The U.S. Nuclear Regulatory Commission is in the process of rescinding or revising guidance and policies posted on this webpage in accordance with Executive Order 14151 Ending Radical and Wasteful Government DEI Programs and Preferencing, and Executive Order 14168 Defending Women From Gender Ideology Extremism and Restoring Biological Truth to the Federal Government. In the interim, any previously issued diversity, equity, inclusion, or gender-related guidance on this webpage should be considered rescinded that is inconsistent with these Executive Orders.

Event Notification Report for November 3, 1999

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           11/02/1999 - 11/03/1999

                              ** EVENT NUMBERS **

35790  36385  36386  36387  36388  36389  

+------------------------------------------------------------------------------+
|Fuel Cycle Facility                              |Event Number:   35790       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PADUCAH GASEOUS DIFFUSION PLANT      |NOTIFICATION DATE: 06/03/1999|
|   RXTYPE: URANIUM ENRICHMENT FACILITY          |NOTIFICATION TIME: 14:44[EDT]|
| COMMENTS: 2 DEMOCRACY CENTER                   |EVENT DATE:        06/02/1999|
|           6903 ROCKLEDGE DRIVE                 |EVENT TIME:        16:30[CDT]|
|           BETHESDA, MD 20817    (301)564-3200  |LAST UPDATE DATE:  11/02/1999|
|    CITY:  PADUCAH                  REGION:  3  +-----------------------------+
|  COUNTY:  McCRACKEN                 STATE:  KY |PERSON          ORGANIZATION |
|LICENSE#:  GDP-1                 AGREEMENT:  Y  |DAVID HILLS          R3      |
|  DOCKET:  0707001                              |DON COOL             NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  THOMAS WHITE                 |                             |
|  HQ OPS OFFICER:  FANGIE JONES                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|OCBA 76.120(c)(2)(i)     ACCID MT EQUIP FAILS   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| THREE SPRINKLER SYSTEMS DECLARED INOPERABLE DUE TO CORRODED HEADS (24-hour   |
| report)                                                                      |
|                                                                              |
| "On 06/02/99 at 1630 CDT, the Plant Shift Superintendent (PSS) was notified  |
| that numerous sprinkler heads were corroded, affecting 16 sprinkler systems  |
| in C-337 and one system in C-333, such that the ability of the sprinklers to |
| flow sufficient water was called into question.  Subsequently, these         |
| sprinkler systems were declared inoperable, and TSR-required actions         |
| establishing roving fire patrols were initiated.  This deficiency was        |
| detected during scheduled system inspections conducted by Fire Protection    |
| personnel.  Currently, functionality of the sprinkler heads has not been     |
| fully evaluated by Fire Protection personnel, and the remaining cascade      |
| buildings are currently being inspected, and if necessary, this report will  |
| be updated to identify any additional areas.  It has been determined that    |
| this event is reportable under 10CFR76.120(c)(2) as an event in which        |
| equipment is disabled or fails to function as designed."  The NRC resident   |
| inspector has been notified of this event.                                   |
|                                                                              |
| * * * UPDATE AT 1022 EDT ON 06/04/99 FROM CAGE TO TROCINE * * *              |
|                                                                              |
| "Two sprinkler heads on system D-1 in C-337 and two sprinkler heads on       |
| system 27 in C-335 were identified to also be corroded.  These were          |
| identified to the PSS on 06/03/99 at 1600 CDT and 1601 CDT, respectively,    |
| and determined to require an update to this report by the PSS.  It has been  |
| determined that this event is reportable under 10CFR76.120(c)(2) as an event |
| in which equipment is disabled or fails to function as designed."  Paducah   |
| personnel notified the NRC resident inspector of this update.  The NRC       |
| operations officer notified the R3DO (Hills) and NMSS EO (Combs).            |
|                                                                              |
| * * * UPDATE AT 2152 EDT ON 06/17/99 FROM WALKER TO POERTNER * * *           |
|                                                                              |
