Event Notification Report for October 12, 1999
U.S. Nuclear Regulatory Commission Operations Center Event Reports For 10/08/1999 - 10/12/1999 ** EVENT NUMBERS ** 36012 36209 36273 36274 36275 36276 36277 36278 36279 36280 36281 !!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED !!!!!!! +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 36012 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: CLINTON REGION: 3 |NOTIFICATION DATE: 08/10/1999| | UNIT: [1] [] [] STATE: IL |NOTIFICATION TIME: 14:23[EDT]| | RXTYPE: [1] GE-6 |EVENT DATE: 08/10/1999| +------------------------------------------------+EVENT TIME: 12:30[CDT]| | NRC NOTIFIED BY: ROBERT POWERS |LAST UPDATE DATE: 10/08/1999| | HQ OPS OFFICER: BOB STRANSKY +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |BRUCE BURGESS R3 | |10 CFR SECTION: | | |AOUT 50.72(b)(1)(ii)(B) OUTSIDE DESIGN BASIS | | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N Y 100 Power Operation |100 Power Operation | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | EMERGENCY DIESEL GENERATOR DECLARED INOPERABLE DUE TO FUEL OIL LEAK | | | | "Abnormal readings from the lube oil analysis of the division 2 diesel | | generator lead to further testing of its lube oil. Gas chromatography | | analysis of the division 2 diesel generator lube oil showed a 5.7% fuel oil | | dilution. Vendor recommendations were to not operate the diesel with greater | | than 5.0% fuel oil dilution. The division 2 diesel generator was tagged out | | for maintenance and declared inoperable on 8/9/99 at 1330 central time. | | During maintenance of the division 2 diesel generator it was discovered that | | the 12th cylinder of the 16 cylinder engine fuel injector return line | | fitting was weeping fuel oil. | | | | "This notification is being made pursuant to 10CFR5072(b)(1)(ii)(B) as a | | condition outside of the design basis of the plant because of the discovery | | that the division 2 diesel generator has been incapable of performing its | | design function (intended safety function) for an extended period of time | | during operation." | | | | The NRC resident inspector has been informed of this notification by the | | licensee. | | | | * * * RETRACTION 1803 10/8/1999 FROM ED TIEDEMANN TAKEN BY STRANSKY * * * | | | | "This report is to retract the notification of 8/10/1999, based on further | | evaluation by onsite engineering and licensing personnel, and offsite | | resources. The engineering evaluation performed for this event determined | | that the diesel generator would have fulfilled the design basis | | requirements, even with the effects of fuel dilution in the lube oil. " | | | | The NRC resident inspector has been informed of this retraction. Notified | | R3DO (Jacobson). | +------------------------------------------------------------------------------+ !!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED !!!!!!! +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 36209 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: QUAD CITIES REGION: 3 |NOTIFICATION DATE: 09/21/1999| | UNIT: [1] [2] [] STATE: IL |NOTIFICATION TIME: 20:41[EDT]| | RXTYPE: [1] GE-3,[2] GE-3 |EVENT DATE: 09/10/1999| +------------------------------------------------+EVENT TIME: 14:40[CDT]| | NRC NOTIFIED BY: DARYL CLARK |LAST UPDATE DATE: 10/08/1999| | HQ OPS OFFICER: DICK JOLLIFFE +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |ROGER LANKSBURY R3 | |10 CFR SECTION: | | |AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION | | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N Y 100 Power Operation |100 Power Operation | |2 N Y 100 Power Operation |100 Power Operation | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | -CONTROL ROOM EMERGENCY FILTRATION SYSTEM INOP DUE TO FAILING ITS | | SURVEILLANCE TEST- | | | | At 1440 CDT on 09/10/99, while performing the Control Room Emergency | | Filtration (CREF) System monthly surveillance test, the system flow rate was | | found to be 2317 scfm. The required tech spec