Skip to main content

Alert

Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for October 31, 2000

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           10/30/2000 - 10/31/2000

                              ** EVENT NUMBERS **

37085  37394  37472  37473  37474  37475  

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   37085       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  FLORIDA BUREAU OF RADIATION CONTROL  |NOTIFICATION DATE: 06/15/2000|
|LICENSEE:  PROFESSIONAL SERVICE INDUSTRIES INC  |NOTIFICATION TIME: 10:25[EDT]|
|    CITY:  TAMPA                    REGION:  2  |EVENT DATE:        06/14/2000|
|  COUNTY:                            STATE:  FL |EVENT TIME:        09:00[EDT]|
|LICENSE#:  22-12                 AGREEMENT:  Y  |LAST UPDATE DATE:  10/30/2000|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |RUDOLPH BERNHARD     R2      |
|                                                |                             |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  CHARLES ADAMS (FACSIMILE)    |                             |
|  HQ OPS OFFICER:  BOB STRANSKY                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT                                                       |
|                                                                              |
| The State of Florida Bureau of Radiation Control reported that a Troxler     |
| soil moisture/density gauge (Model 3430, Serial #30059), containing 8 mCi of |
| Cs-137 and 40 mCi of Am-241/Be, had been stolen from a state licensee. The   |
| licensee reported that the gauge was stolen from a temporary job site        |
| between the hours of 6 p.m. on 6/13/00 and 9 a.m. on 6/14/00. The chain link |
| fence surrounding the site was not damaged, but the door to the shed had     |
| been pried open. The lock on the storage locker containing the container and |
| gauge had been cut. The gauge and container were the only items taken. The   |
| Hillsborough Sheriff's Office and the Florida Bureau of Radiation Control    |
| are investigating. The Sheriff's Office is planning to issue a press         |
| release.                                                                     |
|                                                                              |
| * * * UPDATE 1544 EST 10/30/2000 FROM ADAMS TAKEN BY STRANSKY * * *          |
|                                                                              |
| "Licensee reported that a gauge was stolen on June 14th. The gauge was found |
| on October 30 at Veterans Memorial Park in Tampa. Item was found along a     |
| bike path. The gauge was slightly damaged, but the sources were intact       |
| locked in the gauge. Swipes showed no contamination. Item has been returned  |
| to owner."                                                                   |
|                                                                              |
| Notified R2DO (Boland).                                                      |
+------------------------------------------------------------------------------+