| "Three sprinkler heads on system C-15 and five sprinkler heads on system B-8 |
| in C-333 were identified to also be corroded.  The PSS was notified of this  |
| condition at 1300 CDT on 06/17/99 and determined that an update to this      |
| report was required.  It has been determined that this event is reportable   |
| under 10CFR76.120(c)(2) as an event in which equipment is disabled or fails  |
| to function as designed."  Paducah personnel notified the NRC resident       |
| inspector of this update.  The NRC operations officer notified the R3DO      |
| (Madera).                                                                    |
|                                                                              |
| * * * UPDATE 1440 EDT 6/18/1999 FROM UNDERWOOD TAKEN BY STRANSKY * * *       |
|                                                                              |
| "Two sprinkler heads on system C-15 and one sprinkler head on system B-8 in  |
| C-333 were identified to have corrosion.  The PSS was notified of this       |
| condition at 1350 CDT on 06/18/99.  The area of the fire patrol for system   |
| C-15 was expanded to include the two heads identified as corroded.  The one  |
| head on system B-8 was in the area already being patrolled.  The PSS         |
| determined that an update to this report was required."  The NRC resident    |
| inspector has been informed of this update.  Notified R3DO (Madera).         |
|                                                                              |
| * * * UPDATE 1315 EDT 6/25/1999 FROM WALKER TAKEN BY STRANSKY * * *          |
|                                                                              |
| "Two sprinkler heads on system D-8 and three sprinkler heads on system D-7   |
| in C-337 were identified to have corrosion.  The PSS was notified of the     |
| condition on system D-8 at 0125 CDT on 06/25/99 and at 1019 CDT on 06/25/99  |
| for system D-7.  Both systems were immediately declared inoperable and LCO   |
| fire patrol actions were implemented.  It was determined that an update to   |
| this report was required."  The NRC resident inspector has been informed of  |
| this update.  Notified R3DO (Jordan).                                        |
|                                                                              |
| * * * UPDATE 2119 EDT 7/30/1999 FROM CAGE TAKEN BY STRANSKY * * *            |
|                                                                              |
| "Five sprinkler heads and one sprinkler piping tee on C-337 system D-7 were  |
| identified to have corrosion. The PSS was notified of these corroded system  |
| parts and declared the system inoperable at 0931 CDT on 07/30/99.  LCO       |
| required fire patrols of the affected area were initiated.  The PSS          |
| determined that an update to this event report was required."  The NRC       |
| resident inspector has been informed of this update.  Notified R3DO          |
| (Wright).                                                                    |
|                                                                              |
| * * * UPDATE AT 1655 EDT ON 07/31/99 FROM WHITE TAKEN BY STRANSKY * * *      |
|                                                                              |
| "Two sprinkler heads on C-337 System D-1 were identified to have corrosion.  |
| The PSS was notified of these corroded system parts and declared the system  |
| inoperable at 1155 CDT on 7/31/99.  LCO required fire patrols of the         |
| affected area were initiated.  The PSS determined that an update to this     |
| report was required."  The NRC resident inspector has been informed of this  |
| update.  Notified R3DO (Wright).                                             |
|                                                                              |
| * * * UPDATE AT 1546 EDT ON 08/10/99 FROM WHITE TAKEN BY STRANSKY * * *      |
|                                                                              |
| "Two sprinkler heads on C-337 system C-15 were identified to have corrosion. |
| The PSS was notified of these corroded system parts and declared the system  |
| inoperable at 1130 CDT on 8/10/99.  LCO required fire patrols of the         |
| affected area were initiated.  The PSS determined that an update to this     |
| report was required."  The NRC resident inspector has been informed of this  |
| update.  Notified R3DO (Burgess).                                            |
|                                                                              |
