The U.S. Nuclear Regulatory Commission is in the process of rescinding or revising guidance and policies posted on this webpage in accordance with Executive Order 14151 Ending Radical and Wasteful Government DEI Programs and Preferencing, and Executive Order 14168 Defending Women From Gender Ideology Extremism and Restoring Biological Truth to the Federal Government. In the interim, any previously issued diversity, equity, inclusion, or gender-related guidance on this webpage should be considered rescinded that is inconsistent with these Executive Orders.

Event Notification Report for March 17, 1999

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           03/16/1999 - 03/17/1999

                              ** EVENT NUMBERS **

35469  35475  

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35469       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SOUTH TEXAS              REGION:  4  |NOTIFICATION DATE: 03/12/1999|
|    UNIT:  [] [2] []                 STATE:  TX |NOTIFICATION TIME: 19:02[EST]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        03/12/1999|
+------------------------------------------------+EVENT TIME:        14:12[CST]|
| NRC NOTIFIED BY:  TIM FRAWLEY                  |LAST UPDATE DATE:  03/16/1999|
|  HQ OPS OFFICER:  DICK JOLLIFFE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |GARY SANBORN         R4      |
|10 CFR SECTION:                                 |WILLIAM BECKNER, EO  NRR     |
|AESF 50.72(b)(2)(ii)     ESF ACTUATION          |ROSEMARY HOGAN       IRO     |
|NLCO                     TECH SPEC LCO A/S      |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| - PARTIAL LOSS OF OFFSITE POWER DUE TO A FAULT IN A SWITCHYARD CIRCUIT       |
| BREAKER -                                                                    |
|                                                                              |
| AT 1412 CST ON 03/12/99, DURING PLANT SWITCHYARD ACTIVITIES, UNIT 2          |
| EXPERIENCED A LOSS OF POWER TO THE #2 STANDBY TRANSFORMER DUE TO A FAULT IN  |
| A SWITCHYARD CIRCUIT BREAKER.  THIS CONDITION CAUSED TRAIN 'B' AND TRAIN 'C' |
| 4160-VOLT ESF BUSES TO ACTUATE ON A LOSS OF OFFSITE POWER.  THE FOLLOWING    |
| ESF SYSTEMS ACTUATED: TRAIN 'B' AND TRAIN 'C' ESF EDGs, ESSENTIAL COOLING    |
| WATER SYSTEM, ESSENTIAL CHILLED WATER SYSTEM, COMPONENT COOLING WATER        |
| SYSTEM, CONTROL ROOM HVAC SYSTEM, AND AUXILIARY FEEDWATER SYSTEM (ON RECIRC  |
| MODE).                                                                       |
|                                                                              |
| DURING THIS EVENT, THE SPENT FUEL POOL TEMPERATURE INCREASED APPROXIMATELY   |
| 1.5�F, AND THE TRAIN 'B' ESF EDG (#22) OUTPUT BREAKER FAILED TO CLOSE        |
| AUTOMATICALLY.  THE LICENSEE DECLARED THE TRAIN 'B' ESF EDG (#22)            |
| INOPERABLE, EVEN THOUGH IT IS FUNCTIONAL (72-HOUR LCO).                      |
|                                                                              |
| THERE WAS NO FIRE, AND NO PERSONNEL WERE INJURED.  THE LICENSEE RESTORED ALL |
| SYSTEMS TO NORMAL.  UNIT 2 IS STABLE AND OPERATING AT 100% POWER.            |
|                                                                              |
| THE LICENSEE IS INVESTIGATING THE CAUSE OF THE FAULT IN THE SWITCHYARD       |
| CIRCUIT BREAKER AND THE TRAIN 'B' ESF EDG (#22) OUTPUT BREAKER FAILING TO    |
| CLOSE AUTOMATICALLY.                                                         |
|                                                                              |
| THE LICENSEE PLANS TO SUBMIT A LICENSEE EVENT REPORT ON THIS EVENT TO THE    |
| NRC.                                                                         |
|                                                                              |
| THIS EVENT HAD NO IMPACT ON UNIT 1.                                          |
|                                                                              |
| THE NRC RESIDENT INSPECTOR WAS ON SITE DURING THIS EVENT AND REPORTED IT TO  |
| REGION 4.                                                                    |
| REGION 4 PERSONNEL WERE AWARE OF THIS EVENT PRIOR TO THE LICENSEE REPORTING  |
| IT TO THE NRC OPERATIONS OFFICER.                                            |
|                                                                              |
|                                                                              |
| * * * UPDATE AT 1207 ON 03/13/99 FROM TIM FRAWLEY TO JOLLIFFE * * *          |
|                                                                              |
| AT 1412 CST ON 03/12/99, DURING THE LOSS OF POWER TO #2 STANDBY TRANSFORMER, |
| THE LICENSEE ENTERED TECH SPEC 3.0.3 FOR UNIT 2 DUE TO THE LOSS OF POWER TO  |
| TWO 13.8-KV STANDBY BUSES AND THE INOPERABLE CONDITION OF THE TRAIN 'B' ESF  |
| EDG (#22); THIS CONDITION IS NOT COVERED UNDER THE ACTIONS OF TECH SPEC      |
| 3.8.1.1 (AC ELECTRICAL POWER SOURCES).                                       |
|                                                                              |
| AT 1530 CST ON 03/12/99, THE LICENSEE RESTORED POWER TO THE TWO 13.8-KV      |
| STANDBY BUSES.                                                               |
|                                                                              |
