The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.
Event Notification Report for March 10, 2000
U.S. Nuclear Regulatory Commission
Operations Center
Event Reports For
03/09/2000 - 03/10/2000
** EVENT NUMBERS **
36776 36777 36778 36779 36780 36781 36782
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 36776 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: OCONEE REGION: 2 |NOTIFICATION DATE: 03/09/2000|
| UNIT: [1] [2] [3] STATE: SC |NOTIFICATION TIME: 11:16[EST]|
| RXTYPE: [1] B&W-L-LP,[2] B&W-L-LP,[3] B&W-L-L|EVENT DATE: 03/09/2000|
+------------------------------------------------+EVENT TIME: 10:35[EST]|
| NRC NOTIFIED BY: MICHAEL HILL |LAST UPDATE DATE: 03/09/2000|
| HQ OPS OFFICER: DOUG WEAVER +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |EDWARD MCALPINE R2 |
|10 CFR SECTION: | |
|ASHU 50.72(b)(1)(i)(A) PLANT S/D REQD BY TS | |
|NLCO TECH SPEC LCO A/S | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
|2 N Y 100 Power Operation |100 Power Operation |
|3 N Y 100 Power Operation |100 Power Operation |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| TECH SPEC REQUIRED SHUTDOWN - LOSS OF CONTROL ROOM AIR CONDITIONING |
| |
| The licensee has two control room chillers. The 'A' chiller tripped because |
| of low freon. The 'B' chiller was started and then tripped on two |
| occasions. Based on the unreliability of the 'B' chiller, the licensee |
| considered both chillers inoperable and entered Tech Spec 3.0.3 as a result. |
| The licensee will start reducing power of all three units at 1 percent per |
| hour at 1130. However they expect that they will have one chiller back in |
| service prior to reaching the 2235, the time the units need to be in mode |
| 3. |
| |
| The licensee notified the NRC resident inspector. |
| |
| * * * UPDATE ON 3/9/00 @ 1329 BY CLARKSON TO GOULD * * * |
| |
| Actions were undertaken to restore the 'B' Chilled water train to operable |
| status. At 1246 hours, on March 9, 2000, the 'B' Chilled Water train was |
| returned to operable status and Technical Specifications 3.0.3 and 3.7.16, |
| Condition E were exited. The shutdown of all three Oconee units was also |
| halted at approximately 98% power and the units are being returned to 100%. |
| |
| The NRC Resident Inspector was informed. |
| |
| The Reg 2 RDO (McAlpine) was notified. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|General Information or Other |Event Number: 36777 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: INSPECTION SERVICES COMPANY |NOTIFICATION DATE: 03/09/2000|
|LICENSEE: INSPECTION SERVICES COMPANY |NOTIFICATION TIME: 11:40[EST]|
| CITY: PLYMOUTH REGION: 3 |EVENT DATE: 03/09/2000|
| COUNTY: STATE: MI |EVENT TIME: 10:30[EST]|
|LICENSE#: 21-26744-01 AGREEMENT: N |LAST UPDATE DATE: 03/09/2000|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |ROGER LANKSBURY R3 |
| |JOHN HICKEY NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: KRUZEL | |
| HQ OPS OFFICER: CHAUNCEY GOULD | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|BAB1 20.2201(a)(1)(i) LOST/STOLEN LNM>1000X | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| STOLEN MOISTURE DENSITY GAUGE |
| |
| INSPECTION SERVICES CO. REPORTED THAT A HUMBOLDT MOISTURE DENSITY GAUGE |
| MODEL 5001 SERIAL # 2996 WAS STOLEN FROM THEIR PICKUP TRUCK WHILE IT WAS |
| PARKED IN THEIR FACILITY PARKING LOT IN PLYMOUTH, MI. THE GAUGE WAS BOLTED |
| TO THE TRUCK AT THE TIME OF THE THEFT. THE DEVICE CONTAINED 8 MILLICURIES |
| OF Cs-137 AND 40 MILLICURIES OF Am-241. THE LOCAL POLICE WERE NOTIFIED. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|General Information or Other |Event Number: 36778 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: PUBLIC SERVICE ELECTRIC AND GAS CO. |NOTIFICATION DATE: 03/09/2000|
|LICENSEE: BFGOODRICH COMPANY |NOTIFICATION TIME: 12:15[EST]|
| CITY: HANCOCK'S BRIDGE REGION: 1 |EVENT DATE: 03/09/2000|
| COUNTY: STATE: NJ |EVENT TIME: [EST]|
|LICENSE#: AGREEMENT: N |LAST UPDATE DATE: 03/09/2000|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |GREG CRANSTON R1 |