| * * * UPDATE AT 1154 EDT ON 08/22/99 FROM WALKER TO POERTNER * * *           |
|                                                                              |
| Four adjacent sprinkler heads on the C-333 building System B-1 were          |
| identified to have corrosion.  The PSS was notified of the corroded system   |
| parts and declared the system inoperable at 0918 CDT on 08/22/99.  LCO       |
| required fire patrols were initiated.  The NRC Resident Inspector will be    |
| notified.  The NRC Operations Officer notified the R3DO (Clayton).           |
|                                                                              |
| * * * UPDATE 2015 EDT ON 08/28/99 FROM W. F. GAGE TO S. SANDIN * * *         |
|                                                                              |
| Two adjacent sprinkler heads on the C-337 building System D-11 were          |
| identified to have corrosion.  The PSS was notified of these corroded system |
| parts and declared the system inoperable at 1420 CDT on 08/28/99.   LCO      |
| required fire patrols of the affected area were initiated.  Paducah          |
| personnel informed the NRC Resident Inspector.  The NRC Operations Officer   |
| notified the R3DO (Leach) and NMSS EO (Piccone).                             |
|                                                                              |
| * * * UPDATE 2037 EDT ON 08/29/99 FROM KEVIN BEASLEY TO S. SANDIN * * *      |
|                                                                              |
| Two adjacent sprinkler heads on the C-337 building System D-15 were          |
| identified to have corrosion and the PSS declared the system inoperable at   |
| 0925 CDT on 08/29/99.  Also two adjacent heads on the C-337 building System  |
| D-10 were identified to have corrosion and the PSS declared the system       |
| inoperable at 1450 CDT.   LCO required fire patrols for both of the affected |
| areas were initiated in the time frame required by TSR.  Paducah personnel   |
| informed the NRC Resident Inspector.  The NRC Operations Officer notified    |
| the R3DO (Leach) and NMSS EO (Piccone).                                      |
|                                                                              |
| * * * UPDATE AT 0930 EDT ON 09/01/99  BY ERIC WALKER TO FANGIE JONES * * *   |
|                                                                              |
| Add two adjacent sprinkler heads on the C-337 building System D-14 were      |
| declared inoperable.  Paducah personnel informed the NRC Resident Inspector. |
| The NRC Operations Officer notified the R3DO (David Hills) and NMSS (Robert  |
| Pierson).                                                                    |
|                                                                              |
| * * * UPDATE AT 1133 EDT ON 09/08/99  BY TOM WHITE TO FANGIE JONES * * *     |
|                                                                              |
| Add two adjacent sprinkler heads on the C-331 building System 26 were        |
| declared inoperable at 2155 CDT on 09/07/99.  An LCO required fire patrol    |
| for the affected area was initiated in the time frame required by the TSR.   |
| Paducah personnel informed the NRC Resident Inspector.  The NRC Operations   |
| Officer notified the R3DO (Monte Phillips) and NMSS (Josie Piccone).         |
|                                                                              |
| * * * UPDATE AT 0948 ON 09/30/99 BY ERIC WALKER TO DOUG WEAVER * * *         |
|                                                                              |
| Add two adjacent sprinkler heads on the C-333 building System B-15 were      |
| identified to have corrosion and the PSS declared the system inoperable at   |
| 0815 CDT on 9/30/99.  An LCO required fire patrol for the affected area was  |
| initiated in the time frame required by the TSR.  Paducah personnel informed |
| the NRC Resident Inspector.   The NRC operations officer notified the R3DO   |
| (Vegel) and NMSS (Cool).                                                     |
|                                                                              |
| * * * UPDATE AT 1600 ON 10/13/99 BY WALKER TO GOULD * * *                    |
|                                                                              |
| Two adjacent sprinkler heads on the C-333 building System A-11 were          |
| Identified to have corrosion and the PSS declared the system inoperable at   |
