Skip to main content

The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.

Event Notification Report for September 22, 2000

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           09/21/2000 - 09/22/2000

                              ** EVENT NUMBERS **

37251  37300  37304  37330  37358  37359  37360  37361  37362  37363  37364  37365 


!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37251       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PERRY                    REGION:  3  |NOTIFICATION DATE: 08/23/2000|
|    UNIT:  [1] [] []                 STATE:  OH |NOTIFICATION TIME: 18:22[EDT]|
|   RXTYPE: [1] GE-6                             |EVENT DATE:        08/23/2000|
+------------------------------------------------+EVENT TIME:        15:00[EDT]|
| NRC NOTIFIED BY:  BOB KIDDER                   |LAST UPDATE DATE:  09/21/2000|
|  HQ OPS OFFICER:  DICK JOLLIFFE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |PATRICK HILAND       R3      |
|10 CFR SECTION:                                 |                             |
|AINB 50.72(b)(2)(iii)(B) POT RHR INOP           |                             |
|AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION    |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       98       Power Operation  |98       Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| - ECC SYSTEM MOV MAY NOT CLOSE DURING A LOCA AND A LOOP AS REQUIRED  -       |
|                                                                              |
| While reviewing motor operated valve (MOV) data from December, 1999, plant   |
| staff personnel identified an error in the analyzed data for the closing     |
| torque for an MOV in the Emergency Closed Cooling (ECC) System that is       |
| required to close during a Loss of Coolant Accident (LOCA) and a Loss of     |
| Offsite Power (LOOP).                                                        |
|                                                                              |
| The valve, #OP42-F0295B, isolates the ECC System from the Nuclear Closed     |
| Cooling (NCC) Water System.  A second isolation valve, #OP42-F0290, was      |
| subsequently found to have insufficient data to ensure that it alone would   |
| have provided the required isolation.  Failure of both valves to potentially |
| not close completely could cause the ECC System to transfer the system's     |
| cooling water inventory via the NCC Water System to the Intermediate         |
| Building resulting in the loss of cooling capability of the ECC System. This |
| would result in the loss of cooling capability for the systems required to   |
| support the Residual Heat Removal (RHR) 'B' and 'C' Subsystems. The #F0290   |
| valve has been successfully tested to ensure that it has adequate torque to  |
| close under accident conditions; however, there is insufficient leakage test |
| data available on this valve at this time.  Therefore, assuming that valve   |
| #F0290 leaks and valve #F0295B does not fully close, a total loss of         |
| inventory would potentially occur for Division 2.                            |
|                                                                              |
| Therefore, this condition is being conservatively reported to the NRC as a   |
| loss of safety function during a past outage which removed RHR 'A' from      |
| service, until further evaluation is completed.                              |
|                                                                              |
| Valve #OP42-F0295B has been electrically closed under static flow conditions |
| to ensure continued operability of the ECC System.                           |
|                                                                              |
| Licensee planned actions include further evaluation of past test data or     |
| performance of a specific leak test on valve #OP42-F0290 and further         |
| evaluation of data on valve #OP42-F0295B.                                    |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
|                                                                              |
| * * * RETRACTED AT 1622 EDT ON 9/21/00 BY MICHAEL McFARLAND TO FANGIE JONES  |
| * * *                                                                        |
|                                                                              |
| "A 10 CFR 50.72, four (4) hour non-emergency notification was initially made |
| on 8-23-2000, due to Emergency Closed Cooling Loop B inoperability           |
| subsequent to valve OP42-F0295B inoperability, due to inadequate closing     |
| torque under dynamic flow conditions concurrent with an outage on the        |
| alternate, Division 1, equipment. it was indeterminate at that time if       |
| sufficient torque existed for the valve to close under accident conditions.  |
|                                                                              |
| "Subsequent to the event notification, the valve has been tested under       |
| dynamic flow and reevaluated. This information has resulted in a             |
| determination that the OP42-F0295B valve has been, and continues to be,      |
| operable under both normal and accident conditions.                          |
|                                                                              |
