The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.
Event Notification Report for October 25, 2000
U.S. Nuclear Regulatory Commission
Operations Center
Event Reports For
10/24/2000 - 10/25/2000
** EVENT NUMBERS **
37391 37448 37452 37453
!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37391 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CLINTON REGION: 3 |NOTIFICATION DATE: 09/29/2000|
| UNIT: [1] [] [] STATE: IL |NOTIFICATION TIME: 17:40[EDT]|
| RXTYPE: [1] GE-6 |EVENT DATE: 09/29/2000|
+------------------------------------------------+EVENT TIME: 13:20[CDT]|
| NRC NOTIFIED BY: MARSHALL FUNKHOUSER |LAST UPDATE DATE: 10/24/2000|
| HQ OPS OFFICER: DOUG WEAVER +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |BRENT CLAYTON R3 |
|10 CFR SECTION: | |
|AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 99 Power Operation |99 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| HIGH PRESSURE CORE SPRAY DIESEL GENERATOR INOPERABLE |
| |
| At 1320 hours on 9/29/00, the seismic bolts of the Division 3 Diesel |
| Generator (DG) control panel door were discovered missing. At 1450, |
| Engineering determined that the seismic qualification of the control panel |
| was in question with these bolts missing. |
| |
| On 9/27/00, during the day shift, the Division 3 DG was tested per Clinton |
| Power Station (CPS) procedure 9080.02, DIESEL GENERATOR 1C OPERABILITY - |
| MANUAL AND QUICK START OPERABILITY. This procedure requires instrumentation |
| to be connected within the local control panel (1E22-S001B). The bolts to |
| this panel were discovered missing today at 1320. It is possible that they |
| had been missing since the performance of CPS 9080.02 but is unknown at this |
| time. The Division 3 DG is not analyzed for these missing bolts and is |
| considered inoperable while in this condition. |
| |
| This event is being reported pursuant to 10CFR50.72 (b)(2)(iii)(D) as a |
| condition that alone could have prevented the fulfillment of the High |
| Pressure Core Spray (HPCS) system, a single-train safety system needed to |
| mitigate the consequences of an accident, since the Division 3 DG is an |
| essential support system for the HPCS system needed to mitigate a small |
| break LOCA concurrent with a Loss of offsite power. |
| |
| The bolts were restored at 1442 today and the Division 3 DG is operable. |
| |
| The licensee notified the NRC resident inspector. |
| |
| * * * UPDATE ON 10/24/00 @ 1826 BY SCHOTTEL TO GOULD * * * RETRACTION |
| |
| Further evaluation of this condition by engineering concluded that the |
| absence of the bolts was seismically acceptable. A calculation determined |
| that the estimated impact acceleration resulting from the unsecured door |
| impacting the panel is 0.06g. Because this acceleration is small in |
| relation to the seismic test margin documented in the original seismic |
| calculation of the panel, the unsecured door would not have prevented the |
| control panel from performing its safety function during seismic events. On |
| this basis, the Division 3 DG and HPCS safety functions were not adversely |
| affected by the absence of the bolts. Therefore, this issue Is not |
| reportable under the provisions of 10CFR50.72 or 10CFR50.73 and this event |
| notification is retracted. |
| |
| |
| The NRC Resident Inspector was notified. |
| |
| The Reg 3 RDO(Vegel) was informed. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37448 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: INDIAN POINT REGION: 1 |NOTIFICATION DATE: 10/22/2000|
| UNIT: [2] [] [] STATE: NY |NOTIFICATION TIME: 07:55[EDT]|
| RXTYPE: [2] W-4-LP,[3] W-4-LP |EVENT DATE: 10/22/2000|
+------------------------------------------------+EVENT TIME: 01:50[EDT]|
| NRC NOTIFIED BY: KEVIN DONALLY |LAST UPDATE DATE: 10/24/2000|
| HQ OPS OFFICER: FANGIE JONES +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |WILLIAM COOK R1 |
|10 CFR SECTION: | |
|NLTR LICENSEE 24 HR REPORT | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2 N N 0 Refueling |0 Refueling |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| 24 HOUR REPORT - 10 CFR 50.72 AND APPENDIX R |
| |
| "A section of the high pressure fire header will be isolated and drained. |
| The reason for the impairment is planned maintenance for the replacement of |
| a section of 12" piping and various small bore valve replacements. This |
| header section provides fire protection for the Units 1 and 2 Intake |
| Structure, the Auxiliary Boiler Feed Pump Building, the Transformer Yard and |
| the Electrical Tunnel Deluge System. |
| |