| 1307 CDT on 10/13/99.  An LCO required fire patrol for the affected area was |
| initiated in the time frame required by the TSR.  Paducah personnel informed |
| the NRC Resident Inspector.   The NRC operations officer notified the R3DO   |
| (Madera) and NMSS (Moore).                                                   |
|                                                                              |
| * * * UPDATE AT 1520 ON 10/19/99 FROM UNDERWOOD TAKEN BY STRANSKY * * *      |
|                                                                              |
| Six sprinkler heads on the C-337 building System D-16 were identified to     |
| have corrosion and the PSS declared the system inoperable at 1052 CDT on     |
| 10/19/99.  An LCO required fire patrol for the affected area was initiated   |
| in the time frame required by the TSR.  The NRC Resident Inspector has been  |
| informed of this update.  The NRC Operations Officer notified R3DO           |
| (Jorgensen).                                                                 |
|                                                                              |
| * * * UPDATE AT 2140 ON 10/19/99 FROM WALKER TAKEN BY STRANSKY * * *         |
|                                                                              |
| Seven sprinkler heads on the C-337 building System A-7 were identified to    |
| have corrosion, and another four had been painted over.  In addition, three  |
| adjacent sprinkler heads on the C-337 building System A-8 were identified to |
| have corrosion.  The PSS declared the systems inoperable at 1900 CDT on      |
| 10/19/99.  An LCO required fire patrols for the affected areas were          |
| initiated in the time frame required by the TSR.  The NRC Resident Inspector |
| has been informed of this update.  The NRC Operations Officer notified R3DO  |
| (Wright).                                                                    |
|                                                                              |
| * * * UPDATE AT 1713 ON 10/21/99 FROM CAGE TAKEN BY JOLLIFFE * * *           |
|                                                                              |
| Four sprinkler heads on the C-337 building System A-5, twelve sprinkler      |
| heads on the C-337 building System A-8, three sprinkler heads on the C-337   |
| building System A-9, and six sprinkler heads on the C-337 building System    |
| B-8 were identified to have corrosion.  On 10/21/99, the PSS declared        |
| Systems A-5 and A-9 inoperable at 1028 CDT, System A-8 inoperable at 1227    |
| CDT and System B-8 inoperable at 1406 CDT.   An LCO required fire patrol for |
| the affected areas was initiated in the time frame required by the TSR..     |
| The NRC Resident Inspector has been informed of this update.  The NRC        |
| Operations Officer notified the R3DO Bruce Jorgensen.                        |
|                                                                              |
| * * * UPDATE AT 2128 ON 10/22/99 FROM ERIC WALKER TAKEN BY JOLLIFFE * * *    |
|                                                                              |
| At 1400 CDT on 10/22/99, the PSS was notified that numerous corroded         |
| sprinkler heads were discovered in the C-337 building on sprinkler systems   |
| B-1, B-3, B-5, B-6, B-7, B-11 and D-17.  Due to the number of systems called |
| into question, the PSS declared all of the sprinkler systems in C-337 on the |
| cell floor (a total of 66 systems) inoperable and TSR required actions       |
| establishing roving fire patrols were initiated within the required time     |
| frame.  The NRC Resident lnspector has been informed of this update.  The    |
| NRC Operations Officer notified the R3DO Bruce Jorgensen.                    |
|                                                                              |
| * * * UPDATE AT 1239 ON 10/24/99 FROM TOM WHITE TAKEN BY JOLLIFFE * * *      |
|                                                                              |
| At 1200 CDT on 10/23/99, the PSS was notified that numerous corroded         |
| sprinkler heads were discovered in the C-337 building on sprinkler systems   |
| B-13 and B-14 on the ground floor,  The PSS declared these systems           |
| inoperable and TSR required actions establishing roving fire patrols were    |
| initiated within the required time frame.  At 1600 CDT on 10/23/99, the PSS  |
| was notified that numerous corroded sprinkler heads were discovered in the   |
| C-337 building on sprinkler systems A-16, B-12, C-8, C-12, C-15, D-5 and D-8 |