| "Since the valve was determined to have been continuously operable, no       |
| Technical Specification Required Actions were exceeded and both loops of ECC |
| remained operable. This event was determined not reportable and ENF 37251 is |
| retracted."                                                                  |
|                                                                              |
| The licensee notified the NRC Resident Inspector.  The R3DO (Bruce Burgess)  |
| was notified.                                                                |
+------------------------------------------------------------------------------+

!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Fuel Cycle Facility                              |Event Number:   37300       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PORTSMOUTH GASEOUS DIFFUSION PLANT   |NOTIFICATION DATE: 09/09/2000|
|   RXTYPE: URANIUM ENRICHMENT FACILITY          |NOTIFICATION TIME: 10:21[EDT]|
| COMMENTS: 2 DEMOCRACY CENTER                   |EVENT DATE:        09/08/2000|
|           6903 ROCKLEDGE DRIVE                 |EVENT TIME:        20:00[EDT]|
|           BETHESDA, MD 20817    (301)564-3200  |LAST UPDATE DATE:  09/21/2000|
|    CITY:  PIKETON                  REGION:  3  +-----------------------------+
|  COUNTY:  PIKE                      STATE:  OH |PERSON          ORGANIZATION |
|LICENSE#:  GDP-2                 AGREEMENT:  N  |GARY SHEAR           R3      |
|  DOCKET:  0707002                              |                             |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  JEFF CASTLE                  |                             |
|  HQ OPS OFFICER:  STEVE SANDIN                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NBNL                     RESPONSE-BULLETIN      |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 24-HOUR NRC BULLETIN 91-01 REPORT INVOLVING SAFETY SYSTEM ACTUATION          |
|                                                                              |
| "On 9/8/2000 at 2000 hours a safety system actuation occurred in the X344    |
| building.  Autoclave #4 was in Mode II 'Heating'  when the High Condensate   |
| Level Shutoff safety system actuated.  Per TSR 2.1.3.7, the autoclave was    |
| placed in Mode VII  'Shutdown', a mode in which the High Condensate level    |
| Shutoff system is not required, and declared inoperable. This is being       |
| reported as a valid safety system actuation.  An engineering evaluation has  |
| been initiated to review the system conditions that surrounded the actuation |
| of the safety system."                                                       |
|                                                                              |
| Operations notified both the NRC resident inspector and DOE site             |
| representative.                                                              |
|                                                                              |
| * * * RETRACTED AT 2323 EDT ON 9/21/00 BY ERIC SPAETH TO FANGIE JONES * * *  |
|                                                                              |
| "RETRACTION:  On 09/21/00, the Plant Shift Superintendent retracted the      |
| above Event. At the time of the High Condensate Level Shutoff (HCLS) system  |
| actuation, the autoclave was being cycled on and off in accordance with the  |
| applicable procedure for heating a Russian cylinder. Follow up investigation |
| by engineering and operations has determined the HCLS actuation occurred     |
| while AC #4 was in Mode VII 'Shutdown'.                                      |
|                                                                              |
| "Discussions with building supervision and the operator who witnessed the    |
| HCLS actuation revealed the AC #4 had been shutdown as part of the on/off    |
| heating cycle before the actuation occurred. Based on the configuration of   |
| AC #4 at the time, the AC would have been in Mode VII 'Shutdown'.            |
|                                                                              |
| "Since the HCLS system is not required to be operable in Mode VII            |
| 'Shutdown', the HCLS system actuation was invalid, and is not reportable in  |
| accordance with 10CFR76.120(c)(2). Accordingly, this event is being          |
| retracted."                                                                  |
|                                                                              |
| The plant has informed the NRC Resident Inspector.  The R3DO (Bruce Burgess) |
| and NMSS EO (John Greeves) has been notified.                                |
+------------------------------------------------------------------------------+

!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   37304       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  LAKEHEAD PIPE LINE CO., INC          |NOTIFICATION DATE: 09/11/2000|
|LICENSEE:  LAKEHEAD PIPE LINE CO., INC          |NOTIFICATION TIME: 11:20[EDT]|
|    CITY:  LEWISTON                 REGION:  3  |EVENT DATE:        09/11/2000|
|  COUNTY:                            STATE:  MI |EVENT TIME:        08:00[EDT]|
|LICENSE#:  22-26732-01           AGREEMENT:  N  |LAST UPDATE DATE:  09/21/2000|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |MARK RING            R3      |
