The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.
Event Notification Report for August 23, 2000
U.S. Nuclear Regulatory Commission
Operations Center
Event Reports For
08/22/2000 - 08/23/2000
** EVENT NUMBERS **
37245 37246 37247 37248
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37245 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: FITZPATRICK REGION: 1 |NOTIFICATION DATE: 08/21/2000|
| UNIT: [1] [] [] STATE: NY |NOTIFICATION TIME: 19:33[EDT]|
| RXTYPE: [1] GE-4 |EVENT DATE: 08/21/2000|
+------------------------------------------------+EVENT TIME: 18:00[EDT]|
| NRC NOTIFIED BY: KERRY ALLEN |LAST UPDATE DATE: 08/22/2000|
| HQ OPS OFFICER: DICK JOLLIFFE +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |CHRISTOPHER CAHILL R1 |
|10 CFR SECTION: | |
|APRE 50.72(b)(2)(vi) OFFSITE NOTIFICATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION REGARDING OIL SPILL ONSITE |
| |
| "Oil was discovered covering the gravel over an approximate 1 meter diameter |
| area. The area was located under vent pipe for the main turbine generator |
| air detraining tank on the turbine building roof." |
| |
| The NRC resident inspector will be notified by the licensee. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Other Nuclear Material |Event Number: 37246 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: WA DIVISION OF RADIATION PROTECTION |NOTIFICATION DATE: 08/22/2000|
|LICENSEE: COLUMBIA ASPHALT & GRAVEL |NOTIFICATION TIME: 15:10[EDT]|
| CITY: YAKIMA REGION: 4 |EVENT DATE: 08/19/2000|
| COUNTY: STATE: WA |EVENT TIME: [PDT]|
|LICENSE#: WN-10440-1 AGREEMENT: Y |LAST UPDATE DATE: 08/22/2000|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |WILLIAM JOHNSON R4 |
| |JOSEPHINE PICCONE NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: TERRY FRAZEE | |
| HQ OPS OFFICER: DICK JOLLIFFE | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|NAGR AGREEMENT STATE | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT: LOST PORTABLE MOISTURE DENSITY GAUGE |
| |
| This notification of an event in Washington state as reported to the WA |
| Department of Health, Division of Radiation Protection. (WA Event Report |
| #WA-00-039) Date of event: August 19, 2000 |
| |
| Licensee: Columbia Asphalt & Gravel |
| City and state: Yakima, WA |
| License number: WN-10440-1 |
| Type of license: Portable Gauge |
| Location of Event: Toppenish, WA |
| |
| ABSTRACT: Tired and exhausted after a 60 hour work week, the gauge operator |
| packed up and headed for home. The next morning when he went out to his |
| van, parked in a secured lot, he discovered that the van was unlocked and |
| the gauge transport box was open. The Campbell Pacific Model MC3 was |
| missing. He called the police to report it stolen and called the Division's |
| emergency number. The Division provided him instructions on issuing a press |
| release and suggested offering a reward. The gauge operator also drove back |
| to the job site to double check that he had not inadvertently left the gauge |
| behind. No one was working at the site on August 20, 2000, and he did not |
| find the gauge. |
| |
| On Monday, August 21, 2000, the gauge operator reported that the gauge had |
| been returned to him by the "flaggers". One of the employees of the traffic |
| control contractor at the site was familiar with portable gauges and |
| realized that the gauge operator had inadvertently drove off without the |
| gauge at the end of work on Saturday. The flagger secured the gauge and |
| notified the gauge operator immediately at the start of the next workday. |
| The gauge was returned safely and this case is closed for purposes of |
| reporting to NRC. |
| |
| What is the notification or reporting criteria involved? WAC 246-221-240 |
| Activity and isotope(s) involved: 10 millicuries Cs-137; 50 millicuries |
| Am-24 1/Be |
| Lost, Stolen or Damaged? Campbell Pacific, Model MC3, S/N M370803865 |
| Disposition/recovery: Recovered Status: Closed |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|General Information or Other |Event Number: 37247 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: MIDWEST INSPECTION SERVICES |NOTIFICATION DATE: 08/22/2000|
|LICENSEE: MIDWEST INSPECTION SERVICES |NOTIFICATION TIME: 17:30[EDT]|
| CITY: OAK CITY REGION: 4 |EVENT DATE: 08/22/2000|
| COUNTY: STATE: OK |EVENT TIME: 15:00[CDT]|
|LICENSE#: 35-27005-01 AGREEMENT: N |LAST UPDATE DATE: 08/22/2000|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |WILLIAM JOHNSON R4 |
| |JOSEPHINE PICCONE NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: DENNIS EZZELL | |
| HQ OPS OFFICER: DICK JOLLIFFE | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|BAD1 20.2202(a)(1) PERS OVEREXPOSURE | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| - FILM BADGE WITH HIGH READING FOR JULY, 2000 MAY HAVE BEEN TAMPERED WITH - |
| |
| On 07/24/00, an employee resigned from Midwest Inspection Services, Oak |
| City, OK. The individual's film badge for the month of July, 2000, was sent |
| to Landauer Company for processing. At 1500 CDT on 08/22/00, Landauer |
| reported to Midwest Inspection Services that the badge read 710 Rem for the |
| month of July, 2000. |
| |
| Mr Ezzell, Midwest Inspection Services, feels that the film badge reading is |
| incorrect and that the badge may have been tampered with possibly by a |
| disgruntled employee who also resigned from Midwest Inspection Services in |
| July, 2000. Blood samples of the first individual will be taken on 08/23/00 |
| and his red and white blood cells will be counted. |
| |
| Mr Ezzell notified NRC Region 4 Mark Shaffer and plans to continue to |
| investigate this incident. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 37248 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: DUANE ARNOLD REGION: 3 |NOTIFICATION DATE: 08/23/2000|
| UNIT: [1] [] [] STATE: IA |NOTIFICATION TIME: 05:14[EDT]|
| RXTYPE: [1] GE-4 |EVENT DATE: 08/23/2000|
+------------------------------------------------+EVENT TIME: 02:30[CDT]|
| NRC NOTIFIED BY: MIKE HAUNER |LAST UPDATE DATE: 08/23/2000|
| HQ OPS OFFICER: JOHN MacKINNON +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |PATRICK HILAND R3 |
|10 CFR SECTION: | |
|AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| BOTH RIVER WATER SUPPLY SYSTEMS WERE DECLARED INOPERABLE. |
| |
| At 0230 the River Water Supply (RWS) instrument air system failed resulting |
| in an invalid low RWS pit level alarm. Operators restored system air |
| pressure at 0243. The loss of instrument air pressure also resulted in the |
| loss of automatic traveling screen control and the screen high differential |
| level alarm function. Because both of the automatic traveling screen wash |
| systems were inoperable, both RWS systems were declared inoperable for the |
| 13 minute duration. Failure of both systems resulted in a loss of safety |
| function (supplies water to the Residual Heat Removal Service Water Pumps |
| and the Emergency Service Water System). The licensee entered the applicable |
| Technical Specifications for the loss of the RWS system. A new air dryer |
| was installed recently and when the operator cycled the power supply to the |
| air dryer it hung up. This caused the Instrument Air blockage. |
| |
| The NRC Resident Inspector was notified of this event by the licensee. |
+------------------------------------------------------------------------------+
Page Last Reviewed/Updated Thursday, March 25, 2021
Page Last Reviewed/Updated Thursday, March 25, 2021