The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.
Event Notification Report for March 6, 2001
U.S. Nuclear Regulatory Commission
Operations Center
Event Reports For
03/05/2001 - 03/06/2001
** EVENT NUMBERS **
37806 37807 37808 37809 37810
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37806 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: HATCH REGION: 2 |NOTIFICATION DATE: 03/05/2001|
| UNIT: [] [2] [] STATE: GA |NOTIFICATION TIME: 12:25[EST]|
| RXTYPE: [1] GE-4,[2] GE-4 |EVENT DATE: 03/05/2001|
+------------------------------------------------+EVENT TIME: 10:13[EST]|
| NRC NOTIFIED BY: BRUCE BUTLER |LAST UPDATE DATE: 03/05/2001|
| HQ OPS OFFICER: JOHN MacKINNON +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |STEPHEN CAHILL R2 |
|10 CFR SECTION: | |
|*INB 50.72(b)(3)(v)(B) POT RHR INOP | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
| | |
|2 N Y 100 Power Operation |100 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| REACTOR CORE ISOLATION COOLING (RCIC) TRIPPED UNEXPECTEDLY DURING TESTING. |
| |
| Received RCIC "B" logic isolation signal causing RCIC in-board isolation |
| valve, 2E51-F007, to close resulting in RCIC trip signal. I&C personnel |
| were performing 57SV-CAL-003-25 ATTS transmitter calibration for RCIC "B" |
| steam line differential pressure transmitter 2E51-N057B when the isolation |
| occurred and this instrument caused the isolation. Investigation is in |
| progress to determine the cause. Received isolation signal at 1013 ET, I&C |
| backed out of the procedure returning 2E51-N057B transmitter to service and |
| RCIC isolation was reset and RCIC returned to standby at 1105 ET. |
| |
| All other Emergency Core Cooling systems were fully operable during the time |
| period RCIC was declared inoperable. |
| |
| The NRC Resident Inspector was notified of this event by the licensee. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Hospital |Event Number: 37807 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: SAINT LUKES HOSPITAL |NOTIFICATION DATE: 03/05/2001|
|LICENSEE: SAINT LUKES HOSPITAL |NOTIFICATION TIME: 15:13[EST]|
| CITY: KANSAS CITY REGION: 3 |EVENT DATE: 02/23/2001|
| COUNTY: STATE: MO |EVENT TIME: 11:15[CST]|
|LICENSE#: 24-00889-01 AGREEMENT: N |LAST UPDATE DATE: 03/05/2001|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |JOHN MADERA R3 |
| |BRIAN SMITH NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: SCOTT SORENSEN | |
| HQ OPS OFFICER: JOHN MacKINNON | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|LADM 35.33(a) MED MISADMINISTRATION | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| POSSIBLE MEDICAL MISADMINISTRATION |
| |
| A remote afterloader device failed to function as it was intended during a |
| random FDA trial. The remote afterloader was in automatic, and it was |
| supposed to insert an intervascular, brachytherapy, 93-mCi, P-32, wire |
| source into a patient. The remote afterloader device did not operate |
| properly, and it inserted and withdrew the wire source 4 times. No dwell |
| time was recorded by the afterloader since the wire source inserted less |
| than 5 seconds each time before the wire source was automatically withdrawn. |
| The patient was supposed to have received a total dose of 20 grays. The |
| patient received a dose much less than intended. The FDA was notified of |
| this event by the licensee. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|General Information or Other |Event Number: 37808 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: TEXAS DEPARTMENT OF HEALTH |NOTIFICATION DATE: 03/05/2001|
|LICENSEE: NON-DESTRUCTIVE INSPECTION, CORP. |NOTIFICATION TIME: 17:45[EST]|
| CITY: CLUTE REGION: 4 |EVENT DATE: 02/27/2001|
| COUNTY: BRAZORIA STATE: TX |EVENT TIME: 00:00[CST]|
|LICENSE#: L02712 AGREEMENT: Y |LAST UPDATE DATE: 03/05/2001|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |WILLIAM JOHNSON R4 |
| |JOSEPH HOLONICH NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: HELEN WATKINS | |
| HQ OPS OFFICER: JOHN MacKINNON | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|NAGR AGREEMENT STATE | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| FOUR RADIOGRAPHERS EXCEEDED ANNUAL EXPOSURE LIMIT. |
| |
| |
| After receiving a Radiation Dosimeter Report on 01/22/01 for wear date of |
| 11/20/00 through 12/19/00, it was discovered the licensee had 4 individual |