|                                                |BRIAN SMITH          NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  ROBERT POLLOCK               |                             |
|  HQ OPS OFFICER:  STEVE SANDIN                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NINF                     INFORMATION ONLY       |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| REPORT INVOLVING POSSIBLE EQUIPMENT SAFETY DEVICE FAILURE                    |
|                                                                              |
| THE LAKEHEAD PIPE LINE RADIATION SAFETY OFFICER (RSO), WAS INFORMED  AT 0800 |
| ON 9/11/00 THAT THE COUNTER ON A NUCLEAR DENSITY GAUGE HAD STOPPED WORKING   |
| SOMETIME IN MAY OF THIS YEAR AT THEIR LEWISTON STATION LOCATED IN LEWISTON,  |
| MICHIGAN.  THE SOURCE IS IN THE SHIELDED AND LOCKED POSITION.  THE DEVICE IS |
| A MODEL 7400 MANUFACTURED BY BERTHOLD SYSTEMS CONTAINING A 350 MILLICURIE    |
| CS-137 SOURCE.                                                               |
|                                                                              |
| * * * RETRACTED AT 1601 EDT ON 9/21/00 BY ROBERT POLLOCK TO FANGIE JONES * * |
| *                                                                            |
|                                                                              |
| After discussion with NRC Region 3 (Geoffrey Wright), it was determined that |
| this event was not reportable as the source was not involved, safely stored  |
| at all times, and the problem was only with the electronics.  This event     |
| notification is retracted.                                                   |
|                                                                              |
| The R3DO (Bruce Burgess) and the NMSS EO (John Greeves) has been informed.   |
+------------------------------------------------------------------------------+

!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37330       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PEACH BOTTOM             REGION:  1  |NOTIFICATION DATE: 09/15/2000|
|    UNIT:  [2] [] []                 STATE:  PA |NOTIFICATION TIME: 17:57[EDT]|
|   RXTYPE: [2] GE-4,[3] GE-4                    |EVENT DATE:        09/15/2000|
+------------------------------------------------+EVENT TIME:        15:05[EDT]|
| NRC NOTIFIED BY:  JESSE JAMES                  |LAST UPDATE DATE:  09/21/2000|
|  HQ OPS OFFICER:  JOHN MacKINNON               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |JAMES TRAPP          R1      |
|10 CFR SECTION:                                 |                             |
|ARPS 50.72(b)(2)(ii)     RPS ACTUATION          |                             |
|AESF 50.72(b)(2)(ii)     ESF ACTUATION          |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2     M/R        Y       15       Power Operation  |0        Hot Shutdown     |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| MANUALLY SCRAMMED THE REACTOR AFTER ENTERING THE RESTRICTIVE AREA OF THE     |
| POWER TO FLOW MAP.                                                           |
|                                                                              |
| On September 15, 2000 at Peach Bottom Atomic Power Station, Unit 2 was       |
| manually scrammed per operating procedure during turbine testing in          |
| preparation for the refuel outage.                                           |
|                                                                              |
| The manual scram was due to entering restricted area of the power to flow    |
| map from Technical Specification 3.4.1, after the trip of the "2B"           |
| recirculation pump.  All rods fully inserted and the reactor was shutdown.   |
| Reactor level during the scram lowered to 0" and a Group II and III primary  |
| and secondary containment isolation was received.  The isolations functioned |
| as designed.  The plant is stable in hot shutdown with the main condenser as |
| a heat sink and the feedwater system is in service for level control.  No    |
| radioactive release or Emergency Core Cooling System injection occurred      |
| during the scram.                                                            |
|                                                                              |
| The turbine was tripped in accordance with the refuel outage plan when the   |
| recirculation pump tripped.  The plan was to perform turbine testing and     |
| then to manually scram the reactor at the same power level.                  |
|                                                                              |
| The reactor was manually scrammed less than one minute after entering the    |
| restricted area of the power to flow map.  No power oscillations were seen.  |
|                                                                              |
| The NRC Resident Inspector was notified of this event by the licensee.       |
|                                                                              |
| * * * RETRACTED AT 1715 EDT ON 9/21/00 BY ANDREW WINTER TO FANGIE JONES * *  |
| *                                                                            |
|                                                                              |