| AT 1553 CST ON 03/12/99, THE LICENSEE EXITED TECH SPEC 3.0.3 FOLLOWING       |
| SATISFACTORY PERFORMANCE OF SURVEILLANCE REQUIREMENT 4.8.1.1.1.a.  THIS      |
| CONDITION IS REPORTABLE TO THE NRC UNDER SECTION 2.G OF FACILITY OPERATING   |
| LICENSE NPF-80.                                                              |
|                                                                              |
| UNIT 2 IS STABLE AND OPERATING AT 100% POWER.                                |
|                                                                              |
| THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.  THE NRC OPERATIONS        |
| OFFICER NOTIFIED THE R4DO (GARY SANBORN), NRR EO (BILL BECKNER), AND IRO MGR |
| (ROSEMARY HOGAN).                                                            |
|                                                                              |
| * * * UPDATE 1916 3/16/99 FROM MERTINK TAKEN BY STRANSKY * * *               |
|                                                                              |
| "ON 3/12/99 STANDBY DIESEL GENERATOR 22 AUTO STARTED IN RESPONSE TO A LOSS   |
| OF OFFSITE POWER TO THE 4.15 kV ENGINEERED SAFETY FEATURES BUS (ESF) E2B.    |
| THE DIESEL GENERATOR OUTPUT BREAKER FAILED TO AUTOMATICALLY CLOSE.           |
| OPERATIONS PERSONNEL MANUALLY CLOSED THE OUTPUT BREAKER USING THE REMOTE     |
| HANDSWITCH IN THE CONTROL ROOM AND ENERGIZED THE ENGINEERED SAFETY FEATURES  |
| BUS. DURING THE TROUBLESHOOTING OF THIS EVENT IT WAS DETERMINED THAT THE     |
| CELL SWITCH IN E2B 480 VOLT LOAD CENTER CUBICLE 3F FOR ESSENTIAL CHILLER 216 |
| WAS FOUND TO BE IN DEGRADED CONDITION. THIS FUNCTION OF THIS CELL SWITCH IS  |
| TO ALLOW THE SEQUENCER TO RECOGNIZE THE BREAKER AS OPEN AND PERFORM THE      |
| REQUIRED SEQUENCING OF ESF LOADS, STARTING WITH THE CLOSING OF THE DIESEL    |
| GENERATOR OUTPUT BREAKER. THIS BREAKER HAD BEEN RACKED OUT SINCE 2/28/99 FOR |
| MAINTENANCE ON THE CHILLER.                                                  |
|                                                                              |
| "SINCE THE PERFORMANCE OF RACKING OUT THIS BREAKER DID NOT VERIFY CELL       |
| SWITCH OPERATION AS DIRECTED BY OPERATING PROCEDURES, DIESEL GENERATOR 22    |
| WAS INOPERABLE SINCE THE RACKING OUT OF THE CHILLER BREAKER ON 2/28/99. WITH |
| THIS DIESEL GENERATOR INOPERABLE, TECHNICAL SPECIFICATIONS REQUIRE           |
| PERFORMANCE OF CONDITIONAL SURVEILLANCES FOR VERIFICATION OF OPERABILITY OF  |
| AC OFFSITE SOURCES. SINCE THIS TECHNICAL SPECIFICATION REQUIREMENT WAS NOT   |
| SATISFIED, THIS EVENT IS REPORTABLE AS A CONDITION PROHIBITED BY TECHNICAL   |
| SPECIFICATIONS AND NOTIFICATION IS MADE PER NPF-80, SECTION 2G."             |
|                                                                              |
| The NRC resident inspector has been informed of this update by the licensee. |
| Notified R4DO (Harrell).                                                     |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35475       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: ROBINSON                 REGION:  2  |NOTIFICATION DATE: 03/16/1999|
|    UNIT:  [2] [] []                 STATE:  SC |NOTIFICATION TIME: 01:20[EST]|
|   RXTYPE: [2] W-3-LP                           |EVENT DATE:        03/15/1999|
+------------------------------------------------+EVENT TIME:        22:12[EST]|
| NRC NOTIFIED BY:  DAVID COOK                   |LAST UPDATE DATE:  03/16/1999|
|  HQ OPS OFFICER:  LEIGH TROCINE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |EDWARD MCALPINE      R2      |
|10 CFR SECTION:                                 |                             |
|NINF                     INFORMATION ONLY       |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| COURTESY NOTIFICATION REGARDING A FATALITY WITHIN THE OWNER CONTROLLED AREA  |
| OUTSIDE THE 1,400-FOOT BARRIER                                               |
|                                                                              |
| The following text is a portion of a facsimile received from the licensee:   |
|                                                                              |
| "At approximately 2212 on 03/15/99, Robinson Security [personnel] notified   |
| the Control Room of an automobile with a fatality on the West Entrance Road  |
| access to the plant outside the site boundary.  The cause of the fatality is |
| unknown, and this occurrence is being investigated by local law enforcement  |
| agencies and the State Law Enforcement Division.  Due to the fatality        |
| occurring off-site, but on CP&L property adjacent to the site boundary, and  |
| [due to] the interaction of several off-site agencies responding to the      |
| scene, the NRC Operations Center is being notified as a courtesy.  This call |
| is for informational purposes only and does not fall within the reporting    |
| criteria of 10 CFR 50.72."                                                   |
|                                                                              |
| The licensee notified the NRC resident inspector.  The licensee does not     |
| plan to issue a press release.                                               |
+------------------------------------------------------------------------------+