| "Indian Point Station is in cold shutdown with the reactor defueled and |
| steam generator replacement in progress. Therefore, the Auxiliary Boiler |
| Feed Pumps and the Main and Unit Auxiliary Transformers are out of service |
| and do not require fire protection. The safety related equipment that is |
| required to be protected under this plant condition are the Service Water |
| Pumps and the 480 VAC Electrical Cables for the Spent Fuel Cooling Pumps and |
| Component Cooling Pumps which traverse the Electrical Tunnel. Compensatory |
| hoses will be staged prior to applying the tagout. Fire tours will also be |
| established to supplement the frequency with which these and the other |
| impaired areas are surveilled. |
| |
| "The 24 Hour notification to the NRC for the Fire header impairment will |
| made pursuant to 10CFR50.72 and App. R as well as the written report to |
| follow within 14 days. The alternate fire protection system will not be |
| established since the station is already in cold shutdown. A 30 day action |
| statement will be entered for the inoperable hydrants protecting the Intake |
| Structure and Service Water Pumps. A separate 14 day action statement will |
| be entered for the inoperable Electrical Tunnel Deluge System. The duration |
| of the impairment will be minimized and further compensatory measures may be |
| necessary should any of the time limits be approached due to unforeseen |
| circumstances." |
| |
| The licensee intends to notify the NRC Resident Inspector. |
| |
| |
| * * * UPDATE ON 10/24/00 @ 1524 BY DONNELLY TO GOULD * * * |
| |
| The following update is providing additional information to clarify this |
| event report. |
| |
| The following is an update to NRC event number 37448. A section of the |
| high-pressure fire header will be isolated and drained for planned |
| maintenance. A section of 12-inch piping is being replaced along with |
| various sections of valves. The isolated section of piping supplies high |
| pressure fire water to the Unit 1 and Unit 2 Intake structure, the Auxiliary |
| Boiler Feed Pump Building, and the Electrical Tunnel Deluge System. |
| |
| The Indian Point Unit 2 Fire Protection Program requires that all piping and |
| valves necessary for proper functioning of any portion of the system |
| required for protection of safe shutdown systems be operable. If this |
| condition is not restored within 24 hours, then an alternate fire protection |
| system must be established or the plant must be placed in the hot shutdown |
| condition utilizing normal operating procedures. Within the next 48 hours, |
| if the system is not restored or an alternate system is not established, |
| then the plant must be placed in the cold shutdown condition. Currently, |
| Indian Point 2 station is in the de-fueled condition, with the core fully |
| unloaded. Therefore, compensatory actions are not required to maintain the |
| plant in the shutdown condition.. |
| |
| Compensatory measures are being undertaken by Indian Point 2 station for |
| prudence. The intake structure contains the Service Water Pumps, which are |
| safe shutdown equipment and are used to cool the Spent Fuel Pool. The |
| inoperable hydrant on the intake structure will be supplemented by staged |
| fire hoses and a 4 hour fire tour, and Indian Point 2 will enter a 30 Day |
| Action Statement per SAO-703. Additional fire hoses will also be staged |
| for the inoperable hydrant outside the auxiliary pump building. The |
| electrical tunnel contains the 480 VAC Electrical cables for the Spent Fuel |
| Cooling Pumps, the Component Cooling Water Pumps as well as additional |
| electrical loads. Compensatory hoses will be staged in this area and the |
| fire detectors are all still operational. A 14 Day Action Statement per |
| SAQ-703 will be entered for this impairment. |
| |
| The 24 Hour Notification to the NRC for the fire header impairment will be |
| made pursuant to 10CFR50.72 and Appendix R by telephone and a follow up |
| facsimile. The duration of the impairment will be minimized and further |
| compensatory measures may be necessary should any of the time limits be |
| approached. due to unforeseen circumstances. Additional action statements |
| may be entered if changes in plant status are required. |
| |
| The NRC Resident Inspector was informed. |
| |
| The Reg 1 RDO(Silk) was notified. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37452 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SOUTH TEXAS REGION: 4 |NOTIFICATION DATE: 10/24/2000|
| UNIT: [1] [] [] STATE: TX |NOTIFICATION TIME: 09:35[EDT]|
| RXTYPE: [1] W-4-LP,[2] W-4-LP |EVENT DATE: 10/24/2000|