flow rate is 2000 scfm +/- | | 10%. The licensee declared the CREF System inoperable per Tech Spec 3.8.D | | and entered a 7 day LCO. This event is being reported to the NRC in | | accordance with 10CFR50.72 (b)(2)(iii)(D), a condition that prevented the | | fulfillment of a safety function. | | | | The licensee declared the CREF System operable 40 minutes later after | | adjusting the air flow. | | | | The licensee is continuing to evaluate the reportability of this issue. | | | | The licensee informed the NRC Resident Inspector. | | | | * * * RETRACTION 2158 10/8/1999 FROM LECHMAIER TAKEN BY STRANSKY * * * | | | | "This report is a retraction of the ENS call made on 9/21/99 concerning the | | Control Room Emergency Filtration System. We have completed our evaluation | | and have determined that the high flow rate condition found would not have | | prevented the system from performing its intended function. Therefore, this | | event is not reportable with respect to 10CFR50.72(b)(2)(iii). | | | | "The system damper that was previously repositioned on 9/1/99 was the cause | | of this high flow. This condition is prohibited by Technical Specifications | | (LCO exceeded) and is reportable in accordance with | | 10CFR50.73(a)(2)(I)(B)." | | | | The NRC resident inspector has been informed of this retraction by the | | licensee. Notified R3DO (Jacobson). | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |General Information or Other |Event Number: 36273 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | REP ORG: BRITISH NUCLEAR FUELS, PLC |NOTIFICATION DATE: 10/08/1999| |LICENSEE: BRITISH NUCLEAR FUELS, PLC |NOTIFICATION TIME: 08:14[EDT]| | CITY: REGION: |EVENT DATE: 08/19/1999| | COUNTY: STATE: |EVENT TIME: [EST]| |LICENSE#: AGREEMENT: N |LAST UPDATE DATE: 10/08/1999| | DOCKET: |+----------------------------+ | |PERSON ORGANIZATION | | |JOHN KINNEMAN R1 | | |BRIAN BONSER R2 | +------------------------------------------------+JOHN JACOBSON R3 | | NRC NOTIFIED BY: EUR ING MIKE R A SMITH |KRISS KENNEDY R4 | | HQ OPS OFFICER: LEIGH TROCINE |KEVIN RAMSEY NMSS | +------------------------------------------------+ | |EMERGENCY CLASS: N/A | | |10 CFR SECTION: | | |CCCC 21.21 UNSPECIFIED PARAGRAPH | | | | | | | | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | 10 CFR PART 21 NOTIFICATION REGARDING THE POTENTIAL FOR A CYLINDER | | (MANUFACTURED BY STARVELEY'S LIMITED AND SUPPLIED BY BNFL TO USEC FOR | | ENRICHMENT) TO BE OVERFILLED BECAUSE THE CERTIFIED WATER CAPACITY STAMPED ON | | THE CYLINDER IS LESS THAN THE SPECIFIED MINIMUM CAPACITY | | | | The following text is a portion of a facsimile received from Eur Ing Mike R. | | A. Smith, MRA Smith BSc CEng MIES, Head of Magnox and Hex Business, British | | Nuclear Fuels (BNFL), Fuel Business Group: | | | | "[10 CFR 21.21(4)(ii) - Identification of the facility, the activity, or the | | basic component supplied for such facility or such activity within the U.S. | | which fails to comply or contains a defect:] 48Y Cylinder no. 1122/0690 | | containing 12,155.5 kg of UF6 supplied to [United States Enrichment | | Corporation (USEC)] by BNFL Fuel for enrichment." | | | | "[10 CFR 21.21(4)(iii) - Identification of the firm constructing the | | facility or supplying the basic component which fails to comply or contains | | a defect:] Cylinder manufactured by Staveley's Limited, Manchester, England | | in 1978. | | | | "[10 CFR 21.21(4)(iv) - Nature of the defect or failure to comply and the | | safety hazard which is created or could be created by such defect or failure | | to comply:] The certified water capacity stamped on the cylinder as part of | | the name plate data is less than the minimum capacity specified in ANSI | | N14.1, Table 1, standard cylinder data for a 48Y cylinder. [The] required | | minimum capacity [is] 142.7 ft�[, and the] actual certified water capacity | | [is] 4,019 kg; equivalent to 142.1 ft�. The cylinder, in its current | | condition, represents no safety hazard since the