Event Notification Report for August 24, 1999

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           08/23/1999 - 08/24/1999

                              ** EVENT NUMBERS **

36058  36059  36060  

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36058       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: GINNA                    REGION:  1  |NOTIFICATION DATE: 08/23/1999|
|    UNIT:  [1] [] []                 STATE:  NY |NOTIFICATION TIME: 12:25[EDT]|
|   RXTYPE: [1] W-2-LP                           |EVENT DATE:        08/23/1999|
+------------------------------------------------+EVENT TIME:        11:45[EDT]|
| NRC NOTIFIED BY:  DOUGLAS GOMEZ                |LAST UPDATE DATE:  08/23/1999|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |KATHLEEN MODES       R1      |
|10 CFR SECTION:                                 |                             |
|AOUT 50.72(b)(1)(ii)(B)  OUTSIDE DESIGN BASIS   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| TEAR DISCOVERED IN THE SUCTION BOOT OF THE CONTROL ROOM RETURN AIR FAN       |
|                                                                              |
| "At 1015 on 8/23/99 a tear was discovered in a flexible suction joint to the |
| Control Room Return Air Fan.  This allowed unisolable outside air to be      |
| drawn into the Control Room Air Handling Unit.  A temporary patch was in     |
| place at 1040.  At 1055 the temporary patch was removed and a Temporary      |
| Modification was installed and completed at 1103.                            |
|                                                                              |
| "Further analysis showed that the tear had allowed inleakage of 178 CFM      |
| which exceeded the allowable leak rate of 45 CFM per UFSAR Section 6.4."     |
|                                                                              |
| An investigation will be conducted to determine the cause of the tear.       |
|                                                                              |
| The licensee informed the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36059       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SAINT LUCIE              REGION:  2  |NOTIFICATION DATE: 08/23/1999|
|    UNIT:  [1] [] []                 STATE:  FL |NOTIFICATION TIME: 14:25[EDT]|
|   RXTYPE: [1] CE,[2] CE                        |EVENT DATE:        08/23/1999|
+------------------------------------------------+EVENT TIME:        12:36[EDT]|
| NRC NOTIFIED BY:  JIM HURCHALLA                |LAST UPDATE DATE:  08/23/1999|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |KENNETH BARR         R2      |
|10 CFR SECTION:                                 |                             |
|ARPS 50.72(b)(2)(ii)     RPS ACTUATION          |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     M/R        Y       100      Power Operation  |0        Hot Standby      |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| MANUAL REACTOR TRIP DUE TO LOSS OF MAIN CONDENSER VACUUM                     |
|                                                                              |
| The reactor was manually tripped (all rods inserted) due to low main         |
| condenser vacuum at 1236 EDT.  The cause of the low vacuum is under          |
| investigation and is unknown at this time.  When the trip occurred the 'A'   |
| side non-essential 6.9 kV bus failed to transfer from the auxiliary (plant)  |
| power to startup (offsite) source resulting in the loss of two of four       |
| reactor coolant pumps.  The cause of the failure to transfer is also unknown |
| and under investigation.                                                     |
|                                                                              |
| The plant is stable in hot standby with forced circulation via the remaining |
| two reactor coolant pumps.  Feedwater is via the main feedwater system and   |
| steaming is via the steam bypass system.                                     |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36060       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: MILLSTONE                REGION:  1  |NOTIFICATION DATE: 08/24/1999|
|    UNIT:  [1] [2] [3]               STATE:  CT |NOTIFICATION TIME: 06:52[EDT]|
|   RXTYPE: [1] GE-3,[2] CE,[3] W-4-LP           |EVENT DATE:        08/24/1999|
+------------------------------------------------+EVENT TIME:        06:30[EDT]|
| NRC NOTIFIED BY:  ACKERMAN                     |LAST UPDATE DATE:  08/24/1999|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |KATHLEEN MODES       R1      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(vi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Refueling        |0        Refueling        |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|3     N          Y       100      Power Operation  |100      Power Operation  |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFF SITE NOTIFICATION DUE TO FIRE OUTSIDE OF THE PROTECTED AREA.             |
|                                                                              |
| A FIRE WAS REPORTED AT THE COMPRESSOR OIL SEPARATOR IN THE SWITCHYARD        |
| OUTSIDE THE PROTECTED AREA.  THE FIRE WAS EXTINGUISHED WITHIN 10 MINS WITH   |
| ASSISTANCE FROM OFF SITE FIRE DEPARTMENT.  THE FIRE CONSISTED MOSTLY OF      |
| SMOKE AND SOME FLAMES, BUT THERE WAS NO APPARENT DAMAGE TO THE COMPRESSOR OR |
| SWITCHYARD.  THE STATE DEPARTMENT OF ENVIRONMENTAL PROTECTION AND THE COUNTY |
| WERE NOTIFIED.                                                               |
|                                                                              |
| THE RESIDENT INSPECTOR WILL BE NOTIFIED.                                     |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Wednesday, March 24, 2021