| personnel dosimeters exceeding the annual limits of 5 rem/yr. Participants |
| ID and reported doses are listed below: |
| |
| 1. Participant 00089 ID # 466313013, 5553 mrem. |
| 2. Participant 00190 ID # 452717589, 5661 mrem. |
| 3. Participant 00174 ID # 453959946, 4673 mrem plus as assessment of 417 |
| mrem for a lost dosimeter equal a sum of 5091 mrem. |
| 4. Participant 00255 ID # 222582111, 3995 mrem, plus previous employment |
| assessment of 1065 mrem equal a sum of 5060 mrem. |
| |
| After receiving and reviewing the dosimetry reports phone notification was |
| made confirming the resulting exposures exceeding annual limits in |
| accordance with 25 TAC requirements. At this time the licensee is awaiting |
| the final dosimetry reports for 2000 year to date. Upon receipt of the |
| final dosimetry reports the licensee will set up an investigation date and |
| time. |
| |
| Texas Department of Health is investigating to obtain additional |
| information. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37809 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: NINE MILE POINT REGION: 1 |NOTIFICATION DATE: 03/05/2001|
| UNIT: [1] [] [] STATE: NY |NOTIFICATION TIME: 17:56[EST]|
| RXTYPE: [1] GE-2,[2] GE-5 |EVENT DATE: 03/05/2001|
+------------------------------------------------+EVENT TIME: 16:00[EST]|
| NRC NOTIFIED BY: K BELDEN |LAST UPDATE DATE: 03/05/2001|
| HQ OPS OFFICER: JOHN MacKINNON +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |RICHARD CONTE R1 |
|10 CFR SECTION: | |
|*IND 50.72(b)(3)(v)(D) ACCIDENT MITIGATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| CONTROL ROOM EMERGENCY VENTILATION DECLARED INOPERABLE. |
| |
| Control Room Emergency Ventilation was declared inoperable at 1600 hours. |
| This was a result of the Lab carbon sample analysis not meeting Technical |
| Specification 3.4.5.c of greater than 90% radioactive methyl iodine |
| removal capability when tested. This required entering into a 7 day |
| shutdown Limiting Condition for Operation. Carbon sample analysis is |
| required per Technical Specification to be performed once per cycle (2 |
| years). Licensee is in the process of replacing the carbon. |
| |
| The NRC Resident Inspector was notified of this event. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37810 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SEABROOK REGION: 1 |NOTIFICATION DATE: 03/06/2001|
| UNIT: [1] [] [] STATE: NH |NOTIFICATION TIME: 00:24[EST]|
| RXTYPE: [1] W-4-LP |EVENT DATE: 03/05/2001|
+------------------------------------------------+EVENT TIME: 23:24[EST]|
| NRC NOTIFIED BY: JIM CROWLEY |LAST UPDATE DATE: 03/06/2001|
| HQ OPS OFFICER: LEIGH TROCINE +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: UNU |RICHARD CONTE R1 |
|10 CFR SECTION: |BILL BATEMAN NRR |
|*AEC 50.72(a) (1) (i) EMERGENCY DECLARED |CHARLES MILLER IRO |
|*RPS 50.72(b)(2)(iv)(B) RPS ACTUATION - CRITICA|CHARLIE BAGWELL FEMA |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 A/R Y 100 Power Operation |0 Hot Standby |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| DISCRETIONARY UNUSUAL EVENT DECLARED DUE TO A MOMENTARY LOSS OF OFFSITE |
| POWER DURING AN ONGOING SEVERE WINTER STORM AND SUBSEQUENT AUTOMATIC REACTOR |
| TRIP DUE TO GRID INSTABILITY |
| |
| During an ongoing severe winter storm, the 345-kV breakers tripped open and |
| re-closed resulting in a momentary loss of offsite power. An automatic |
| reactor trip also occurred at 2324 on 03/05/01 due to electrical grid |
| instability. (The exact cause of the reactor trip is currently under |
| investigation because there was no first out indication.) All rods fully |
| inserted. The reactor coolant pumps tripped as expected, and one has been |
| placed back in service. Both emergency diesel generators automatically |
| started but did not load. Availability of the condenser was also lost due |
| to the loss of power, and operators closed the main steam isolation valves. |
| There were no radiation releases, and there were no reactor coolant system |
| or steam generator tube leaks. All systems functioned as required with one |
| exception. The steam-driven emergency feedwater pump failed to |
| automatically actuate. |
| |
| At this time, the unit is in Mode 3. Normal charging and letdown, |