| |VERN HODGE (via fax) NRR |
+------------------------------------------------+ |
| NRC NOTIFIED BY: SUE SIMPSON | |
| HQ OPS OFFICER: BOB STRANSKY | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|CCCC 21.21 UNSPECIFIED PARAGRAPH | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| 10 CFR PART 21 REPORT |
| |
| Replacement emergency diesel generator (EDG) air start motors were supplied |
| to PSE&G with grease on the bendix drive shafts. This did not meet the |
| requirements of the purchase order which stated: "Do not grease the bendix |
| drive: as per the vendor manual this is to be lubricated with SAE 10 oil." |
| Excessive grease on the bendix shaft could harden and prevent the drive |
| pinion from engaging the ring gear on the EDG flywheel during starting. |
| |
| The air start motors were supplied by: |
| |
| BFGoodrich Company (formerly Coltec Industries) |
| Fairbanks Morse Engine Division |
| 701 White Avenue |
| Beloit, WI 53511 |
| |
| Affected FMED Part #s: 21800136-1, 21800145, 21800146 and 21800147 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 36779 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: FT CALHOUN REGION: 4 |NOTIFICATION DATE: 03/09/2000|
| UNIT: [1] [] [] STATE: NE |NOTIFICATION TIME: 12:42[EST]|
| RXTYPE: [1] CE |EVENT DATE: 03/09/2000|
+------------------------------------------------+EVENT TIME: 10:54[CST]|
| NRC NOTIFIED BY: ERICK MATZKE |LAST UPDATE DATE: 03/09/2000|
| HQ OPS OFFICER: BOB STRANSKY +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |KRISS KENNEDY R4 |
|10 CFR SECTION: | |
|AOUT 50.72(b)(1)(ii)(B) OUTSIDE DESIGN BASIS | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| CONTROL ROOM DOSE RATE EXCEEDS STANDARD REVIEW PLAN LIMIT |
| |
| "The Fort Calhoun Station is in the process of revising and reanalyzing the |
| radiological consequences analysis for the plant as a result of corrective |
| actions for LERs 1998-012 and 1998-013. In the process it has been |
| determined that some of the assumptions made when the plant was constructed |
| in the early 1970s, about 30 years ago, need to be validated. An important |
| assumption that was brought into question was that the Control Room has zero |
| (0) standard cubic feet per minute (SCFM) unfiltered inleakage. The control |
| room envelope was recently tested and the unfiltered inleakage was |
| determined to be very small at 8 SCFM. This level of leakage leads to a |
| thyroid dose to the operators of about 32 rem. The Fort Calhoun Station USAR |
| commits the station to NRC Standard Review Plan (SRP) section 6.4 which |
| states that the thyroid dose to the operators shall be no higher than 30 |
| rem. Higher thyroid doses have been approved for other plants and the dose |
| projected certainly would not incapacitate an operator. The calculated dose |
| is in excess of the current plant design basis. |
| |
| "Plant actions to date have included putting in place an Safety Analysis for |
| Operability (SAO) (similar to a Justification for Continued Operation [JCO]) |
| to allow the plant to continue operating in this condition. The plant has |
| been in communication with the NRC staff on the progress of this |
| radiological consequences reanalysis." |
| |
| The NRC resident inspector has been informed of this report by the licensee. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 36780 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SAINT LUCIE REGION: 2 |NOTIFICATION DATE: 03/09/2000|
| UNIT: [1] [2] [] STATE: FL |NOTIFICATION TIME: 14:54[EST]|
| RXTYPE: [1] CE,[2] CE |EVENT DATE: 03/09/2000|
+------------------------------------------------+EVENT TIME: 13:47[EST]|
| NRC NOTIFIED BY: CALVIN WARD |LAST UPDATE DATE: 03/09/2000|
| HQ OPS OFFICER: BOB STRANSKY +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |EDWARD MCALPINE R2 |
|10 CFR SECTION: | |
|AOUT 50.72(b)(1)(ii)(B) OUTSIDE DESIGN BASIS | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
