Skip to main content

The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.

Event Notification Report for February 28, 2001

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           02/27/2001 - 02/28/2001

                              ** EVENT NUMBERS **

37784  

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37784       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SALEM                    REGION:  1  |NOTIFICATION DATE: 02/27/2001|
|    UNIT:  [] [2] []                 STATE:  NJ |NOTIFICATION TIME: 23:38[EST]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        02/27/2001|
+------------------------------------------------+EVENT TIME:        19:15[EST]|
| NRC NOTIFIED BY:  3                            |LAST UPDATE DATE:  02/27/2001|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |RICHARD CONTE        R1      |
|10 CFR SECTION:                                 |                             |
|NONR                     OTHER UNSPEC REQMNT    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 24 HOUR REPORT REQUIRED BY PLANT OPERATING LICENSE                           |
|                                                                              |
| "This notification is being made to report a violation of the Salem Unit 2   |
| Operating Licensee Section 2.C.10, 'Fire Protection.'   Approximately 95% of |
| the installed emergency lights on Unit 2 have been rendered inoperable as a  |
| result of discharge testing.  Per the Fire Protection Program, these lights  |
| being inoperable would require that suitable hand held lighting be available |
| to operators required to perform Appendix 'R' shutdown activities.  These    |
| lights were checked and of the 16 lights(8 per Unit) 8 did not pass the      |
| required 3 minute test(at 1915).  This constituted a violation of the fire   |
| protection program requirements and could have reduced operators ability to  |
| respond to a shut-down from outside the control room.   The 8 inoperable     |
| hand held lights have been replaced with operable hand held lights, bring    |
| the unit into compliance with the Fire Protection Program at 2020 on         |
| 2/27/01."                                                                    |
|                                                                              |
| The NRC Resident Inspector was notified.                                     |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Thursday, March 25, 2021

Page Last Reviewed/Updated Thursday, March 25, 2021