actual contents of 2,155.5 | | kg of UF6 still allows a cylinder ullage of 7.2%. The cylinder has the | | potential to be overfilled if the normal maximum fill limit for a 48Y was | | reached (12,501 kg of UF6 as specified in ANSI N14.1)." | | | | "[10 CFR 21.21(4)(v) - The date on which the information of such defect or | | failure to comply was obtained:] A memo was sent from USEC on 19 August | | 1999, informing BNFL Fuel that they had noted the certified water capacity | | was less than the ANSI-N14.1 minimum." | | | | "[10 CFR 21.21(4)(vi) - In the case of a basic component which contains a | | defect or fails to comply, the number and location of all such components in | | use at, supplied for, or being supplied for one or more facilities or | | activities subject to the regulations in this part:] Cylinder 1122/0690 is | | one of a batch of 108 cylinders purchased from Staveleys in 1978. All other | | 48Y Type Cylinders 1122/0600 to 1122/0707 inclusive, numbering 107, are | | located on licensed sites in the UK." | | | | "[10 CFR 21.21(4)(vii) - The corrective action which has been, is being, or | | will be taken; the name of the individual or organization responsible for | | the action; and the length of time that has been or will be taken to | | complete the action:] Having established that cylinder 1122/0690 is safe to | | feed; it is proposed to discuss with USEC the possibility of proceeding with | | the feed to their diffusion plant, as planned. Alternatively, should USEC | | be unwilling to proceed then concession will be sought to transfer the | | cylinder back to BNFL in the UK." | | | | "Once emptied, the cylinder will be removed from service to prevent any | | possibility of a re-occurrence." | | | | "The Head of Site at BNFL Springfields has commissioned a Working Party, | | which includes an independent senior engineer, independent senior operations | | manager, and standards/surveillance engineers." | | | | "The Working Party: | | a) Has already independently verified that there are no other under | | capacity cylinders located in the U.S.; | | b) Will independently verify whether or not any other BNFL cylinders are | | under capacity; | | c) In the event that the independent verification does reveal any further | | such defective cylinders, will initiate appropriate action to remove such | | cylinders from service; | | d) Will monitor the implementation of any such actions through to | | completion; | | e) [Has] already examined and modified BNFL's cylinder filling procedures | | to prevent an under capacity cylinder from being filled in the future; | | [and] | | f) [Is] in the process of reviewing our cylinder purchase specification to | | prevent any further under capacity cylinders from being supplied." | | | | "[10 CFR 21.21(4)(viii) - Any advice related to the defect or failure to | | comply about the facility, activity, or basic component that has been, is | | being, or will be given to purchasers or licensees:] The UK Nuclear | | Installations Inspectorate (NII) and Department of the Environment, | | Transport, and Regions (DETR) have been advised of this notification." | | | | (Call the NRC operations officer for contact information.) | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 36274 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: NINE MILE POINT REGION: 1 |NOTIFICATION DATE: 10/08/1999| | UNIT: [1] [] [] STATE: NY |NOTIFICATION TIME: 09:44[EDT]| | RXTYPE: [1] GE-2,[2] GE-5 |EVENT DATE: 10/08/1999| +------------------------------------------------+EVENT TIME: 09:05[EDT]| | NRC NOTIFIED BY: THOMAS HOWARD |LAST UPDATE DATE: 10/08/1999| | HQ OPS OFFICER: LEIGH TROCINE +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: UNU |JOHN KINNEMAN R1 | |10 CFR SECTION: |TAD MARSH NRR | |AAEC 50.72 (a) (1) (I) EMERGENCY DECLARED |CHARLES MILLER IRO | | |MIKE TSCHILTZ EDO | | |BURNICE CARR FEMA | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N Y 24 Power Operation |24 Power Operation | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | DECLARATION OF UNUSUAL EVENT DUE TO THE POSSIBILITY THAT VARIOUS AREAS OF | | THE PLANT ARE INACCESSIBLE DUE TO A HAZARDOUS ATMOSPHERE | | | | The following text is a portion of a facsimile received from the licensee: | | | | "[At 0905 on 10/08/99, an] Unusual Event [was] declared due to Cardox fire | | system discharge ([carbon dioxide]) in [the Administration Building at | | 0815]. Various levels of the plant are being considered inaccessible until | | [oxygen] levels are verified [to be] satisfactory. [Carbon dioxide] venting | | is in progress. [There is no] effect on plant operation at [the] present | | time[, and no effect is currently] anticipated." | | | | "[The] preliminary cause of discharge of [carbon dioxide] appears to be a | | switch malfunction. No fire was detected." | | | | The licensee stated that the Cardox fire system has both a 30-second siren | | and flashing red lights prior to the discharge of carbon dioxide in order to | | allow personnel to evacuate the affected areas. There were no injuries | | reported, and carbon dioxide venting is currently in progress. The | | Administration Building and some adjacent areas of the turbine building were | | affected. | | | | The licensee notified the NRC resident inspector as well as state and local | | agencies. The licensee also plans to issue a media/press release. | | | | * * * UPDATE 1219 10/8/1999 FROM MATTESON TAKEN BY STRANSKY * * * | | | | The Unusual Event was terminated at 1210 EDT. The NRC resident inspector has | | been informed. Notified R1DO (Kinneman), NRR (Marsh), IRO (Miller), FEMA | | (Carr). | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 36275 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: SAINT LUCIE REGION: 2 |NOTIFICATION DATE: 10/08/1999| | UNIT: [1] [2] [] STATE: FL |NOTIFICATION TIME: 13:17[EDT]| | RXTYPE: [1] CE,[2] CE |EVENT DATE: 10/08/1999| +------------------------------------------------+EVENT TIME: 11:10[EDT]| | NRC NOTIFIED BY: CALVIN WARD |LAST UPDATE DATE: 10/08/1999| | HQ OPS OFFICER: BOB STRANSKY +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |BRIAN BONSER R2 | |10 CFR SECTION: | | |APRE 50.72(b)(2)(vi) OFFSITE NOTIFICATION | | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N N 0 Cold Shutdown |0 Cold Shutdown | |2 N Y 100 Power Operation |100 Power Operation | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | OFFSITE NOTIFICATION REQUIRED BY NPDES PERMIT | | | | The licensee contacted the Florida Department of Environmental Protection | | (DEP) regarding the discharge of effluent to the Atlantic Ocean. The site | | settling ponds were pumped down due to high water levels caused by recent | | rain. The site National Pollution Discharge Elimination System (NPDES) | | permit requires that the licensee contact the state DEP regarding this | | discharge. No release limits were exceeded. The NRC resident inspector has | | been informed of this notification by the licensee. | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 36276 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: SALEM REGION: 1 |NOTIFICATION DATE: 10/08/1999| | UNIT: [1] [2] [] STATE: NJ |NOTIFICATION TIME: 16:13[EDT]| | RXTYPE: [1] W-4-LP,[2] W-4-LP |EVENT DATE: 10/08/1999| +------------------------------------------------+EVENT TIME: 15:50[EDT]| | NRC NOTIFIED BY: RUSS GUMBERT |LAST UPDATE DATE: 10/08/1999| | HQ OPS OFFICER: BOB STRANSKY +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |JOHN KINNEMAN R1 | |10 CFR SECTION: | | |ADEG 50.72(b)(1)(ii) DEGRAD COND DURING OP | | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N N 0 Refueling |0 Refueling | |2 N Y 100 Power Operation |100 Power Operation | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | 10 CFR PART 50, APPENDIX R ISSUE REGARDING CABLE SEPARATION | | | | The following is text of a (rather lengthy) facsimile submitted by the | | licensee: | | | | "1. Description of Condition | | | | "During a review of the Salem Post-fire Safe Shutdown