| on the cell floor,  These systems have already been declared inoperable and  |
| fire patrols are already being performed.  The NRC Resident Inspector has    |
| been notified of this update.  The NRC Operations Officer notified the R3DO  |
| Bruce Jorgensen.                                                             |
|                                                                              |
| * * * UPDATE AT 1117 ON 10/25/99 FROM W. F. CAGE TAKEN BY SANDIN * * *       |
|                                                                              |
| At 1940 CDT on 10/24/99, the PSS was notified that numerous corroded         |
| sprinkler heads had been discovered on High Pressure Fire Water Systems C-4, |
| C-5, C-6 and C-8, located in the C-337 building.  These systems had          |
| previously been declared inoperable and fire patrols were already being      |
| performed at the time of discovery.  The NRC Resident Inspector has been     |
| notified of this update.  The NRC Operations Officer notified R3DO           |
| (Lanksbury) and NMSS (Brain Smith).                                          |
|                                                                              |
| * * * UPDATE AT 2235 ON 10/27/99 BY WHITE TAKEN BY MACKINNON * * *           |
|                                                                              |
| At 1517 CDT on 10/27/99, the PSS was notified that nine corroded sprinkler   |
| heads had been discovered on High Pressure Fire Water System A-12 located in |
| the C-333 building.  This system has been declared inoperable and fire       |
| patrols have been initiated.  The NRC Resident Inspector has been notified   |
| of this update.  The NRC Operations Officer notified R3DO (Jordan) and NMSS  |
| EO (Hickey).                                                                 |
|                                                                              |
| * * * UPDATE AT 2150 ON 10/30/99 BY UNDERWOOD TAKEN BY WEAVER * * *          |
|                                                                              |
| At 1950 CDT on 10/30/99, the PSS was notified that numerous corroded         |
| sprinkler heads had been discovered on High Pressure Fire Water Systems A-5, |
| A-9, A-11, C-5, and C-7 in the C-333 building.  Reference ATR-1 1999-6699    |
| and 6702.  These systems have been declared inoperable and fire patrols have |
| been initiated.  Also, due to the number of inoperable sprinkler heads, the  |
| remaining systems on the cell floor of C-333 were called into question and   |
| declared inoperable.  Fire patrols for the entire cell floor have been       |
| initialed.  The PSS determined that an update to this report was required.   |
| The NRC Resident Inspector has been notified of this update.  The NRC        |
| Operations Officer notified R3DO (Jordan) and NMSS EO (Hickey).              |
|                                                                              |
| * * * UPDATE AT 2111 ON 10/31/99 BY UNDERWOOD TAKEN BY WEAVER * * *          |
|                                                                              |
| At 1412 CDT on 10/31/99, the PSS was notified that five corroded sprinkler   |
| heads had been discovered on High Pressure Fire Water System 9 in the C-335  |
| building.  There were two adjacent corroded heads discovered in two separate |
| locations and a third individual head at a different location.  The system   |
| was declared inoperable and fire patrols were initiated.  The corroded heads |
| have since been replaced and the system returned to operable status.   The   |
| NRC Resident Inspector was notified of this update.  The NRC Operations      |
| Officer notified R3DO (Jordan) and NMSS EO (Hickey).                         |
|                                                                              |
| * * * UPDATE AT 2121 ON 11/01/99 BY KEVIN BEASLEY TAKEN BY JOLLIFFE * * *    |
|                                                                              |
| At 0930 CST on 11/01/99, the PSS was notified that three corroded sprinkler  |
| heads had been discovered on the High Pressure Fire Water System B-4 in the  |
| C-337 building.  Two of these sprinkler heads are adjacent.  Two adjacent    |
| corroded sprinkler heads were also discovered on the High Pressure Fire      |
| Water System B-5 in the C-337 building.  These systems were declared         |
| inoperable and fire patrols were initiated.  Work has been initiated to      |