| "On September 15, 2000 PBAPS reported that Unit 2 was manually scrammed in   |
| accordance with operating instructions during turbine testing. The report    |
| identified that the manual scram was initiated based on entering the         |
| restricted area of the power to flow map after the tripping of the 2B        |
| Recirculation Pump. This notification is being retracted based on the        |
| following:                                                                   |
|                                                                              |
| "NUREG 1022 Revision 1 specifically states that 'The Commission is           |
| interested both in events where an ESF was needed to mitigate the            |
| consequences (whether or not the equipment performed properly) and events    |
| where an ESF actuated unnecessarily....This indicates an intent to require   |
| reporting actuations of features that mitigate the consequences of           |
| significant events.' Therefore, the following is an analysis of these two    |
| underlying reasons for reporting ESF actuations:                             |
|                                                                              |
| 1. The need for the ESF to mitigate the consequences of an event:            |
|                                                                              |
| The September 15, 2000 PBAPS manual scram was initiated because the plant    |
| operator made a conservative decision in accordance with station procedures  |
| to initiate a reactor scram. At the time this decision was made, the plant   |
| conditions were approximately 16 percent power and 24 percent core flow.     |
| Although this condition is close to an operational limit conservatively      |
| established by the licensee and the operator made the correct decision to    |
| commence the plant shutdown, the ESF actuation was not necessary to mitigate |
| the consequences of this evolution. Moreover, plant conditions were not      |
| changing in a direction that would have required the manual scram to         |
| mitigate the consequences of significant events.                             |
|                                                                              |
| 2. Events where an ESF actuated unnecessarily:                               |
|                                                                              |
| The actuation of a manual scram and the subsequent PCIS Group II and Ill     |
| actuations were part of a preplanned shutdown for the commencement of the    |
| PBAPS Unit 2's thirteenth refueling outage (2R13) and were necessary to      |
| complete the plant shutdown. The decision to insert the manual scram in      |
| accordance with station procedures, resulted in the preplanned shutdown      |
| commencing slightly early. Therefore, the ESP did not actuate unnecessarily  |
| since it was already planned to shutdown the plant by inserting a manual     |
| scram.                                                                       |
|                                                                              |
| "Therefore, based on the above discussion, this event is not reportable      |
| because the manual scram resulted from and was, in accordance with the       |
| licensee's procedure, and part of a preplanned sequence of reactor           |
| operation."                                                                  |
|                                                                              |
| The licensee notified the NRC Resident Inspector.  The R1DO (William Ruland) |
| has been notified.                                                           |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37358       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: POINT BEACH              REGION:  3  |NOTIFICATION DATE: 09/20/2000|
|    UNIT:  [1] [2] []                STATE:  WI |NOTIFICATION TIME: 17:51[EDT]|
|   RXTYPE: [1] W-2-LP,[2] W-2-LP                |EVENT DATE:        09/20/2000|
+------------------------------------------------+EVENT TIME:        16:05[CDT]|
| NRC NOTIFIED BY:  RYAN RODE                    |LAST UPDATE DATE:  09/21/2000|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |BRUCE BURGESS        R3      |
|10 CFR SECTION:                                 |                             |
|AOUT 50.72(b)(1)(ii)(B)  OUTSIDE DESIGN BASIS   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| PLANT OUTSIDE 10 CFR PART 50 APPENDIX R DESIGN BASIS DUE TO PROCEDURAL       |
| ISSUES                                                                       |
|                                                                              |
| "During the final review of the new Appendix R rebaselining project, it was  |
| discovered that the refueling water storage tank (RWST) inventory could be   |
| lost if AOP 10A, 'Safe Shutdown-Local Control' and AOP 10B 'Safe to Cold     |
| Shutdown in Local Control' were performed as written. The postulated event   |
| occurs during an Appendix R fire where SI-851(RHR pump suction from          |
| containment sump B) encounters a spurious open signal, causing the RWST to   |
| drain via backflow into containment. The procedures do not address this      |
| potential failure early enough into the event to preclude a potential loss   |