Analysis a concern was | | identified with the cable routing of the pressurizer PORV and block valves. | | The cable for each PORV and its associated block valve is routed in the same | | cable tray inside the containment. The pressurizer PORVs and block valves | | are considered a high/low pressure interface point for 10CFR50 Appendix R | | analysis. Therefore each PORV block valve combination is considered as | | redundant components that require proper separation in accordance with | | Section III.G.2 of Appendix R to prevent hot shorts, open circuits, or | | shorts to ground from causing spurious operation of these valves. | | | | "In the event of a postulated fire inside containment a block valve could | | lose power; since this valve is in the open position it would not be able to | | be closed. A hot short could also cause the PORV to spuriously open. These | | two occurrences together would result in the loss of Reactor Coolant System | | (RCS) inventory control. This condition does not satisfy the 10CFR50 | | Appendix R performance goal of inventory control for post-fire Safe Shutdown | | (SSD). | | | | "A second similar concern exists with the PORVs and block valves for | | Alternate Shutdown (ASD) capability. ASD is implemented in the event of a | | fire in the Control Room, Relay Room or the ceiling of the 460V Switchgear | | room. A fire in the above areas could lead to the spurious operation of the | | PORVs. Operators implement the ASD methodology in accordance with procedures | | S1(2).OP-AB.CR-0002. Spurious operation of the PORV could occur prior to the | | operators reaching the step in the ASD to operate the local switch for the | | block valve and close the block valve. In the current procedure, it takes | | approximately 20 minutes to reach the step to operate the transfer switch | | for the block valve. Prior to closing the block valve, there would be a loss | | of RCS inventory control due to the spurious operation of the PORV. | | | | "2. Impact Statement | | | | "For design basis accident mitigation (UFSAR Chapter 15), the PORV and block | | valves are not impacted and remain operable. Currently, the PORV and block | | valve configuration does not meet the requirements of 10CFR50 Appendix R and | | therefore is outside the design basis of the plant for Appendix R. This item | | is reportable in accordance with 10CFR50.72. | | | | "The inadvertent opening of the PORV and block valve would result in RCS | | depressurization. For the block valve and PORV to open the following needs | | to occur: | | | | "* an external or internal "hot short" of the PORV solenoid DC control | | circuitry which causes the energization of the solenoid, coincident with the | | complete loss of the power supply cable to the PORV block valve, which | | prevents remote operation (closure) of the block valve, is a very low | | probability event. | | | | "* The control cables have external insulation, with an armored shield, | | with multiple individual insulated conductors within the shield. In order | | for the internal hot short to occur, the external fire would have to burn | | through the cable external jacket, and shielding, and then selectively | | affect specific DC conductors within the cable to enable conductors of the | | correct polarity to come in contact in such a manner to energize the | | solenoid valve and open the PORV. The same external fire would also have to | | damage the power supply to the block valve to preclude operation, as stated | | above. | | | | "* In order for the external hot short to occur, another cable in the | | same raceway system, which is also of a shielded construction, would have to | | have one of its internal conductors affected by the external fire affect the | | conductors of the PORV control circuit, which is contained in its own | | shielded cable. This is an even more unlikely scenario. | | | | "The probability of a fire, of a magnitude that would cause the above to | | occur inside containment is