| replace the corroded heads.  The NRC Resident Inspector has been notified of |
| this update.  The NRC Operations Officer notified the R3DO Jim Creed.        |
|                                                                              |
| * * * UPDATE AT 2143 ON 11/02/99 BY KEVIN BEASLEY TAKEN BY JOLLIFFE * * *    |
|                                                                              |
| At 1400 CST on 11/02/99, the PSS was notified that numerous corroded         |
| sprinkler heads had been discovered on High Pressure Fire Water Systems C-8  |
| and D-7 in the C-333 building.  These systems had been previously declared   |
| inoperable and fire patrols were being performed at the time of discovery.   |
| Work has been initiated to replace the corroded heads.  The NRC Resident     |
| Inspector has been notified of this update.  The NRC Operations Officer      |
| notified the R3DO Jim Creed.                                                 |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36385       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PALISADES                REGION:  3  |NOTIFICATION DATE: 11/02/1999|
|    UNIT:  [1] [] []                 STATE:  MI |NOTIFICATION TIME: 11:45[EST]|
|   RXTYPE: [1] CE                               |EVENT DATE:        11/02/1999|
+------------------------------------------------+EVENT TIME:        09:00[EST]|
| NRC NOTIFIED BY:  BOB VINCENT                  |LAST UPDATE DATE:  11/02/1999|
|  HQ OPS OFFICER:  DICK JOLLIFFE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |JAMES CREED          R3      |
|10 CFR SECTION:                                 |                             |
|ADAS 50.72(b)(2)(i)      DEG/UNANALYZED COND    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Refueling        |0        Refueling        |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| - INDICATIONS DISCOVERED ON CONTROL ROD DRIVE SEAL HOUSINGS -                |
|                                                                              |
| At 0900 on 11/02/99, a dye penetrant (PT) examination of the control rod     |
| drive seal housing for control rod #44 revealed a potential crack-like       |
| indication in the Reactor Coolant System pressure boundary.  The PT          |
| examination was performed to investigate a boric acid deposit on the         |
| exterior surface of the housing which was discovered during a previous       |
| visual inspection.  A small indication was also found on the seal housing    |
| for control rod #30.  The plant is in a refueling outage.  An investigation  |
| to characterize the indications and determine their cause and extent is in   |
| progress.  This situation will be resolved prior to plant restart.           |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36386       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: FT CALHOUN               REGION:  4  |NOTIFICATION DATE: 11/02/1999|
|    UNIT:  [1] [] []                 STATE:  NE |NOTIFICATION TIME: 17:45[EST]|
|   RXTYPE: [1] CE                               |EVENT DATE:        11/02/1999|
+------------------------------------------------+EVENT TIME:        16:00[CST]|
| NRC NOTIFIED BY:  ERICK MATZKE                 |LAST UPDATE DATE:  11/02/1999|
|  HQ OPS OFFICER:  DICK JOLLIFFE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |CLAUDE JOHNSON       R4      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(vi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Cold Shutdown    |0        Cold Shutdown    |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| - STATE NOTIFIED OF AN OIL/GREASE RELEASE IN EXCESS OF THEIR NPDES RELEASE   |
| PERMIT LIMIT -                                                               |
|                                                                              |
| On 10/04/99, a mixture of oil and grease was released from the plant.  The   |
| licensee sent a composite sample of the mixture to an offsite facility for   |
| analysis.  At 1600 CST on 11/02/99, the licensee received the results of the |
| analysis and notified the State of Nebraska that the release (13 mg/l) was   |
| in excess of the station's NPDES release permit limit (10 mg/l).             |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36387       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: GRAND GULF               REGION:  4  |NOTIFICATION DATE: 11/02/1999|
|    UNIT:  [1] [] []                 STATE:  MS |NOTIFICATION TIME: 19:06[EST]|
