The U.S. Nuclear Regulatory Commission is in the process of rescinding or revising guidance and policies posted on this webpage in accordance with Executive Order 14151 Ending Radical and Wasteful Government DEI Programs and Preferencing, and Executive Order 14168 Defending Women From Gender Ideology Extremism and Restoring Biological Truth to the Federal Government. In the interim, any previously issued diversity, equity, inclusion, or gender-related guidance on this webpage should be considered rescinded that is inconsistent with these Executive Orders.

Event Notification Report for August 18, 1999

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           08/17/1999 - 08/18/1999

                              ** EVENT NUMBERS **

36017  

!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36017       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: MILLSTONE                REGION:  1  |NOTIFICATION DATE: 08/11/1999|
|    UNIT:  [] [2] []                 STATE:  CT |NOTIFICATION TIME: 14:08[EDT]|
|   RXTYPE: [1] GE-3,[2] CE,[3] W-4-LP           |EVENT DATE:        08/11/1999|
+------------------------------------------------+EVENT TIME:        13:53[EDT]|
| NRC NOTIFIED BY:  KEN TRUESDALE                |LAST UPDATE DATE:  08/17/1999|
|  HQ OPS OFFICER:  LEIGH TROCINE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |HAROLD GRAY          R1      |
|10 CFR SECTION:                                 |                             |
|ADEG 50.72(b)(1)(ii)     DEGRAD COND DURING OP  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| DISCOVERY OF A HISTORICAL CONDITION INVOLVING LOW DIESEL GENERATOR VOLTAGE   |
|                                                                              |
| The licensee determined that voltage for the 'B' emergency diesel generator  |
| would not have met the technical specification criteria, and this rendered   |
| the 'B' emergency diesel generator inoperable approximately 32 days prior to |
| 08/05/99.  Although the voltage was discovered to be low during a test run   |
| of the 'B' emergency diesel generator on 08/05/99, it was thought to be      |
| acceptable (satisfactory) at the time of the test run.  However, subsequent  |
| engineering review determined that the voltage was in fact below the         |
| technical specification (TS) acceptance criteria.                            |
|                                                                              |
| The licensee determined this event to be reportable at 1353 on 08/11/99.     |
|                                                                              |
| The licensee notified the NRC resident inspector.                            |
|                                                                              |
| ******************** UPDATE AT 1435 ON 08/17/99 FROM STEPHEN BAKER TO        |
| TROCINE ********************                                                 |
|                                                                              |
| The following text is a portion of a facsimile received from the licensee:   |
|                                                                              |
| "Condition Report M2-99-2179[, 'B' Emergency Diesel Generator Slow Start Did |
| Not Meet TS Acceptance Criteria,'] was written when it was identified that   |
| the output voltage for the "B" emergency diesel generator (EDG) did not meet |
| the TS acceptance criteria, potentially rendering the diesel inoperable."    |
|                                                                              |
| "The original reportability determination for this condition concluded that  |
| this condition was reportable under 10CFR 50.73(a)(2)(i), Technical          |
| Specifications, and 10CFR50.72(b)(1)(ii), Outside Design Basis, based upon   |
| initial investigation of the deficiency.  Accordingly, a prompt report was   |
| issued on 08/11/99 per                                                       |
| 10CFR50.72(b)(1)(ii)."                                                       |
|                                                                              |
| "Upon further investigation of this condition it was determined that while   |
| the voltage requirements of the applicable surveillance procedure were not   |
| met, the requirements of [TS] Surveillance Requirement 4.8.1.1.2.a.2 were    |
| met.  Additionally, it was discovered that the output voltage was set        |
| sufficiently high during the previous month's surveillance such that the EDG |
| would have loaded properly and performed its required safety function(s)     |
| during the period in question."                                              |
|                                                                              |
| "Therefore, this condition is NOT reportable under the requirements of       |
| 10CFR50.73(5)(2)(i), Technical Specifications, or 10CFR50.72(b)(1)(ii),      |
| Outside Design Basis, and it is recommended that the associated prompt       |
| report be retracted."                                                        |
|                                                                              |
| "Based on the above discussion, this is not a condition which is adverse to  |
| safety.  This deficiency was reviewed against the requirements of            |
| 10CFR50.72, 10CFR50.73, [and] 10CFR50.9(b), and [it was] determined to be    |
| not reportable."                                                             |
|                                                                              |
| The licensee notified the NRC resident inspector.  The NRC operations        |
| officer notified the R1DO (Eselgroth).                                       |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Thursday, March 25, 2021