+------------------------------------------------+EVENT TIME: 04:58[CDT]|
| NRC NOTIFIED BY: BILL MOOKHOEK |LAST UPDATE DATE: 10/24/2000|
| HQ OPS OFFICER: FANGIE JONES +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |GREG PICK R4 |
|10 CFR SECTION: | |
|AESF 50.72(b)(2)(ii) ESF ACTUATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| ESF ACTUATION RESULTING IN A SINGLE VALVE ISOLATION |
| |
| "On October 24, 2000, at 0458 hours, while Unit 1 was operating at 100% |
| power, a spurious actuation of the Train C Phase B Containment Isolation |
| Signal occurred. This actuation resulted in the closure of a single |
| Engineered Safety Features Containment Isolation Valve servicing the cooling |
| supply to the Reactor Coolant Pumps. Cooling to the Reactor Coolant Pumps |
| was not interrupted since there are two parallel paths in this penetration |
| to prevent inadvertent isolation of the cooling supply. No other components |
| changed position and the Unit continued to operate at 100% power. The cause |
| of the actuation is not yet known, but the actuation only effected valve |
| 1-CC-MOV-0404. Trouble shooting is in process to determine the cause of the |
| event, No other components are controlled by the Train C Phase B actuation |
| logic." |
| |
| The licensee notified the NRC Resident Inspector. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37453 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SURRY REGION: 2 |NOTIFICATION DATE: 10/24/2000|
| UNIT: [1] [] [] STATE: VA |NOTIFICATION TIME: 10:30[EDT]|
| RXTYPE: [1] W-3-LP,[2] W-3-LP |EVENT DATE: 10/24/2000|
+------------------------------------------------+EVENT TIME: 07:41[EDT]|
| NRC NOTIFIED BY: LISA HILBERT-SEMMES |LAST UPDATE DATE: 10/24/2000|
| HQ OPS OFFICER: FANGIE JONES +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |ANNE BOLAND R2 |
|10 CFR SECTION: | |
|ARPS 50.72(b)(2)(ii) RPS ACTUATION | |
|AESF 50.72(b)(2)(ii) ESF ACTUATION | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 A/R Y 100 Power Operation |0 Hot Shutdown |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| AUTOMATIC REACTOR TRIP DUE TO WORK DONE ON WRONG UNIT'S EHC |
| |
| "At 0741 hours, with Surry Power Station Unit 1 at 100% reactor power, a low |
| low S/G level condition was received and an automatic reactor trip occurred. |
| lmmediately prior to the trip, the Main Steam Dump Valves were observed to |
| have received an open demand, and a loss of turbine load was exhibited. The |
| loss of turbine load was caused by human error due to work on the wrong |
| unit. It was determined that work was being conducted on the Unit 1 EHC |
| System. The work was intended to be one on the Unit 2 EHC System. |
| |
| "All control rods inserted into the core as designed. IRPI B8 rod bottom |
| light was not received due to a burned out light bulb. The light bulb was |
| replaced and indicated properly. The IRPI indication for this rod trended |
| with all other IRPI indications, and indicated <20 steps withdrawn. The |
| shutdown margin for Unit 1 was determined to be satisfactory. Auxiliary |
| feedwater automatically initiated as designed on low low steam generator |
| level following the trip. Primary RCS temperature decreased to |
| approximately 543 degrees following the reactor trip. |
| |
| "No primary safety or power operated relief valves were actuated during he |
| event. As a result of the loss of turbine load, the secondary power |
| operated relief valves actuated during the transient. No indication of |
| primary to secondary leakage exists, therefore no adverse radiological |
| consequences resulted from this event. |
| |
| "All electrical busses transferred properly following the trip and all |
| emergency diesel generators are operable. There were no radiation releases |
| due to this event, nor were there any personnel injuries or contamination |
| events. The cause of the event is being investigated. |
| |
| "Unit 1 is currently at Hot Shutdown with RCS temperature being maintained |
| at approximately 547 degrees. |
| |
| "Unit 2 was not affected by this event and remains stable at CSD with RCS |
| temperature at approximately 100�F and the RCS depressurized to atmospheric |
| pressure with containment Type A test conditions being established. |
| |
| "This event is being reported in accordance with 10CFR50.72(b)(2)(ii)." |
| |
| The licensee notified the NRC Resident Inspector. |
+------------------------------------------------------------------------------+
Page Last Reviewed/Updated Thursday, March 25, 2021
Page Last Reviewed/Updated Thursday, March 25, 2021