|2 N Y 100 Power Operation |100 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| UNITS OUTSIDE OF DESIGN BASIS DUE TO 10 CFR PART 50, APPENDIX R ISSUE |
| |
| Following is the abstract of an engineering document submitted to the NRC |
| Operations Center: |
| |
| "As part of the continuing resolution of fire protection program issues |
| identified during a Follow-up Fire Protection Functional Inspection at St. |
| Lucie in December 1999, a detailed review of Appendix R circuit separation |
| and protection for the Units 1 & 2 containment was performed. This review |
| considered the design and licensing basis for these features as described in |
| the Unit 1 & 2 Updated Final Safety Analysis Reports (UFSARs), associated |
| NRC Safety Evaluation Reports (SERs), Appendix R requirements and guidance |
| provided in Generic Letter 86-10. The review has identified a number of |
| separation issues for various safe shutdown circuits and/or components |
| credited for post-fire safe shutdown operations following a fire in |
| containment. The affected equipment is hi/lo pressure interface equipment |
| along with control and indication equipment associated with the reactor |
| coolant system." |
| |
| The discrepancies noted in the report affect the power operated relief |
| valves (PORVs), as well as pressurizer pressure and level instrumentation. |
| The licensee has determined that the conditions do not affect operability of |
| the affected equipment due to the low combustible material loading inside |
| the containment and the low probability that a fire would occur inside the |
| containment. The NRC resident inspector has been informed of this report by |
| the licensee. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 36781 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: DIABLO CANYON REGION: 4 |NOTIFICATION DATE: 03/09/2000|
| UNIT: [1] [] [] STATE: CA |NOTIFICATION TIME: 14:56[EST]|
| RXTYPE: [1] W-4-LP,[2] W-4-LP |EVENT DATE: 03/09/2000|
+------------------------------------------------+EVENT TIME: 09:18[PST]|
| NRC NOTIFIED BY: CHITWOOD |LAST UPDATE DATE: 03/09/2000|
| HQ OPS OFFICER: BOB STRANSKY +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |KRISS KENNEDY R4 |
|10 CFR SECTION: | |
|AESF 50.72(b)(2)(ii) ESF ACTUATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| CONTROL ROOM VENTILATION PLACED IN PRESSURIZATION MODE DUE TO SMOKE |
| |
| At 0906 PST, rod drive motor/generator set 1-2 tripped due to overcurrent. |
| Heavy smoke from burnt insulation was observed in the vicinity. In order to |
| prevent the smoke from entering the control room, the shift foreman directed |
| operators to manually place the control room ventilation system in |
| pressurization mode (mode 4). |
| |
| The NRC resident inspector will be informed of this report by the licensee. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Fuel Cycle Facility |Event Number: 36782 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PORTSMOUTH GASEOUS DIFFUSION PLANT |NOTIFICATION DATE: 03/09/2000|
| RXTYPE: URANIUM ENRICHMENT FACILITY |NOTIFICATION TIME: 17:04[EST]|
| COMMENTS: 2 DEMOCRACY CENTER |EVENT DATE: 03/09/2000|
| 6903 ROCKLEDGE DRIVE |EVENT TIME: 03:32[EST]|
| BETHESDA, MD 20817 (301)564-3200 |LAST UPDATE DATE: 03/09/2000|
| CITY: PIKETON REGION: 3 +-----------------------------+
| COUNTY: PIKE STATE: OH |PERSON ORGANIZATION |
|LICENSE#: GDP-2 AGREEMENT: N |ROGER LANKSBURY R3 |
| DOCKET: 0707002 |THOMAS ESSIG NMSS |
+------------------------------------------------+ |
| NRC NOTIFIED BY: JEFF CASTLE | |
| HQ OPS OFFICER: BOB STRANSKY | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|NBNL RESPONSE-BULLETIN | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| 24-HOUR NRC BULLETIN 91-01 REPORT |
| |
| "At 0332 hours on 03/09/2000, it was identified that an error had been made |
| in connecting a cell calibration test buggy, covered by NCSA-PLANT069, at |
| X-330 building cell 31-3-9. The cell was connected to the HI DAT (HI DATUM) |
| port instead of the PROCESS inlet port. The NCSA identifies installed |