!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37394       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: RIVER BEND               REGION:  4  |NOTIFICATION DATE: 10/01/2000|
|    UNIT:  [1] [] []                 STATE:  LA |NOTIFICATION TIME: 03:56[EDT]|
|   RXTYPE: [1] GE-6                             |EVENT DATE:        09/30/2000|
+------------------------------------------------+EVENT TIME:        23:33[CDT]|
| NRC NOTIFIED BY:  HUSTON                       |LAST UPDATE DATE:  10/30/2000|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |CHUCK CAIN           R4      |
|10 CFR SECTION:                                 |                             |
|AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION    |                             |
|NLCO                     TECH SPEC LCO A/S      |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| PLANT ENTERED LCO ACTION STATEMENT WHEN BOTH PRIMARY CONTAINMENT UNIT        |
| COOLERS WHERE DECLARED INOPERABLE.                                           |
|                                                                              |
| On 09/30/00 at 2333, both Primary Containment Unit Coolers were declared     |
| inoperable based on an apparent failure to fully meet required volumetric    |
| flow rates.  The Tech Spec SR 3.6.1.7.2 required values are greater than or  |
| equal to 50,000 CFM.   Actual calculated values were determined to be        |
| approximately 45,000 CFM for Unit cooler A and 48,000 CFM for Unit cooler B. |
| This condition may impact the ability of these unit coolers to perform their |
| design safety functions.  This report is being made pursuant to 10 CFR 50.72 |
| b.2.iii.D for loss of function required to mitigate an accident.             |
| Activities to restore function include evaluation of test data and           |
| methodology, cleaning of unit cooler coils, verification of calibration      |
| data, and verification of system alignment.                                  |
| The plant is in a 8 hour LCO to restore one of the coolers to operable       |
| status or be in mode 3 within the following 12 hours.                        |
|                                                                              |
| The NRC Resident Inspector was notified.                                     |
|                                                                              |
| * * * UPDATE ON 10/1/00 AT 2320 BY HUSTON, RECEIVED BY WEAVER * * *          |
|                                                                              |
| Both Primary Containment Unit Coolers A and B (Divisions I and II) have been |
| re-tested satisfactorily verifying both safety function and Tech Spec        |
| operability. The station declared both Containment Unit Cooler A and B       |
| operable and exited the LCO regarding Primary Containment Unit Coolers at    |
| 1048 hours on 10/1/00                                                        |
|                                                                              |
| The station is evaluating information developed to determine whether a       |
| retraction is warranted.                                                     |
|                                                                              |
| The licensee will notify the NRC resident inspector.  The Operations Center  |
| notified the R4DO (Cain).                                                    |
|                                                                              |
| * * * RETRACTION 2005 EST 10/30/2000 FROM CHASE TAKEN BY STRANSKY * * *      |
|                                                                              |
| "On September 30, 2000 at 2333, both primary containment unit coolers A and  |
| B were declared inoperable based on an apparent failure to meet required     |
| volumetric flow rates (50,000 CFM) as stated in Technical Specification      |
| Surveillance Requirement (SR) 3.6.1.7.2. This event was reported as a loss   |
| of function in accordance with 10CFR50.72 b.2.iii.D.                         |
|                                                                              |
| "During Engineering evaluations of unit cooler condition, the surveillance   |
| test methodology was noted to contain a unit cooler face area that was       |
| smaller than the area depicted in the applicable design information.         |
| In-field measurements were taken on the unit coolers. These field            |
| measurements confirmed that a larger face area value should have been        |
| incorporated into the test methodology. Effectively, RBS had imposed a more  |
| conservative face area value resulting in lowering the  as calculated  flow  |
| rates that are used to determine acceptability.                              |
|                                                                              |
| "Recalculation of the volumetric flow using the appropriate area resulted in |
| the required Technical Specification SR 3.6.1.7.2 flow rate of 50,000 cubic  |
| feet per minute being achieved for primary containment unit cooler B.        |
| Therefore, primary containment unit cooler B was actually operable on        |
| September 30, 2000, at 2333 and at least one operable unit cooler was always |
| maintained. Therefore, this issue was not reportable.                        |
|                                                                              |
| "The coils of primary containment unit coolers A and B were also cleaned.    |
| Subsequently, using either the previous or recalculated value for the unit   |
| cooler face area, both unit coolers re-tested satisfactorily and were        |
| restored to service."                                                        |
|                                                                              |
| The NRC resident inspector will be informed of this retraction by the        |
| licensee. Notified R4DO (Harrell).                                           |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Other Nuclear Material                           |Event Number:   37472       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  PHILIP MORRIS USA                    |NOTIFICATION DATE: 10/30/2000|
|LICENSEE:  PHILIP MORRIS USA                    |NOTIFICATION TIME: 10:17[EST]|
|    CITY:  RICHMOND                 REGION:  2  |EVENT DATE:        10/29/2000|
|  COUNTY:                            STATE:  VA |EVENT TIME:        10:56[EST]|
|LICENSE#:  45-00385-06           AGREEMENT:  N  |LAST UPDATE DATE:  10/30/2000|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |ANNE BOLAND          R2      |
|                                                |DON COOL             NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  CHUCK STIFF                  |                             |
|  HQ OPS OFFICER:  DOUG WEAVER                  |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|IBBF 30.50(b)(2)(ii)     EQUIP DISABLED/FAILS   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| GAUGE SHUTTER FAILED TO CLOSE                                                |
