Event Notification Report for October 25, 2000
U.S. Nuclear Regulatory Commission Operations Center Event Reports For 10/24/2000 - 10/25/2000 ** EVENT NUMBERS ** 37391 37448 37452 37453 !!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED !!!!!!! +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 37391 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: CLINTON REGION: 3 |NOTIFICATION DATE: 09/29/2000| | UNIT: [1] [] [] STATE: IL |NOTIFICATION TIME: 17:40[EDT]| | RXTYPE: [1] GE-6 |EVENT DATE: 09/29/2000| +------------------------------------------------+EVENT TIME: 13:20[CDT]| | NRC NOTIFIED BY: MARSHALL FUNKHOUSER |LAST UPDATE DATE: 10/24/2000| | HQ OPS OFFICER: DOUG WEAVER +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |BRENT CLAYTON R3 | |10 CFR SECTION: | | |AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION | | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N Y 99 Power Operation |99 Power Operation | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | HIGH PRESSURE CORE SPRAY DIESEL GENERATOR INOPERABLE | | | | At 1320 hours on 9/29/00, the seismic bolts of the Division 3 Diesel | | Generator (DG) control panel door were discovered missing. At 1450, | | Engineering determined that the seismic qualification of the control panel | | was in question with these bolts missing. | | | | On 9/27/00, during the day shift, the Division 3 DG was tested per Clinton | | Power Station (CPS) procedure 9080.02, DIESEL GENERATOR 1C OPERABILITY - | | MANUAL AND QUICK START OPERABILITY. This procedure requires instrumentation | | to be connected within the local control panel (1E22-S001B). The bolts to | | this panel were discovered missing today at 1320. It is possible that they | | had been missing since the performance of CPS 9080.02 but is unknown at this | | time. The Division 3 DG is not analyzed for these missing bolts and is | | considered inoperable while in this condition. | | | | This event is being reported pursuant to 10CFR50.72 (b)(2)(iii)(D) as a | | condition that alone could have prevented the fulfillment of the High | | Pressure Core Spray (HPCS) system, a single-train safety system needed to | | mitigate the consequences of an accident, since the Division 3 DG is an | | essential support system for the HPCS system needed to mitigate a small | | break LOCA concurrent with a Loss of offsite power. | | | | The bolts were restored at 1442 today and the Division 3 DG is operable. | | | | The licensee notified the NRC resident inspector. | | | | * * * UPDATE ON 10/24/00 @ 1826 BY SCHOTTEL TO GOULD * * * RETRACTION | | | | Further evaluation of this condition by engineering concluded that the | | absence of the bolts was seismically acceptable. A calculation determined | | that the estimated impact acceleration resulting from the unsecured door | | impacting the panel is 0.06g. Because this acceleration is small in | | relation to the seismic test margin documented in the original seismic | | calculation of the panel, the unsecured door would not have prevented the | | control panel from performing its safety function during seismic events. On | | this basis, the Division 3 DG and HPCS safety functions were not adversely | | affected by the absence of the bolts. Therefore, this issue Is not | | reportable under the provisions of 10CFR50.72 or 10CFR50.73 and this event | | notification is retracted. | | | | | | The NRC Resident Inspector was notified. | | | | The Reg 3 RDO(Vegel) was informed. | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 37448 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: INDIAN POINT REGION: 1 |NOTIFICATION DATE: 10/22/2000| | UNIT: [2] [] [] STATE: NY |NOTIFICATION TIME: 07:55[EDT]| | RXTYPE: [2] W-4-LP,[3] W-4-LP |EVENT DATE: 10/22/2000| +------------------------------------------------+EVENT TIME: 01:50[EDT]| | NRC NOTIFIED BY: KEVIN DONALLY |LAST UPDATE DATE: 10/24/2000| | HQ OPS OFFICER: FANGIE JONES +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |WILLIAM COOK R1 | |10 CFR SECTION: | | |NLTR LICENSEE 24 HR REPORT | | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |2 N N 0 Refueling |0 Refueling | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | 24 HOUR REPORT - 10 CFR 50.72 AND APPENDIX R | | | | "A section of the high pressure fire header will be isolated and drained. | | The reason for the impairment is planned maintenance for the replacement of | | a section of 12" piping and various small bore valve replacements. This | | header section provides fire protection for the Units 1 and 2 Intake | | Structure, the Auxiliary Boiler Feed Pump Building, the Transformer Yard and | | the Electrical Tunnel Deluge System. | | | | "Indian