| of RWST inventory. This puts Point Beach Nuclear Power Plant outside of its  |
| design basis because 10CFR50 Appendix R Section III.L.2.b performance goals  |
| might not be met for the above scenario."                                    |
|                                                                              |
| The NRC resident inspector will be informed of this notification by the      |
| licensee.                                                                    |
|                                                                              |
| * * * UPDATE AT 1424 EDT ON 9/21/00 BY RYAN RODE TO FANGIE JONES * * *       |
|                                                                              |
| "This is an update to Event Notification 37358. That notification reported a |
| procedural deficiency involving AOP 10A, 'Safe Shutdown - Local Control' and |
| AOP 10B. 'Safe to Cold Shutdown in Local Control,' in the event of a         |
| postulated Appendix R fire which results in a spurious open signal to the    |
| SI-851A/B valves, 'RHR Pump Suction from Containment Sump B.' This           |
| notification discussed the concern with this spurious valve opening          |
| occurring during AOP 10A, which was a potential loss of RWST inventory to    |
| the containment sump through the SI-856A/B, 'RHR Pump Suctions From RWST,'   |
| valves.                                                                      |
|                                                                              |
| "Although appropriately identified in the License's condition report, this   |
| notification did not include a discussion of the concern identified during   |
| conduct of procedure AOP 10B. Specifically, since no action is specified to  |
| verify that the SI-851 A/B valves are closed in either AOP 10A or AOP 10B,   |
| in the event of the Appendix R fire which results in the spurious opening of |
| those valves, when the RHR system is aligned for normal recirculation during |
| the cooldown, the RCS inventory could be reduced by leakage through the open |
| SI-851 valve to the containment sump. As mentioned in the original event     |
| notification, 10 CFR 50 Appendix R Section III.L.2.b requires the            |
| performance goal for maintaining RCS level within the level indication in    |
| the pressurizer be met. The procedures as written do not assure this         |
| performance goal would be met and are reported as a potential condition that |
| is outside the Appendix R design basis."                                     |
|                                                                              |
| The licensee notified the NRC Resident Inspector.  The R3DO (Bruce Burgess)  |
| has been notified.                                                           |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37359       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SUMMER                   REGION:  2  |NOTIFICATION DATE: 09/21/2000|
|    UNIT:  [1] [] []                 STATE:  SC |NOTIFICATION TIME: 06:51[EDT]|
|   RXTYPE: [1] W-3-LP                           |EVENT DATE:        09/21/2000|
+------------------------------------------------+EVENT TIME:        06:00[EDT]|
| NRC NOTIFIED BY:  LUCAS                        |LAST UPDATE DATE:  09/21/2000|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |THOMAS DECKER        R2      |
|10 CFR SECTION:                                 |                             |
|AUNA 50.72(b)(1)(ii)(A)  UNANALYZED COND OP     |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       96       Power Operation  |96       Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| TURBINE DRIVEN EMERGENCY FEED PUMP DISCHARGE VALVE WAS DISCOVERED LOCKED.    |
|                                                                              |
| The turbine driven Emergency Feed pump discharge valve (XV601036-EF) was     |
| discovered locked closed instead of locked open as required.  This condition |
| rendered the turbine driven Emergency Feed pump inoperable.  The valve was   |
| last operated on 8/4/00.  During the period when the discharge valve was     |
| closed, both diesels had been removed from service for maintenance.  The "A" |
| D/G was removed from service between 9/5/00 - 9/6/00 and the "B" D/G was     |
| removed from service between 9/19/00 - 9/20/00.   The licensee is            |
| investigating the cause.                                                     |
|                                                                              |
| The NRC Resident Inspector will be notified.                                 |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   37360       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  MARYLAND DEPART. OF THE ENVIRONMENT  |NOTIFICATION DATE: 09/21/2000|
|LICENSEE:  D W KOZERA INC                       |NOTIFICATION TIME: 09:48[EDT]|
|    CITY:  BALTIMORE                REGION:  1  |EVENT DATE:        09/20/2000|
|  COUNTY:                            STATE:  MD |EVENT TIME:        14:30[EDT]|
|LICENSE#:  MD0514901             AGREEMENT:  Y  |LAST UPDATE DATE:  09/21/2000|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |WILLIAM RULAND       R1      |