| chemical traps on the test buggy as a passive design characteristic relied |
| upon to prevent an accumulation of uranium in the vacuum pump oil. The |
| installed traps are also a control contingency in preventing back flow of |
| vacuum pump oil to the cell manifold. Connection of the process system to |
| the HI DAT port bypassed these chemical traps and provided a direct flow |
| path between the process gas system and vacuum pump. |
| |
| "Establishing a connection between the vacuum pump and cell process gas |
| manifold constitutes a loss of one control of the double contingency control |
| principle. The cell calibration buggy was disconnected and it was determined |
| that no oil from the vacuum pump had migrated through the buggy to the cell |
| manifold. The potential for a criticality to occur is precluded based on the |
| amount of oil contained in the vacuum pump and by the assay of the material |
| at that point of the cascade. Pull compliance with NCSA-PLANT069 was |
| regained when the calibration buggy was disconnected from the cell |
| manifold. |
| |
| "There was no loss of hazardous/radioactive material or |
| radioactive/radiological contamination exposure as a result of this event. |
| |
| "SAFETY SIGNIFICANCE OF EVENTS: |
| |
| "This event has a low safety significance. Due to operator error, the cell |
| was connected to the wrong inlet port This allowed the possibility that |
| process gas could bypass the chemical trap(s) and then collect in the oil |
| reservoir of the vacuum pump. The oil reservoir (limited to <= one quart) is |
| sized such that it is safe for 100% enriched material. The process gas that |
| may have entered the oil reservoir of the pump is approximately 2.25% |
| enriched. There is insufficient oil In the vacuum pump for a criticality to |
| occur. Additionally the test buggy has been disconnected from the cell. |
| Thus, there is no possibility of adding additional uranium to the oil |
| reservoir of the vacuum pump. |
| |
| "POTENTIAL CRITICALITY PATHWAYS INVOLVED (BRIEF SCENARIO(S) OF HOW |
| CRITICALITY COULD OCCUR): |
| |
| "For a criticality to occur, sufficient UF6 would need to collect in the oil |
| reservoir of the vacuum pump and the vacuum pump would need to be replaced |
| with a different model such that the oil reservoir is large enough (greater |
| than 3 quarts) for a criticality to occur. |
| |
| "CONTROLLED PARAMETERS (MASS, MODERATION, GEOMETRY, CONCENTRATION, ETC.): |
| |
| "This NCSA relied on preventing the accumulation of process gas from |
| collecting in the vacuum pump oil by placing a chemical trap upstream of the |
| vacuum pump. This control was lost. The second control was to limit the |
| amount of oil in the vacuum pump to less than 1 quart, which is less than |
| the minimum volume of oil required for a criticality at 100% U235. |
| |
| "ESTIMATED AMOUNT, ENRICHMENT, FORM OF LICENSED MATERIAL (INCLUDE PROCESS |
| LIMIT AND % WORST CASE OF CRITICAL MASS): |
| |
| "At this time it is not known if any UF6 reached the oil reservoir for the |
| vacuum pump. Enrichment in cell 31-3-9 is estimated to be 2.25% U-235. If |
| process gas reached the oil reservoir, it would be in the form of UF4/oil |
| mixture. |
| |
| "NUCLEAR CRITICALITY SAFETY CONTROL(S) OR CONTROL SYSTEM(S) AND DESCRIPTION |
| OF THE FAILURES OR DEFICIENCIES |
| |
| "Nuclear criticality safety is maintained by two controls, the first Is the |
| placement of chemical traps upstream of the vacuum pump. This control was |
| lost. The second control was on the allowed volume of oil in the reservoir |
| of the vacuum pump. This control was maintained throughout the event. Thus, |
| one control relied on for double contingency was lost." |
| |
| The NRC resident inspector has been informed of this notification. |
+------------------------------------------------------------------------------+
Page Last Reviewed/Updated Thursday, March 25, 2021
Page Last Reviewed/Updated Thursday, March 25, 2021