The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.
Event Notification Report for January 25, 1999
U.S. Nuclear Regulatory Commission
Operations Center
Event Reports For
01/22/1999 - 01/25/1999
** EVENT NUMBERS **
35197 35297 35298 35299 35300 35301 35302 35303 35304 35305 35306 35307
35308 35309 35310 35311
!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 35197 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: LIMERICK REGION: 1 |NOTIFICATION DATE: 12/27/1998|
| UNIT: [] [2] [] STATE: PA |NOTIFICATION TIME: 17:43[EST]|
| RXTYPE: [1] GE-4,[2] GE-4 |EVENT DATE: 12/27/1998|
+------------------------------------------------+EVENT TIME: 14:30[EST]|
| NRC NOTIFIED BY: JOHN HUNTER |LAST UPDATE DATE: 01/22/1999|
| HQ OPS OFFICER: LEIGH TROCINE +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |JOHN WHITE R1 |
|10 CFR SECTION: | |
|AINA 50.72(b)(2)(iii)(A) POT UNABLE TO SAFE SD | |
|AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION | |
|NLCO TECH SPEC LCO A/S | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
| | |
|2 N Y 100 Power Operation |100 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| HIGH PRESSURE COOLANT INJECTION (HPCI) DECLARED INOPERABLE DURING |
| SURVEILLANCE TESTING DUE TO LOW LUBE OIL PRESSURES. |
| |
| The following text is a portion of a facsimile received from the licensee: |
| |
| "Unit 2 HPCI was secured and declared inoperable after being placed in |
| service for a regularly scheduled surveillance test. During performance of |
| the pump, valve, and flow test, a lube oil pressure alarm annunciated due to |
| low lube oil pressures in various points throughout the system. All other |
| parameters were normal, and the system was operating properly. HPCI was |
| then secured, and a normal shutdown of the system was achieved. No other |
| abnormalities were identified throughout the entire evolution. |
| Investigation continues as to the cause of the low lube oil pressure |
| alarm." |
| |
| The unit was placed in a 14-day technical specification limiting condition |
| for operation as a result of this issue. |
| |
| The licensee plans to notify the NRC resident inspector. |
| |
| *** RETRACTION OF EVENT ON 01/22/99 AT 1418 EST FROM TONKINSON TAKEN BY |
| MacKINNON *** |
| |
| During surveillance testing of the Unit 2 HPCI system on 12/27/98, a low oil |
| pressure alarm was received in the control room. Lube oil pressure was |
| observed to be below the recommended value on a local pressure gauge at one |
| location. The low oil pressure was on a section of piping that supplies |
| lube oil to the governor end bearing only. All other system parameters were |
| normal, and surveillance testing acceptance criteria were satisfied. The |
| system was declared inoperable at that time. |
| |
| The ball valve supplying lube oil to the affected portion of piping was |
| removed, cleaned, and re-installed. Other lube oil system inspections |
| occurred. The lube oil was analyzed, and there was no evidence of bearing |
| degradation. |
| |
| Subsequent engineering analysis, with support from the turbine and bearing |
| manufacturers, concluded that the as-found oil pressure was sufficient to |
| supply lube oil to the governor end bearing indefinitely. No bearing damage |
| would be expected with operation at the observed oil pressure. The as-found |
| condition would not adversely affect the capability of the HPCI system to |
| fulfill safety-related functions. The HPCI system, therefore, was not |
| inoperable due to as-found lube oil pressure condition. |
| |
| The NRC resident inspector was notified of this retraction by the licensee. |
| The R2DO (Costello) was notified by the NRC operations officer. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 35297 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: DIABLO CANYON REGION: 4 |NOTIFICATION DATE: 01/22/1999|
| UNIT: [1] [2] [] STATE: CA |NOTIFICATION TIME: 00:59[EST]|
| RXTYPE: [1] W-4-LP,[2] W-4-LP |EVENT DATE: 01/21/1999|
+------------------------------------------------+EVENT TIME: 18:25[PST]|
| NRC NOTIFIED BY: JOSEPHINE BROWN |LAST UPDATE DATE: 01/22/1999|
| HQ OPS OFFICER: BOB STRANSKY +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |DALE POWERS R4 |
|10 CFR SECTION: | |
|NINF INFORMATION ONLY | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
|2 N Y 100 Power Operation |100 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| This notification is a courtesy call regarding a safeguards system |
| degradation related to a computer. Compensatory measures were taken |
| immediately upon discovery. (Refer to the HOO log for additional details.) |
| |
| The NRC resident inspector will be informed of this notification by the |
| licensee. |
| |
| *** UPDATE ON 01/22/99 AT 1430 EST FROM ART WELLS TAKEN BY MacKINNON *** |
| |
| After further review, the licensee made this a loggable report. The |
| secondary alarm system is back in service. |
| |
| The NRC resident Inspector will be notified of this event update by the |
| licensee. The R4DO (Powers) was notified by the NRC operations officer. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 35298 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: INDIAN POINT REGION: 1 |NOTIFICATION DATE: 01/22/1999|
| UNIT: [] [3] [] STATE: NY |NOTIFICATION TIME: 09:38[EST]|
| RXTYPE: [2] W-4-LP,[3] W-4-LP |EVENT DATE: 01/22/1999|
+------------------------------------------------+EVENT TIME: 09:15[EST]|
| NRC NOTIFIED BY: C. KOCSIS |LAST UPDATE DATE: 01/22/1999|
| HQ OPS OFFICER: BOB STRANSKY +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |FRANK COSTELLO R1 |
|10 CFR SECTION: | |
|AOUT 50.72(b)(1)(ii)(B) OUTSIDE DESIGN BASIS | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
| | |