|                                                |JOSIE PICCONE        NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  MANLEY                       |                             |
|  HQ OPS OFFICER:  CHAUNCEY GOULD               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| LOST TROXLER MOISTURE DENSITY GAUGE REPORTED TO THE MARYLAND DEPARTMENT OF   |
| THE ENVIRONMENT (MDE)                                                        |
|                                                                              |
| Maryland licensee, D W Kozera Inc. of Baltimore, Md. lost a Troxler moisture |
| density gauge model 3430 serial # 25607 in Adamstown, Md.  The gauge was     |
| missing from the back of a flat bed truck , which had its tailgate down,     |
| that was being driven around the Greenhill Manor Residential subdivision(New |
| Design Rd & Union Ridge Rd in Fredrick City).  The gauge, which apparently   |
| fell out of the back of the truck, was not in its case and the source rod    |
| was not padlocked.  The source (7.2 millicuries of cesium 137 and 39.7       |
| millicuries of americium 241), as far as they know, was in the shielded      |
| position and has not been found.  MDE has conducted an initial investigation |
| and it appears that they may issue a press release.                          |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37361       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PEACH BOTTOM             REGION:  1  |NOTIFICATION DATE: 09/21/2000|
|    UNIT:  [2] [3] []                STATE:  PA |NOTIFICATION TIME: 16:07[EDT]|
|   RXTYPE: [2] GE-4,[3] GE-4                    |EVENT DATE:        09/21/2000|
+------------------------------------------------+EVENT TIME:        15:30[EDT]|
| NRC NOTIFIED BY:  JOHN POPIELARSKI             |LAST UPDATE DATE:  09/21/2000|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |WILLIAM RULAND       R1      |
|10 CFR SECTION:                                 |                             |
|AESS 50.72(b)(1)(v)      EMERGENCY SIREN INOP   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2     N          N       0        Cold Shutdown    |0        Cold Shutdown    |
|3     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE EMERGENCY SIRENS IN DEGRADED CONDITION                               |
|                                                                              |
| "On September 21, 2000 at 1530, it was identified that at least 17 of Peach  |
| Bottom's 97 Emergency Offsite Sirens were in a degraded condition. The exact |
| cause of the degraded sirens is not known at this time, but the ability of   |
| the licensee to detect the degraded sirens has been compromised due to poor  |
| maintenance practices. A plan is being developed and implemented to repair   |
| the degraded sirens and appropriate interim compensatory measures are being  |
| put in place to compensate for the degraded condition."                      |
|                                                                              |
| An investigation is underway into this matter.  The contractor responsible   |
| for the siren maintenance has no other responsibilities on site.             |
|                                                                              |
| The licensee has notified the NRC Resident Inspector.                        |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37362       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: RIVER BEND               REGION:  4  |NOTIFICATION DATE: 09/21/2000|
|    UNIT:  [1] [] []                 STATE:  LA |NOTIFICATION TIME: 16:15[EDT]|
|   RXTYPE: [1] GE-6                             |EVENT DATE:        09/21/2000|
+------------------------------------------------+EVENT TIME:        11:38[CDT]|
| NRC NOTIFIED BY:  DONALD CHASE                 |LAST UPDATE DATE:  09/21/2000|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |JEFF SHACKELFORD     R4      |
|10 CFR SECTION:                                 |                             |
|AINA 50.72(b)(2)(iii)(A) POT UNABLE TO SAFE SD  |                             |
|AINB 50.72(b)(2)(iii)(B) POT RHR INOP           |                             |
|AINC 50.72(b)(2)(iii)(C) POT UNCNTRL RAD REL    |                             |
|AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION    |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| POSSIBILITY THAT BOTH DIVISION 1 AND 2 DIESEL GENERATORS WERE INOPERABLE FOR |
| 9 HOURS                                                                      |
|                                                                              |
| "This condition deals with a past Reportability issue. During a condition    |
| report review for Functional Failure/Maintenance Preventable Functional      |
| Failure determination (FF/MPFF), River Bend has determined that both Standby |
| Diesel Generators may have been inoperable at the same time.                 |
|                                                                              |
| "A failure in a light socket related to the Division I Diesel Generator      |
| created a functional failure in that during a seismic event, the breaker     |
| logic for the Division I diesel generator output breaker could have been     |
| affected in such a way that the breaker would not close. The failed light    |