| pressurizer heaters and sprays, and one reactor coolant pump are being |
| utilized for primary system level, pressure, and transport control. Water |
| is being supplied to the steam generators via an electric-driven emergency |
| feedwater pump, and the atmospheric dumps are being utilized as the heat |
| sink. Containment parameters are normal. The grid is currently available |
| for offsite power, and the emergency diesel generators are still running. |
| |
| Based on a discretionary shift management call, the licensee declared an |
| Unusual Event at 2336 on 03/05/01. The licensee stated that a |
| "Discretionary Event" under item 18A refers to an event in progress (or has |
| occurred) that indicates a potential degradation of the level of safety of |
| the station. The licensee plans to notify the NRC when the Unusual Event |
| has terminated or if conditions degrade. |
| |
| A severe winter storm is currently ongoing. At the time of the event, the |
| unit was experiencing winds at a rate of approximately 50 miles per hour. |
| The licensee reported that these strong winds were ongoing and that only a |
| few inches of snow had fallen (although up to 2 feet is expected). |
| |
| The licensee notified the state at 2347 on 03/05/01 and plans to notify the |
| NRC resident inspector as well as applicable local officials. The licensee |
| also plans to issue a press release. |
| |
| ***** UPDATE AT 0222 ON 03/06/01 FROM JIM HILL TO LEIGH TROCINE ***** |
| |
| This update provides both clarifications/corrections to the original event |
| notification and additional information regarding licensee plans. |
| |
| CLARIFICATIONS/CORRECTIONS: Prior to the event, two of three offsite power |
| lines had been lost in close succession. The remaining offsite line was |
| subsequently lost, and its breaker re-closed within a short duration. This |
| resulted in the momentary loss of offsite power and subsequent plant |
| transient. This initial electrical imbalance was sufficient to result in |
| the automatic starting and loading of both emergency diesel generators. |
| |
| CURRENT STATUS: The unit remains in the Unusual Event, and winds are |
| currently sustained at a rate of approximately 40 miles per hour. All three |
| offsite power lines have been restored. Both emergency diesel generators |
| remain in operation and continue to provide power to both vital (emergency) |
| buses. The non-vital buses have been re-energized from offsite power. An |
| additional auxiliary pump (the startup feedwater pump) has also been started |
| to provide additional water to the steam generators. This pump is a |
| non-safety related housekeeping pump. |
| |
| PLANS: Within the next half hour, the licensee plans to commence a |
| discretionary plant cooldown and plans to place the unit in Mode 5 (Cold |
| Shutdown). At some point in time, the licensee also plans to secure the |
| electric-driven emergency feedwater pump and rely on the startup feedwater |
| pump to supply water to the steam generators. |
| |
| The licensee notified the NRC resident inspector and an onsite member of an |
| NRC residual heat removal inspection team. The NRC operations officer |
| notified the R1DO (Conte), NRR EO (Bateman), and IRO (Miller). |
| |
| ***** UPDATE AT 0438 ON 03/06/01 FROM JIM HILL TO LEIGH TROCINE ***** |
| |
| The licensee has commenced a plant cooldown and anticipates that it will |
| take approximately 6 hours for the unit to reach Cold Shutdown. Other than |
| commencement of the cooldown, there has been no change in plant conditions |
| or equipment status. |
| |
| The licensee stated that the criteria for exiting the Unusual Event have |
| been met. However, the licensee currently plans to remain in the Unusual |
| Event for a while longer because the high line insulators onsite are still |
| arcing and are suspect and because the in-house vital buses are still being |
| powered by the emergency diesel generators. |
| |
| The licensee notified an onsite member of an NRC residual heat removal |
| inspection team, who in turn notified the NRC resident inspector. The NRC |
| operations officer notified the R1DO (Conte), NRR EO (Bateman), and IRO |
| (Miller). |
+------------------------------------------------------------------------------+
Page Last Reviewed/Updated Thursday, March 25, 2021
Page Last Reviewed/Updated Thursday, March 25, 2021