Skip to main content

The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.

Event Notification Report for February 23, 2001

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           02/22/2001 - 02/23/2001

                              ** EVENT NUMBERS **

37771  37772  

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37771       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CALLAWAY                 REGION:  4  |NOTIFICATION DATE: 02/22/2001|
|    UNIT:  [1] [] []                 STATE:  MO |NOTIFICATION TIME: 16:28[EST]|
|   RXTYPE: [1] W-4-LP                           |EVENT DATE:        02/21/2001|
+------------------------------------------------+EVENT TIME:        18:45[CST]|
| NRC NOTIFIED BY:  HENSON                       |LAST UPDATE DATE:  02/22/2001|
|  HQ OPS OFFICER:  JOHN MacKINNON               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |LINDA SMITH          R4      |
|10 CFR SECTION:                                 |                             |
|*PRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION MADE TO MISSOURI PUBLIC SERVICE COMMISSION              |
|                                                                              |
| An onsite apprentice welder injured his left hand.  Onsite Medical Emergency |
| Team evaluated the injury and had the individual transported offsite to the  |
| local hospital.  The Missouri Public Service Commission was notified of this |
| incident by the licensee.                                                    |
|                                                                              |
| The NRC Resident Inspector was notified of this event by the licensee.       |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37772       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: MONTICELLO               REGION:  3  |NOTIFICATION DATE: 02/22/2001|
|    UNIT:  [1] [] []                 STATE:  MN |NOTIFICATION TIME: 21:34[EST]|
|   RXTYPE: [1] GE-3                             |EVENT DATE:        02/22/2001|
+------------------------------------------------+EVENT TIME:        18:30[CST]|
| NRC NOTIFIED BY:  B. WELLER                    |LAST UPDATE DATE:  02/22/2001|
|  HQ OPS OFFICER:  JOHN MacKINNON               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |MARK RING            R3      |
|10 CFR SECTION:                                 |                             |
|*INB 50.72(b)(3)(v)(B)   POT RHR INOP           |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| "EVEN" TRAIN CORE SPRAY, RHR OR RHRSW PUMPS OPERATION FROM THE ALTERNATE     |
| SHUTDOWN SYSTEM COULD BE LOST DUE TO A POSTULATED HOT SHORT.                 |
|                                                                              |
| An Alternate Shutdown System design deficiency resulting in a vulnerability  |
| to a single hot short during a Control Room Cable Spreading Room fire has    |
| been identified.  The effect of the postulated hot short would be to actuate |
| the Bus 16 load shed logic  while the bus is powered from the emergency      |
| diesel generator.  This could result in the inability to operate the even    |
| train Core Spray, Residual Heat Removal (RHR)  or RHR Service Water  pumps.  |
| No means are in place to circumvent the postulated hot short.  A one hour    |
| fire watch patrol in the cable spreading room and control room has been      |
| established with Alternate Shutdown System inoperable.  All other Emergency  |
| Core Cooling Systems are fully operable.                                     |
|                                                                              |
| The NRC Resident Inspector will be notified of this event by the licensee.   |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Thursday, March 25, 2021