Point Station is in cold shutdown with the reactor defueled and | | steam generator replacement in progress. Therefore, the Auxiliary Boiler | | Feed Pumps and the Main and Unit Auxiliary Transformers are out of service | | and do not require fire protection. The safety related equipment that is | | required to be protected under this plant condition are the Service Water | | Pumps and the 480 VAC Electrical Cables for the Spent Fuel Cooling Pumps and | | Component Cooling Pumps which traverse the Electrical Tunnel. Compensatory | | hoses will be staged prior to applying the tagout. Fire tours will also be | | established to supplement the frequency with which these and the other | | impaired areas are surveilled. | | | | "The 24 Hour notification to the NRC for the Fire header impairment will | | made pursuant to 10CFR50.72 and App. R as well as the written report to | | follow within 14 days. The alternate fire protection system will not be | | established since the station is already in cold shutdown. A 30 day action | | statement will be entered for the inoperable hydrants protecting the Intake | | Structure and Service Water Pumps. A separate 14 day action statement will | | be entered for the inoperable Electrical Tunnel Deluge System. The duration | | of the impairment will be minimized and further compensatory measures may be | | necessary should any of the time limits be approached due to unforeseen | | circumstances." | | | | The licensee intends to notify the NRC Resident Inspector. | | | | | | * * * UPDATE ON 10/24/00 @ 1524 BY DONNELLY TO GOULD * * * | | | | The following update is providing additional information to clarify this | | event report. | | | | The following is an update to NRC event number 37448. A section of the | | high-pressure fire header will be isolated and drained for planned | | maintenance. A section of 12-inch piping is being replaced along with | | various sections of valves. The isolated section of piping supplies high | | pressure fire water to the Unit 1 and Unit 2 Intake structure, the Auxiliary | | Boiler Feed Pump Building, and the Electrical Tunnel Deluge System. | | | | The Indian Point Unit 2 Fire Protection Program requires that all piping and | | valves necessary for proper functioning of any portion of the system | | required for protection of safe shutdown systems be operable. If this | | condition is not restored within 24 hours, then an alternate fire protection | | system must be established or the plant must be placed in the hot shutdown | | condition utilizing normal operating procedures. Within the next 48 hours, | | if the system is not restored or an alternate system is not established, | | then the plant must be placed in the cold shutdown condition. Currently, | | Indian Point 2 station is in the de-fueled condition, with the core fully | | unloaded. Therefore, compensatory actions are not required to maintain the | | plant in the shutdown condition.. | | | | Compensatory measures are being undertaken by Indian Point 2 station for | | prudence. The intake structure contains the Service Water Pumps, which are | | safe shutdown equipment and are used to cool the Spent Fuel Pool. The | | inoperable hydrant on the intake structure will be supplemented by staged | | fire hoses and a 4 hour fire tour, and Indian Point 2 will enter a 30 Day | | Action Statement per SAO-703. Additional fire hoses will also be staged | | for the inoperable hydrant outside the auxiliary pump building. The | | electrical tunnel contains the 480 VAC Electrical cables for the Spent Fuel | | Cooling Pumps, the Component Cooling Water Pumps as well as additional | | electrical loads. Compensatory hoses will be staged in this area and the | | fire detectors are all still operational. A 14 Day Action Statement per | | SAQ-703 will be entered for this impairment. | | | | The 24 Hour Notification to the NRC for the fire header impairment will be | | made pursuant to 10CFR50.72 and Appendix R by telephone and a follow up | | facsimile. The duration of the impairment will be minimized and further | | compensatory measures may be necessary should any of the time limits be | | approached. due to unforeseen circumstances. Additional action statements | | may be entered if changes in plant status are required. | | | | The NRC Resident Inspector was informed. | | | | The Reg 1 RDO(Silk) was notified. | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 37452 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: SOUTH TEXAS REGION: 4 |NOTIFICATION DATE: 10/24/2000| | UNIT: [1] [] [] STATE: TX |NOTIFICATION TIME: 09:35[EDT]| | RXTYPE: [1] W-4-LP,[2] W-4-LP |EVENT DATE: 10/24/2000| +------------------------------------------------+EVENT