|                                                                              |
| "On Sunday October 29, 2000, an Authorized User was conducting a routine,    |
| monthly radiation safety audit. The factory was running that weekend, but    |
| Bay 1 was shut down.  At 10:56 a.m. he noticed the shutter indicator on      |
| maker 1B4 indicated the shutter was open.  The maker at 1B4 is a Hauni       |
| Protos 100 (maker # 1004) with a Hauni weight control system and a Hauni SRM |
| 8000 scanning head (gauge # 1319).  This gauge has three Strontium 90 sealed |
| sources for a combined strength of 0.025 curies.                             |
|                                                                              |
| "The Authorized User inserted a cigarette rod in the pass tube to reduce the |
| radiation level and called the Electrical Supervisor on duty.  An Instrument |
| Electrician (IE) was called to diagnose the weight control system. The IE    |
| found a defective circuit board.  This Circuit board is located in the main  |
| electrical panel that controls the weight control system and the scanning    |
| head.  The Authorized User stayed at the scanning head while the IE removed  |
| the defective circuit board and took it to the Electrical Repair Shop for    |
| repair.  When the repaired circuit board was installed, the problem was      |
| fixed and the shutter closed properly.  The Authorized User used the key     |
| switch to test the shutter several times and conducted a final survey with   |
| the shutter closed to ensure the shutter was closed and the scanning head    |
| was safe.  The maker and scanning head were placed in service on C Shift, at |
| approximately 11:00 p.m., October 29, 2000.  The scanning head shutter would |
| not open and the circuit board was removed and repaired again. The maker and |
| scanning head were returned to service at approximately 6:30 a.m., October   |
| 30, 2000."                                                                   |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37473       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: HATCH                    REGION:  2  |NOTIFICATION DATE: 10/30/2000|
|    UNIT:  [1] [] []                 STATE:  GA |NOTIFICATION TIME: 12:00[EST]|
|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        10/30/2000|
+------------------------------------------------+EVENT TIME:        11:40[EST]|
| NRC NOTIFIED BY:  EDWEN URQUHART               |LAST UPDATE DATE:  10/30/2000|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |ANNE BOLAND          R2      |
|10 CFR SECTION:                                 |                             |
|DDDD 73.71               UNSPECIFIED PARAGRAPH  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Cold Shutdown    |0        Cold Shutdown    |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| SECURITY REPORT                                                              |
|                                                                              |
| Unescorted access granted inappropriately. Compensatory measures taken upon  |
| discovery. The NRC resident inspector has been informed of this event by the |
| licensee. Contact the NRC Operations Center for additional details.          |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Fuel Cycle Facility                              |Event Number:   37474       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PORTSMOUTH GASEOUS DIFFUSION PLANT   |NOTIFICATION DATE: 10/30/2000|
|   RXTYPE: URANIUM ENRICHMENT FACILITY          |NOTIFICATION TIME: 12:26[EST]|
| COMMENTS: 2 DEMOCRACY CENTER                   |EVENT DATE:        10/29/2000|
|           6903 ROCKLEDGE DRIVE                 |EVENT TIME:        19:54[EST]|
|           BETHESDA, MD 20817    (301)564-3200  |LAST UPDATE DATE:  10/30/2000|
|    CITY:  PIKETON                  REGION:  3  +-----------------------------+
|  COUNTY:  PIKE                      STATE:  OH |PERSON          ORGANIZATION |
|LICENSE#:  GDP-2                 AGREEMENT:  N  |DAVID HILLS          R3      |
|  DOCKET:  0707002                              |BRIAN SMITH          NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  KEITH VANDERPOOL             |                             |
|  HQ OPS OFFICER:  BOB STRANSKY                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NCFR                     NON CFR REPORT REQMNT  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 24-HOUR GASEOUS DIFFUSION PLANT REPORT                                       |
|                                                                              |
| "At approximately 1954 hours, 10/29/00, operations personnel investigated a  |
| LAW CADP smoke head alarm. While investigating the alarm for smoke head SXE  |
| 2786 for LAW 2A compressor the operations personnel did not identify any     |
| visible release but smelled HF in the area. The 'SEE & FLEE' emergency       |
| procedures were immediately implemented. The affected LAW station withdrawal |
| loop was in standby at the time of the alarm. Results of all surveys         |
| performed during the emergency response were less than MDA. At 2102 hours an |
| all clear was granted on the emergency response. PORTS is reporting this     |
| alarm as a valid actuation of a 'Q' Safety System.                           |
|                                                                              |
| "This is reportable to the NRC as a valid actuation of a 'Q' Safety System   |
| in accordance with Safety Analysis Report, section 6.9 (24-HOUR REPORT)."    |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37475       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PILGRIM                  REGION:  1  |NOTIFICATION DATE: 10/30/2000|
|    UNIT:  [1] [] []                 STATE:  MA |NOTIFICATION TIME: 13:23[EST]|
|   RXTYPE: [1] GE-3                             |EVENT DATE:        10/30/2000|
+------------------------------------------------+EVENT TIME:        12:30[EST]|
| NRC NOTIFIED BY:  KEN GRACIA                   |LAST UPDATE DATE:  10/30/2000|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |HAROLD GRAY          R1      |
|10 CFR SECTION:                                 |                             |
|AESS 50.72(b)(1)(v)      EMERGENCY SIREN INOP   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| EMERGENCY SIRENS INOPERABLE DUE TO FAILURE OF RADIO REPEATERS                |
|                                                                              |
| The licensee reported that all offsite emergency sirens were inoperable      |
| during the period from 0150 10/29/00 through 0745 10/30/00 due to the        |
| failure of both radio repeaters. This condition was discovered during siren  |
| troubleshooting on 10/30/00. One of the repeaters has been restored to       |
| service. The NRC resident inspector will be informed of this event by the    |
| licensee.                                                                    |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Thursday, March 25, 2021

Page Last Reviewed/Updated Thursday, March 25, 2021