extremely low for the following reasons. | | | | "* The main source of combustion inside containment is the oil in the | | RCP motor. However, the RCP motor is not in the vicinity of the affected | | cable trays. The RCP motor is equipped with detection and suppression | | system. An oil collection system is provided in the event of the leakage. | | | | "* The introduction of transient combustible materials into the | | containment is extremely remote due to limited containment access during | | operation. | | | | "* The RCP motor oil level has a low-level alarm in the control room. | | Any inadvertent oil loss would be detected and corrected early. This reduces | | the probability of lire due to the oil leakage. | | | | "* The cables in the affected cable tray are made up of | | self-extinguishing cable material. This will minimize fire propagation along | | the cables. | | | | "* Containment volume is large. The probability of a plume to occur to | | affect the cable trays is extremely low. | | | | "* A qualitative risk assessment shows that the probability of fire | | inside containment, in the area of concern, is extremely low. | | | | "3. Cause of Occurrence | | | | "The above concerns were not properly evaluated during development of the | | safe shutdown analysis. | | | | "4. Immediate Corrective Actions | | | | "* Establish appropriate compensatory measures for the Alternate | | Shutdown Area in accordance with the fire protection program. | | | | "* A containment loose debris inspection is performed following each | | containment entry during Modes 1-4. | | | | "* Following any containment entry, a walkdown will be performed to | | ensure that there are no combustible loads in the vicinity of the affected | | cable trays. | | | | "* Ensure operating shifts are alerted that spurious operation of the | | PORVs may be caused by a fire inside containment. | | | | "* Additional corrective actions are being evaluated and will be | | implemented as necessary. | | | | "5. Long Term Corrective Actions | | | | "* Prior to startup from the next refueling outage, evaluate potential | | plant modifications and/or licensing/design basis changes. Actions will be | | implemented as required to address the PORV and block valve spurious | | operation concern." | | | | The NRC resident inspector has been informed of this notification by the | | licensee. | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 36277 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: SURRY REGION: 2 |NOTIFICATION DATE: 10/09/1999| | UNIT: [1] [2] [] STATE: VA |NOTIFICATION TIME: 22:13[EDT]| | RXTYPE: [1] W-3-LP,[2] W-3-LP |EVENT DATE: 10/09/1999| +------------------------------------------------+EVENT TIME: 12:41[EDT]| | NRC NOTIFIED BY: LISA HILBERT-SEMMES |LAST UPDATE DATE: 10/09/1999| | HQ OPS OFFICER: BOB STRANSKY +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |BRIAN BONSER R2 | |10 CFR SECTION: |JOHN ZWOLINSKI NRR | |AESF 50.72(b)(2)(ii) ESF ACTUATION |CHARLES MILLER IRO | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N Y 100 Power Operation |100 Power Operation | |2 N Y 100 Power Operation |96 Power Operation | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | EDGs START AND LOAD DUE TO LOSS OF ONE RESERVE STATION SERVICE TRANSFORMER | | | | "At 1241 hours, with Surry Power Station Unit 1 and Unit 2 at 100% reactor | | power, a loss of 'C' Reserve Station Service Transformer (RSST) occurred due | | to a fire on one of the leads. The #1 Emergency Diesel Generator (EDG) auto | | started due to an undervoltage signal on the Unit 1 'H' emergency bus and | | re-energized the Unit 1 'H' emergency bus. Also, the #3 EDG auto started due | | to an undervoltage signal on the Unit 2 'J' emergency bus and re-energized | | the Unit 2 'J' emergency bus. The fire team reported that the fire was out | | at 1243. Unit 1 remained at 100% power. Unit 2 decreased to 96% power due to | | a perturbation on the semi-vital bus when the 'J' emergency bus was | | de-energized