| socket was identified and corrected on 9/5/00 as part of work to replace the |
| light bulb. Since the MAI on the light bulb failure was written on 8/22/00,  |
| it is assumed that the socket failure occurred at that time.                 |
|                                                                              |
| "During the same time period, a lube oil leak developed on the Division II   |
| oil supply which has been determined to be a functional failure. The damaged |
| oil line was replaced on 8/30/00.                                            |
|                                                                              |
| "Therefore, based on the functional failure determinations, there is an      |
| overlapping period of approximately 9 hours that the Division I and II       |
| diesel generators may not have been capable of performing their design bases |
| function.                                                                    |
|                                                                              |
| "This report is being made based on the information available at this time.  |
| River Bend will continue to evaluate the condition associated with the       |
| potential Division I inoperability and will assess the reportability of this |
| condition further based on the results of that evaluation."                  |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37363       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SAN ONOFRE               REGION:  4  |NOTIFICATION DATE: 09/21/2000|
|    UNIT:  [] [2] [3]                STATE:  CA |NOTIFICATION TIME: 19:09[EDT]|
|   RXTYPE: [1] W-3-LP,[2] CE,[3] CE             |EVENT DATE:        09/19/2000|
+------------------------------------------------+EVENT TIME:        07:30[PDT]|
| NRC NOTIFIED BY:  CLAY WILLIAMS                |LAST UPDATE DATE:  09/21/2000|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |KRISS KENNEDY        R4      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(vi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|3     N          Y       100      Power Operation  |100      Power Operation  |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION DUE TO A SULFURIC ACID LEAK CONTAINED ON SITE           |
|                                                                              |
| "This 4-hour telephone notification is being provided in accordance with     |
| 10CFR50.72(b)(2)(vi) for notification of other government agencies. For the  |
| event below, on September 19, 2000, at 0920 PDT, SCE notified the Department |
| of Environmental Health and the Office of Emergency Services (OES Incident   |
| number 00-4232). This notification was delayed due to an internal            |
| miscommunication.                                                            |
|                                                                              |
| "On September 19, 2000, at about 0730 PDT, control room personnel were       |
| notified of a sulfuric acid leak from the High Flow Makeup Demineralizer     |
| Bulk Acid Storage Tank. The leak was from a gasket located between level     |
| transmitter 2/3LT5045 and isolation valve AST-38. The isolation valve was    |
| closed and the leak stopped. All acid (estimated to be about 650 gallons)    |
| was contained within the tank's bermed area and then routed to the waste     |
| neutralization sump. The entire sump contents (about 2,500 gallons of        |
| sulfuric acid and water) were removed for disposal off-site. This occurrence |
| was not a significant impact to the environment and did not hamper site      |
| personnel in the performance of their duties necessary for safe operation.   |
|                                                                              |
| "At the time of this occurrence, both Units 2 and 3 were operating at about  |
| 100 percent power; Unit 1 remains permanently defueled. SCE will notify the  |
| NRC resident inspectors about this notification and will provide them with a |
| copy of this report."                                                        |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37364       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: BRUNSWICK                REGION:  2  |NOTIFICATION DATE: 09/22/2000|
|    UNIT:  [] [2] []                 STATE:  NC |NOTIFICATION TIME: 04:26[EDT]|
|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        09/22/2000|
+------------------------------------------------+EVENT TIME:        04:00[EDT]|
| NRC NOTIFIED BY:  HAMM/SCHALL                  |LAST UPDATE DATE:  09/22/2000|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          UNU                   |THOMAS DECKER        R2      |
|10 CFR SECTION:                                 |BILL BATEMAN         NRR     |
|AAEC                                            |JOSEPH GIITTER       IRO     |
|                                                |LUIS REYES           R2      |
|                                                |HEYMAN               FEMA    |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     A/R        Y       100      Power Operation  |0        Hot Shutdown     |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| FIRE IN THE PROTECTED AREA LASTING GREATER THAN 10 MINUTES RESULTING IN A    |
| REACTOR SCRAM.                                                               |