|   RXTYPE: [1] GE-6                             |EVENT DATE:        11/02/1999|
+------------------------------------------------+EVENT TIME:        16:56[CST]|
| NRC NOTIFIED BY:  ERNEST MATHES                |LAST UPDATE DATE:  11/02/1999|
|  HQ OPS OFFICER:  DICK JOLLIFFE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |CLAUDE JOHNSON       R4      |
|10 CFR SECTION:                                 |                             |
|ADAS 50.72(b)(2)(i)      DEG/UNANALYZED COND    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Refueling        |0        Refueling        |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| - MSIVs LEAKING ABOVE ACCEPTABLE LEAK RATE DURING AN LLRT -                  |
|                                                                              |
| During a local leak rate test with the plant in a refueling outage, the      |
| licensee discovered excess leakage past the 'A' main steam line inboard and  |
| outboard main steam isolation valves (#B21-F022A and #B21-F028A).  This      |
| condition exceeded the acceptable leak rate.  The licensee is determining    |
| corrective action.                                                           |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36388       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: QUAD CITIES              REGION:  3  |NOTIFICATION DATE: 11/02/1999|
|    UNIT:  [] [2] []                 STATE:  IL |NOTIFICATION TIME: 20:57[EST]|
|   RXTYPE: [1] GE-3,[2] GE-3                    |EVENT DATE:        11/02/1999|
+------------------------------------------------+EVENT TIME:        19:01[CST]|
| NRC NOTIFIED BY:  TOM OSELAND                  |LAST UPDATE DATE:  11/02/1999|
|  HQ OPS OFFICER:  DICK JOLLIFFE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |JAMES CREED          R3      |
|10 CFR SECTION:                                 |                             |
|AOUT 50.72(b)(1)(ii)(B)  OUTSIDE DESIGN BASIS   |                             |
|AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION    |                             |
|NLCO                     TECH SPEC LCO A/S      |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| - HIGH PRESSURE COOLANT INJECTION (HPCI) SYSTEM INOPERABLE -                 |
|                                                                              |
| During performance of the HPCI Steam Exhaust Vacuum Breaker Line Check       |
| Valves IST Functional Test, one of four check valves failed to meet its      |
| acceptance criteria.  The licensee isolated the check valve, declared the    |
| HPCI System inoperable, and entered a 14 day LCO.  All other Emergency Core  |
| Cooling Systems are operable.                                                |
|                                                                              |
| The licensee plans to notify the NRC Resident Inspector.                     |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36389       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: LASALLE                  REGION:  3  |NOTIFICATION DATE: 11/02/1999|
|    UNIT:  [] [2] []                 STATE:  IL |NOTIFICATION TIME: 21:16[EST]|
|   RXTYPE: [1] GE-5,[2] GE-5                    |EVENT DATE:        11/02/1999|
+------------------------------------------------+EVENT TIME:        19:47[CST]|
| NRC NOTIFIED BY:  LARRY BLUNK                  |LAST UPDATE DATE:  11/02/1999|
|  HQ OPS OFFICER:  DICK JOLLIFFE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |JAMES CREED          R3      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(vi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| - OFFSITE AGENCIES NOTIFIED OF THE PRESENCE OF OIL LADEN GRAVEL ONSITE -     |
|                                                                              |
| The licensee notified the Illinois Emergency Management Agency and the       |
| National Response Center of the presence of oil in the pea gravel around the |
| oil filling station underground storage tanks.  The oil was present in a two |
| inch layer of gravel at the top of the water table approximately five feet   |
| below ground level.  The filling station consists of a 10,000 gallon diesel  |
| fuel tank, a 10,000 gallon gasoline tank, and a 1,000 gallon waste oil tank. |
| No fire, explosion, or vapor hazards have been identified.  The tanks will   |
| continue to be excavated for State Fire Marshall inspection on 11/04/99.     |
| The oil laden pea gravel will be removed and disposed of properly.           |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+
