The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.
Event Notification Report for August 31, 2000
U.S. Nuclear Regulatory Commission
Operations Center
Event Reports For
08/30/2000 - 08/31/2000
** EVENT NUMBERS **
37273 37274 37275 37276 37277
+------------------------------------------------------------------------------+
|Other Nuclear Material |Event Number: 37273 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: U.S. ARMY |NOTIFICATION DATE: 08/30/2000|
|LICENSEE: U.S. ARMY |NOTIFICATION TIME: 10:01[EDT]|
| CITY: ROCK ISLAND REGION: 3 |EVENT DATE: 08/23/2000|
| COUNTY: STATE: IL |EVENT TIME: [CDT]|
|LICENSE#: 12-00722-06 AGREEMENT: Y |LAST UPDATE DATE: 08/30/2000|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |MELVYN LEACH R3 |
| |BRIAN SMITH NMSS |
+------------------------------------------------+CAUDLE JULIAN R2 |
| NRC NOTIFIED BY: JEFF HAVENNER | |
| HQ OPS OFFICER: FANGIE JONES | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|BAB2 20.2201(a)(1)(ii) LOST/STOLEN LNM>10X | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| MISSING M43A1 CHEMICAL AGENT DETECTOR |
| |
| The licensee reported that one M43A1 chemical agent detector, containing 250 |
| �Ci of Am-241, had been lost during a training exercise at Camp Shelby, |
| Mississippi. The Alabama National Guard was conducting a class, removed |
| the cell containing the chemical agent detector which apparently was not |
| replaced. This was discovered when the assembly was sent in for the |
| detector to be leak checked. An investigation has looked for the missing |
| detector and is still looking for it. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Other Nuclear Material |Event Number: 37274 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: QSL INSPECTION |NOTIFICATION DATE: 08/30/2000|
|LICENSEE: QSL INSPECTION |NOTIFICATION TIME: 11:30[EDT]|
| CITY: TRAINER REGION: 1 |EVENT DATE: 08/29/2000|
| COUNTY: DELAWARE STATE: PA |EVENT TIME: 14:00[EDT]|
|LICENSE#: 37-28085-01 AGREEMENT: N |LAST UPDATE DATE: 08/30/2000|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |PETE ESELGROTH R1 |
| |BRIAN SMITH NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: LANGE | |
| HQ OPS OFFICER: JOHN MacKINNON | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|IBBF 30.50(b)(2)(ii) EQUIP DISABLED/FAILS | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| 30 CURIE IRIDIUM-192 SOURCE'S PIG TAIL DISCONNECTED FROM ITS DRIVE CABLE. |
| |
| Event was reported by the Radiation Safety Officer for QSL Inspection. |
| |
| Disconnect of a Sentinel Amersham 660 exposure device occurred in Bensalem, |
| Pa., yesterday afternoon. After completing an exposure it was discovered |
| that the source had become disconnected from its drive cable and it could |
| not be retracted back to its storage position. The pig tail had become |
| disconnected from the drive cable. The licensee shielded the source and |
| retrieved it. Maximum reading of the radiographers pocket dosimetry devices |
| was 130 mRem (the radiographers actual exposure in retrieving the 30 curie |
| Ir-192 source was less than 130 mRem because he had been wearing the same |
| pocket dosimetry devices during other radiography shots) . On |
| investigation the licensee found that the drive cable selector ring was worn |
| (connects the drive cable to the pig tail). The licensee has taken all of |
| their 30 exposure controls and 27 devices out of service and is inspecting |
| them for any problems. The licensee notified NRC Region 1, John Kinneman, |
| of this event. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|General Information or Other |Event Number: 37275 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: EATON CUTLER-HAMMER |NOTIFICATION DATE: 08/30/2000|
|LICENSEE: EATON CUTLER-HAMMER |NOTIFICATION TIME: 15:06[EDT]|
| CITY: WARRENDALE REGION: 1 |EVENT DATE: 07/31/2000|
| COUNTY: STATE: PA |EVENT TIME: [EDT]|
|LICENSE#: AGREEMENT: N |LAST UPDATE DATE: 08/30/2000|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |PETE ESELGROTH R1 |
| |CAUDLE JULIAN R2 |
+------------------------------------------------+MELVYN LEACH R3 |
| NRC NOTIFIED BY: LAURENCE PATTERSON |CHUCK PAULK R4 |
| HQ OPS OFFICER: LEIGH TROCINE |VERN HODGE (via fax) NRR |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|CCCC 21.21 UNSPECIFIED PARAGRAPH | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| 10 CFR PART 21 NOTIFICATION REGARDING THE POTENTIAL FAILURE OF |
| EATON-CUTLER-HAMMER DS-206 CIRCUIT BREAKERS TO CLOSE ON DEMAND |
| |
| The following text is a portion of a facsimile received from Eaton |
| Cutler-Hammer Nuclear Programs personnel: |
| |
| "The following information is provided pursuant to the requirements of 10 |
| CFR Part 21 to report a potential safety concern. This issue concerns the |
| possibility for malfunction of the Eaton Cutler-Hammer DS-206 circuit |
| breakers due to 'shock-out' of Direct Trip Actuators (DTA). Shock-out is |
| defined as the unwarranted or undesired change in the state of a DTA from |
| the normally un-tripped state to a tripped state. Shock-out occurs as a |
| result of shock caused by the circuit breaker cycling from the open position |
| to the closed position. The shock force is supplied by the closing springs |
| striking the bottom plate of the breaker frame during the breaker closing |
| operation. The result of shock-out is that the DTA trips immediately, |
| returning the breaker to an open condition, which is neither required nor |
| desired." |
| |