then re-energized by the #3 EDG. The unit was returned to 100% | | power at 1400 when all unit conditions were verified stable. All equipment | | performed as expected during the event and there were no unexplained | | occurrences other than the loss of 'C' RSST which is under investigation. | | | | "No adverse radiological consequences resulted from this event. There were | | no radiation releases due to this event, nor were there any personnel | | injuries or contamination events. | | | | "Unit 1 is currently at 100% power and 845 MWe with #1 EDG supplying the 'H' | | emergency bus. | | | | "Unit 2 is currently at 100% power and 855 MWe with #3 EDG supplying the 'J' | | emergency bus. | | | | "This event was initially determined to be not reportable based on the EDG | | auto start signal being due to an undervoltage signal and not a valid ESF | | signal. Upon further review of Tech Specs and NUREG 1022, it was determined | | at 2015 that the EDG auto starts due to an under voltage signal were | | reportable as an ESF actuation." | | | | The NRC resident inspector has been informed of this event by the licensee. | | | | This is event is being reported in accordance with 10 CFR 50.72(b)(2)(ii). | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Research Reactor |Event Number: 36278 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: STATE UNIV OF NEW YORK AT BUFFALO |NOTIFICATION DATE: 10/10/1999| | RXTYPE: 2000 KW PULSTAR |NOTIFICATION TIME: 11:48[EDT]| | COMMENTS: |EVENT DATE: 10/09/1999| | |EVENT TIME: 22:00[EDT]| | |LAST UPDATE DATE: 10/10/1999| | CITY: BUFFALO REGION: 1 +-----------------------------+ | COUNTY: ERIE STATE: NY |PERSON ORGANIZATION | |LICENSE#: R-77 AGREEMENT: Y |JOHN KINNEMAN R1 | | DOCKET: 05000057 | | +------------------------------------------------+ | | NRC NOTIFIED BY: MARK ADAMS | | | HQ OPS OFFICER: BOB STRANSKY | | +------------------------------------------------+ | |EMERGENCY CLASS: N/A | | |10 CFR SECTION: | | |NINF INFORMATION ONLY | | | | | | | | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | COURTESY CALL DUE TO POWER OUTAGE | | | | The licensee reported that a transformer failure resulted in a power outage | | to the reactor facility. The emergency diesel generator started, but was | | manually stopped due to poor operating performance. Partial power has been | | restored from another building. The licensee anticipates that replacement of | | the transformer could take from three to six weeks. This facility has been | | shut down since 1994. The only required equipment affected by the outage are | | gaseous radiation monitors, which have an allowed outage time of 10 days. | | | | The caller made this report because of possible press interest in the event. | | The local media monitors campus radio transmissions, and the caller | | speculated that transmissions regarding the event could be interpreted by | | the media as a serious event. The licensee may make a press release. | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 36279 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: FERMI REGION: 3 |NOTIFICATION DATE: 10/11/1999| | UNIT: [2] [] [] STATE: MI |NOTIFICATION TIME: 13:07[EDT]| | RXTYPE: [2] GE-4 |EVENT DATE: 10/11/1999| +------------------------------------------------+EVENT TIME: 09:59[EDT]| | NRC NOTIFIED BY: COSEO |LAST UPDATE DATE: 10/11/1999| | HQ OPS OFFICER: CHAUNCEY GOULD +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |JOHN JACOBSON R3 | |10 CFR SECTION: | | |AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION | | |NLCO TECH SPEC LCO A/S | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |2 N Y 97 Power Operation |97 Power Operation | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | VARIOUS SAFETY RELATED EQUIPMENT DECLARED INOPERABLE DUE TO LOSS OF COOLING | | TO THE BATTERY CHARGER ROOM . | | | | Following startup of the Division 2 Residual Heat Removal Service Water | | (RHRSW) pumps, it was observed that the Division 2 Emergency Equipment | | Service Water (EESW) pump was rotating backwards. Division 2 RHRSW flow was | | normal at greater than 9000 gpm. The Division 2 Ultimate Heat Sink (UHS) | | service water systems discharge into a common header that can be routed to | | the Division 2 UHS cooling tower fans or directly to the reservoir. This | | indicates that the Division 2 EESW pump discharge check valve is not fully | | closed. The Division 2 EESW pump control was placed in OFF/RESET (normally | | in AUTO) at 0959 hrs on 10/11/99. The pump discharge valve was closed to | | isolate the flow path and Division 2 EESW has been declared inoperable. This | | results in Division 2 Emergency Equipment Cooling Water (EECW) being | | inoperable. Division 2 EECW provides cooling to the High Pressure Coolant | | Injection (HPCI) pump area cooler during accident conditions. Therefore, the | | HPCI system was declared inoperable(14 day LCO) at 0959 on 10/11/99. HPCI | | remains in standby lineup ready for automatic initiation. The Div 2 EECW | | also provides cooling to the battery charger room. With the batteries | | inoperable they are in an 18 hr LCO. | | | | The check valve internals have been inspected and preliminary findings | | indicate that all parts are intact. The failure of the valve appears to be | | caused by a worn disc pin in the valve. Necessary repairs are in progress. | | | | The Resident Inspector was notified. | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 36280 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: POINT BEACH REGION: 3 |NOTIFICATION DATE: 10/11/1999| | UNIT: [1] [2] [] STATE: WI |NOTIFICATION TIME: 16:56[EDT]| | RXTYPE: [1] W-2-LP,[2] W-2-LP |EVENT DATE: 10/11/1999| +------------------------------------------------+EVENT TIME: 15:14[CDT]| | NRC NOTIFIED BY: HASTINGS |LAST UPDATE DATE: 10/11/1999| | HQ OPS OFFICER: CHAUNCEY GOULD +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |JOHN JACOBSON R3 | |10 CFR SECTION: | | |AOUT 50.72(b)(1)(ii)(B) OUTSIDE DESIGN BASIS | | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N Y 100 Power Operation |100 Power Operation | |2 N Y 100 Power Operation |100 Power Operation | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | FIRE BARRIER WALL NOT MEETING THE LICENSEE'S REQUIRED APPENDIX "R" DESIGN | | BASIS. | | | | IT WAS DISCOVERED THAT A WALL SEGMENT SEPARATING THE CONTROL ROOM FROM THE | | CABLE SPREADING ROOM PROVIDES ONLY A 1.5 HOUR FIRE BARRIER INSTEAD OF THE 3 | | HOUR FIRE BARRIER REQUIRED BY THE LICENSEE'S APPENDIX "R" DESIGN | | COMMITMENTS. THIS PLACES THE WALL SEGMENT OUTSIDE APPENDIX "R" DESIGN | | BASIS. HOURLY FIRE WATCHES ON BOTH SIDES OF THIS WALL WERE ALREADY IN PLACE | | PRIOR TO THIS DISCOVERY AND WILL CONTINUE UNTIL THE PROBLEM IS RESOLVED. | | | | THE RESIDENT INSPECTOR WAS INFORMED. | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 36281 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: PALO VERDE REGION: 4 |NOTIFICATION DATE: 10/11/1999| | UNIT: [] [] [3] STATE: AZ |NOTIFICATION TIME: 19:10[EDT]| | RXTYPE: [1] CE,[2] CE,[3] CE |EVENT DATE: 10/11/1999| +------------------------------------------------+EVENT TIME: 08:40[MST]| | NRC NOTIFIED BY: STROUD |LAST UPDATE DATE: 10/11/1999| | HQ OPS OFFICER: CHAUNCEY GOULD +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |KRISS KENNEDY R4 | |10 CFR SECTION: | | |HFIT 26.73 FITNESS FOR DUTY | | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ | | | | | | |3 N Y 100 Power Operation |100 Power Operation | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | CONTRABAND MATERIAL REPORTED AS A FITNESS-FOR-DUTY ISSUE | | | | CONTRABAND MATERIAL FOUND IN THE VITAL AREA. IMMEDIATE COMPENSATORY | | MEASURES TAKEN UPON DISCOVERY. THE RESIDENT INSPECTOR WAS NOTIFIED. | | | | CONTACT THE HEADQUARTERS OPERATIONS OFFICER FOR ADDITIONAL DETAILS. | +------------------------------------------------------------------------------+
Page Last Reviewed/Updated Thursday, March 25, 2021
Page Last Reviewed/Updated Thursday, March 25, 2021