|                                                                              |
| AN UNUSUAL EVENT WAS DECLARED @ 0400 DUE TO A FIRE IN THE MAIN TRANSFORMER   |
| THAT LASTED >10 MINUTES.  OFF SITE FIRE DEPARTMENT WAS CALLED IN TO RESPOND  |
| AND THE FIRE WAS EXTINGUISHED WITHIN 14 MINUTES, HOWEVER THE PLANT STILL     |
| REMAINS IN THE UNUSUAL EVENT.   A REACTOR SCRAM FROM 100% POWER OCCURRED     |
| FOLLOWING A MAIN TURBINE GENERATOR LOCKOUT WHICH RESULTED FROM THE           |
| TRANSFORMER FAILURE.  THERE WERE SOME ERRONEOUS INDICATIONS OF CONTROL ROD   |
| POSITION, BUT  ALL RODS APPEAR TO BE FULLY INSERTED.  THERE WAS NO ECCS      |
| ACTUATION AND NO SAFETY RELIEF VALVES LIFTED DURING THIS EVENT.  THE PLANT   |
| DID NOT LOSE OFFSITE POWER DUE TO THE AUTO TRANSFER FROM THE MAIN            |
| TRANSFORMER TO THE STARTUP AUXILIARY TRANSFORMER.  THE DIESELS AUTOMATICALLY |
| STARTED AND WERE STILL RUNNING AT THE TIME OF THIS REPORT.  GROUP 2,6 AND 8  |
| ISOLATIONS WERE ALSO RECEIVED.  THERE WAS A PROBLEM WITH THE STARTUP LEVEL   |
| CONTROL VALVE WHEN THEY REESTABLISHED REACTOR FEED PUMP, VALVE DID NOT OPEN  |
| PROPERLY SO THEY HAD TO USE THE BACKUP PATH IN THE FEED SYSTEM.   AS A       |
| RESULT OF THIS THE LEVEL WENT LOW ENOUGH TO RECEIVE A SECOND REACTOR SCRAM   |
| SIGNAL.  THE CONDENSER IS BEING USED AS THE HEAT SINK AND THE PLANT IS       |
| STABLE.  THE CAUSES FOR THE TRANSFORMER FIRE AND THE ERRONEOUS CONTROL ROD   |
| INDICATIONS ARE BEING INVESTIGATED.  THERE HAVE BEEN NO INJURIES REPORTED    |
| AND IT IS NOT KNOWN AT THIS TIME IF A PRESS RELEASE WILL BE ISSUED.          |
|                                                                              |
| THE NRC RESIDENT INSPECTOR WAS NOTIFIED.                                     |
|                                                                              |
| * * * UPDATE ON 9/22/00 @ 0528 BY HAMM TO GOULD * * *                        |
|                                                                              |
| THE NOUE WAS TERMINATED AT 0512 DUE TO THE FIRE BEING COMPLETELY             |
| EXTINGUISHED.                                                                |
| THE NRC RESIDENT INSPECTOR WILL BE NOTIFIED.                                 |
| THE EO(BATEMAN), RDO(DECKER), FEMA (HEYMAN)  AND IRO(GIITTER) WERE           |
| NOTIFIED.                                                                    |
|                                                                              |
| SEE EVENT # 37365.                                                           |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   37365       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: BRUNSWICK                REGION:  2  |NOTIFICATION DATE: 09/22/2000|
|    UNIT:  [] [2] []                 STATE:  NC |NOTIFICATION TIME: 06:37[EDT]|
|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        09/22/2000|
+------------------------------------------------+EVENT TIME:        03:40[EDT]|
| NRC NOTIFIED BY:  SCHALL                       |LAST UPDATE DATE:  09/22/2000|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |THOMAS DECKER        R2      |
|10 CFR SECTION:                                 |                             |
|AESF 50.72(b)(2)(ii)     ESF ACTUATION          |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     N          Y       100      Power Operation  |0        Hot Shutdown     |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| PLANT HAD ESF ACTUATIONS DURING A REACTOR SCRAM                              |
|                                                                              |
| A main turbine trip resulted in a reactor scram.  As expected following the  |
| scram, reactor water level dropped to the actuation setpoint for Groups 2, 6 |
| and 8 isolations. The main turbine trip apparently resulted from a fire in B |
| main power transformer.  The fire was reported to the control room at 0346.  |
| The site fire brigade responded and the fire was extinguished at 0402 using  |
| the automatic deluge system and fire hoses.  Offsite fire department         |
| assistance was requested but was not needed to extinguish the fire.   An     |
| Unusual Event was declared at 0400 in accordance with the plant's emergency  |
| procedures.  The Unusual Event was terminated at 0512 based on the plant     |
| being in a stable condition.   During the transient the startup level        |
| control did not control level in the automatic mode.   Reactor level was     |
| controlled using a feedwater bypass valve.   A second reactor scram signal   |
| was generated due a low reactor water level signal received while manual     |
| level control was being established, however all rods were already tully     |
| inserted.  The plant emergency diesels started but did not load. Offsite     |
| power remained available throughout the event.  The NRC Resident Inspector   |
| was notified.                                                                |
|                                                                              |
| HOO Note: see event # 37364                                                  |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Wednesday, March 24, 2021

Page Last Reviewed/Updated Wednesday, March 24, 2021