| "[Eaton Cutler-Hammer Nuclear Programs (C-HNP)] has determined that the root |
| cause of DTA shock-out in DS-206 breakers is the replacement of operating |
| mechanisms and/or closing springs with new operating mechanisms and/or new |
| closing springs, as part of the standard reconditioning process. DTA |
| shock-out has not been observed in vintage DS-206 breakers that are |
| reconditioned in accordance with C-HNP procedures, which does not include |
| the replacement of operating mechanisms and/or closing springs as part of |
| the standard reconditioning process. The standard C-HNP reconditioning |
| process DOES include installation of design upgrades." |
| |
| "To eliminate the possibility of shock-out, when the DS-206 breaker |
| reconditioning process includes installation of a new operating mechanism |
| and/or closing springs, C-HNP recommends the installation of a modified |
| bottom plate to eliminate transmission of shock to the DTA. A modified |
| bottom plate has been designed, [and] tested and is being seismically |
| qualified by C-HNP." |
| |
| "This deficiency was identified and determined to be of a chronic reportable |
| nature on approximately July 31, 2000." |
| |
| "The installed base of the C-HNP supplied operating mechanisms and closing |
| springs is limited to a single utility and plant, Tennessee Valley Authority |
| Sequoyah Nuclear Plant. C-HNP does not know where operating mechanisms and |
| closing springs, procured commercially by third party dedicators, may have |
| been installed in safety-related applications." |
| |
| (Contact the NRC operations officer for supplier contact information.) |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37276 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: MONTICELLO REGION: 3 |NOTIFICATION DATE: 08/30/2000|
| UNIT: [1] [] [] STATE: MN |NOTIFICATION TIME: 17:18[EDT]|
| RXTYPE: [1] GE-3 |EVENT DATE: 08/30/2000|
+------------------------------------------------+EVENT TIME: 15:05[CDT]|
| NRC NOTIFIED BY: KEVIN PEDERSON |LAST UPDATE DATE: 08/30/2000|
| HQ OPS OFFICER: LEIGH TROCINE +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |MELVYN LEACH R3 |
|10 CFR SECTION: | |
|ADAS 50.72(b)(2)(i) DEG/UNANALYZED COND | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N N 0 Cold Shutdown |0 Cold Shutdown |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| FAILURE OF A MAIN STEAM LINE DRAIN PRIMARY CONTAINMENT ISOLATION VALVE TO |
| COMPLETELY OPEN DUE TO LOOSE TORQUE SWITCH WIRE CONNECTIONS |
| |
| The following text is a portion of a facsimile received from the licensee: |
| |
| "During plant shutdown, primary containment isolation valve MO-2373 failed |
| to properly function. The failure was caused by loose torque switch wire |
| connections which caused a failure of the valve to completely open. |
| Improper electrical connections could have prevented full closure of the |
| valve. Therefore, the valve was determined to be inoperable prior to the |
| repair. ([The] valve has been repaired.) The safety function of the |
| redundant primary containment isolation valve was available." |
| |
| The licensee plans to notify the NRC resident inspector. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Fuel Cycle Facility |Event Number: 37277 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PADUCAH GASEOUS DIFFUSION PLANT |NOTIFICATION DATE: 08/31/2000|
| RXTYPE: URANIUM ENRICHMENT FACILITY |NOTIFICATION TIME: 05:30[EDT]|
| COMMENTS: 2 DEMOCRACY CENTER |EVENT DATE: 08/30/2000|
| 6903 ROCKLEDGE DRIVE |EVENT TIME: 16:10[CDT]|
| BETHESDA, MD 20817 (301)564-3200 |LAST UPDATE DATE: 08/31/2000|
| CITY: PADUCAH REGION: 3 +-----------------------------+
| COUNTY: McCRACKEN STATE: KY |PERSON ORGANIZATION |
|LICENSE#: GDP-1 AGREEMENT: Y |MELVYN LEACH R3 |
| DOCKET: 0707001 |BRIAN SMITH NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: - | |
| HQ OPS OFFICER: STEVE SANDIN | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|OCBA 76.120(c)(2)(i) ACCID MT EQUIP FAILS | |
|OCBB 76.120(c)(2)(ii) EQUIP DISABLED/FAILS | |
|OCBC 76.120(c)(2)(iii) REDUNDANT EQUIP INOP | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| AREA CONTROL ROOM (ACR) ALARM POWER LOST DUE TO A FAILURE IN THE POWER |
| TRANSFER SWITCH |
| |
| "At 1610 on 08-30-00 the PSS was informed of a C-331 CAAS Cluster J Trouble |
| alarm. Investigation of trouble alarm revealed that C-331 CAAS Horns |
| solenoids had lost DC power. The C-331 ACR DC alarm power was lost due to |
| the failures in the power transfer switch. Contacts fused together and a |
| solenoid failed which allowed the transfer switch to reposition to the mid |
| (no power) position and prevented repositioning to the emergency power |
| position. Since the CAAS horns did not have power, they were unable to |
| perform the intended safety function, rendering the system inoperable for |
| audibility. The system is required to be operable according to TSR 2.4.4.7.b |
| for the current mode of operation. The horns were without power (inoperable) |
| for approximately 30 minutes until the transfer switch was physically forced |
| to the emergency power position. |
| |
| This event is reportable under 10 CFR 76.120(c)(2) as an event in which |
| equipment required by the TSR is disabled or fails to function as designed. |
| |
| The NRC Resident Inspector has been notified of this event. |
+------------------------------------------------------------------------------+
Page Last Reviewed/Updated Wednesday, March 24, 2021
Page Last Reviewed/Updated Wednesday, March 24, 2021