TIME: 04:58[CDT]| | NRC NOTIFIED BY: BILL MOOKHOEK |LAST UPDATE DATE: 10/24/2000| | HQ OPS OFFICER: FANGIE JONES +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |GREG PICK R4 | |10 CFR SECTION: | | |AESF 50.72(b)(2)(ii) ESF ACTUATION | | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N Y 100 Power Operation |100 Power Operation | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | ESF ACTUATION RESULTING IN A SINGLE VALVE ISOLATION | | | | "On October 24, 2000, at 0458 hours, while Unit 1 was operating at 100% | | power, a spurious actuation of the Train C Phase B Containment Isolation | | Signal occurred. This actuation resulted in the closure of a single | | Engineered Safety Features Containment Isolation Valve servicing the cooling | | supply to the Reactor Coolant Pumps. Cooling to the Reactor Coolant Pumps | | was not interrupted since there are two parallel paths in this penetration | | to prevent inadvertent isolation of the cooling supply. No other components | | changed position and the Unit continued to operate at 100% power. The cause | | of the actuation is not yet known, but the actuation only effected valve | | 1-CC-MOV-0404. Trouble shooting is in process to determine the cause of the | | event, No other components are controlled by the Train C Phase B actuation | | logic." | | | | The licensee notified the NRC Resident Inspector. | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 37453 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: SURRY REGION: 2 |NOTIFICATION DATE: 10/24/2000| | UNIT: [1] [] [] STATE: VA |NOTIFICATION TIME: 10:30[EDT]| | RXTYPE: [1] W-3-LP,[2] W-3-LP |EVENT DATE: 10/24/2000| +------------------------------------------------+EVENT TIME: 07:41[EDT]| | NRC NOTIFIED BY: LISA HILBERT-SEMMES |LAST UPDATE DATE: 10/24/2000| | HQ OPS OFFICER: FANGIE JONES +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |ANNE BOLAND R2 | |10 CFR SECTION: | | |ARPS 50.72(b)(2)(ii) RPS ACTUATION | | |AESF 50.72(b)(2)(ii) ESF ACTUATION | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 A/R Y 100 Power Operation |0 Hot Shutdown | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | AUTOMATIC REACTOR TRIP DUE TO WORK DONE ON WRONG UNIT'S EHC | | | | "At 0741 hours, with Surry Power Station Unit 1 at 100% reactor power, a low | | low S/G level condition was received and an automatic reactor trip occurred. | | lmmediately prior to the trip, the Main Steam Dump Valves were observed to | | have received an open demand, and a loss of turbine load was exhibited. The | | loss of turbine load was caused by human error due to work on the wrong | | unit. It was determined that work was being conducted on the Unit 1 EHC | | System. The work was intended to be one on the Unit 2 EHC System. | | | | "All control rods inserted into the core as designed. IRPI B8 rod bottom | | light was not received due to a burned out light bulb. The light bulb was | | replaced and indicated properly. The IRPI indication for this rod trended | | with all other IRPI indications, and indicated <20 steps withdrawn. The | | shutdown margin for Unit 1 was determined to be satisfactory. Auxiliary | | feedwater automatically initiated as designed on low low steam generator | | level following the trip. Primary RCS temperature decreased to | | approximately 543 degrees following the reactor trip. | | | | "No primary safety or power operated relief valves were actuated during he | | event. As a result of the loss of turbine load, the secondary power | | operated relief valves actuated during the transient. No indication of | | primary to secondary leakage exists, therefore no adverse radiological | | consequences resulted from this event. | | | | "All electrical busses transferred properly following the trip and all | | emergency diesel generators are operable. There were no radiation releases | | due to this event, nor were there any personnel injuries or contamination | | events. The cause of the event is being investigated. | | | | "Unit 1 is currently at Hot Shutdown with RCS temperature being maintained | | at approximately 547 degrees. | | | | "Unit 2 was not affected by this event and remains stable at CSD with RCS | | temperature at approximately 100�F and the RCS depressurized to atmospheric | | pressure with containment Type A test conditions being established. | | | | "This event is being reported in accordance with 10CFR50.72(b)(2)(ii)." | | | | The licensee notified the NRC Resident Inspector. | +------------------------------------------------------------------------------+
Page Last Reviewed/Updated Thursday, March 25, 2021
Page Last Reviewed/Updated Thursday, March 25, 2021