTS                           |
|                                                                              |
| On July 5, 2001, Detroit Edison received confirmation from General Electric  |
| of a non-conservative analysis that supports Operation Power Range Monitor   |
| (OPRM) scram setpoints.  The non-conservative analysis is generic and been   |
| determined to affect Fermi 2.   The OPRM had been conservatively declared    |
| inoperable on June 27, 2001, at 1333 hours as a result of preliminary        |
| notification by General Electric.                                            |
|                                                                              |
| The consequences of the non-conservative analysis are that the associated    |
| OPRM Reactor Protective System (RPS) scram setpoints are non-conservative.   |
| The non-conservative RPS setpoints may result in violating the Minimum       |
| Critical Power Ratio (MCPR) safety limit during a thermal-hydraulic          |
| instability.                                                                 |
|                                                                              |
| All OPRM channels have been declared inoperable. Technical Specification     |
| 3.3.1.1 Action J requires an alternate method of detecting and suppressing   |
| thermal-hydraulic instabilities to be implemented within 12 hours.           |
| Alternate methods have been established, thus, the Technical Specification   |
| required action is satisfied.   Fermi 2 has 120 days to restore the OPRMs to |
| an operable condition.                                                       |
|                                                                              |
| This initial report is being made in accordance with 10CFR50.72 (B)(3)(V)(A) |
| as a condition that could have prevented the fulfillment of the safety       |
| function of a system needed to shutdown the reactor.                         |
|                                                                              |
| See EN #38104, GE Nuclear Energy 10CFR21 report.                             |
|                                                                              |
| The NRC Resident Inspector will be notified.                                 |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Thursday, March 25, 2021