|3 N Y 100 Power Operation |100 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| SINGLE FAILURE COULD PREVENT COMPLETE CONTAINMENT ISOLATION DURING VENTING |
| (Refer to event #35301 for a similar event on Unit 2.) |
| |
| The following text is a portion of a facsimile received from the licensee: |
| |
| "At approximately 0915 hours on January 22, 1999, it was determined that |
| during containment pressure relief, the containment isolation function could |
| not be completely achieved if there [was] a containment isolation signal, |
| coupled with the single failure of containment isolation valve VS-PCV-1190 |
| to close. This would occur since initiation of pressure relief results in |
| three-way valve PS-SOV-1280 (a one-inch valve with one-inch ports on the |
| weld channel supply line between VS-PCV-1190 and VS-PCV-1191) changing |
| position to isolate [the] weld channel and vent the line between the |
| containment isolation valves (VS-PCV-1190 and VS-PCV-1191) to atmosphere. |
| If a postulated event were to occur that resulted in a containment isolation |
| signal, VS-PCV-1190 must close before an interlock with PS-SOV-1280 would |
| allow that valve to change position and supply weld channel gas between the |
| containment isolation valves. Thus, during pressure relief, a single |
| failure of VS-PCV-1190 to close on a containment isolation signal could |
| result in a one-inch vent path. Immediate corrective action was taken to |
| administratively restrict containment pressure relief until corrective |
| action to assure containment integrity during containment pressure relief |
| can be established such as isolation using an installed weld channel manual |
| isolation valve. This is a condition that resulted, during past containment |
| pressure relief operations, in Indian Point 3 being outside the plant design |
| basis for containment isolation." |
| |
| The NRC resident inspector has been informed of this notification by the |
| licensee. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Other Nuclear Material |Event Number: 35299 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: U.S. ARMY |NOTIFICATION DATE: 01/22/1999|
|LICENSEE: U.S. ARMY |NOTIFICATION TIME: 09:48[EST]|
| CITY: FT. SHAFTER REGION: 4 |EVENT DATE: 01/21/1999|
| COUNTY: STATE: HI |EVENT TIME: [HST]|
|LICENSE#: 12-00722-06 AGREEMENT: N |LAST UPDATE DATE: 01/22/1999|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |ROGER LANKSBURY R3 |
| |DONALD COOL NMSS |
+------------------------------------------------+DALE POWERS R4 |
| NRC NOTIFIED BY: J. HAVENNER | |
| HQ OPS OFFICER: BOB STRANSKY | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|IBBF 30.50(b)(2)(ii) EQUIP DISABLED/FAILS | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| EXCESSIVE SURFACE CONTAMINATION OF SEALED SOURCE |
| |
| The U.S. Army Radioisotope Committee, located in Rock Island, IL, reported |
| the following incident that occurred at Fort Shafter, HI. Wipe tests of a |
| chemical agent monitor containing a 10-mCi Ni-63 source indicate that the |
| sealed source is leaking. Count rates of up to 17,586 dpm/100 cmďż˝ were |
| recorded. The device has been removed from service. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 35300 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: THREE MILE ISLAND REGION: 1 |NOTIFICATION DATE: 01/22/1999|
| UNIT: [1] [] [] STATE: PA |NOTIFICATION TIME: 10:06[EST]|
| RXTYPE: [1] B&W-L-LP,[2] B&W-L-LP |EVENT DATE: 01/22/1999|
+------------------------------------------------+EVENT TIME: 09:30[EST]|
| NRC NOTIFIED BY: JOHN SCHORK |LAST UPDATE DATE: 01/22/1999|
| HQ OPS OFFICER: BOB STRANSKY +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |FRANK COSTELLO R1 |
|10 CFR SECTION: | |
|AOUT 50.72(b)(1)(ii)(B) OUTSIDE DESIGN BASIS | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |100 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| BORIC ACID SYSTEM PIPING MAY NOT BE MAINTAINED AT PROPER TEMPERATURE. |
| |
| The following text is a portion of a facsimile received from the licensee: |
| |
| "CA-P-1A/B discharge piping heat trace is not maintaining adequate |
| temperatures. FSAR sec 9.2.1.2 states, 'Further, all piping, pumps, and |
| valves associated with the boric acid mix tank and the reclaimed boric acid |
| storage tanks to transport boric acid solution from them to the makeup and |
| purification system are provided with redundant electrical heat tracing to |
| ensure that the boric acid solution will be maintained 10 [ďż˝]F or more above |
| its crystallization temperature. The electrical heat tracing is controlled |
| by the temperature of the external surface of the piping systems.' |
| Temperature readings on the surface of the pipe ranged between 97.4 [ďż˝]F and |
| 171 [ďż˝]F. The heat trace setpoints are 160 [ďż˝]F. Based on recent chemistry |
| samples as high as 17,400 ppm and the crystallization curve, Figure 1A in OP |
| 1104-47B, the required temperature to prevent crystallization would be 117 |
| [ďż˝]F. Adding 10 [ďż˝]F would require a minimum 127 [ďż˝]F for the boric acid |
| solution." |
| |
| "The heat trace requirement is to ensure the boron does not crystallize and |
| prevent flow to the makeup tank. Quarterly [in-service] testing is performed |
| for CA-P-1A/B (most recently in November 1998). Although the required |
| solution temperature may not be being maintained, testing has shown that |
| these lines are not blocked and are functioning." |
| |
| "Because the temperature of the boric acid solution within the subject |
| piping cannot be confirmed via direct measurement or analysis at this time |
| to be at or above 127 [ďż˝]F, this condition has been identified as being |
| potentially outside the design basis of the plant and was reported to the |
| NRC within 1 hour in accordance with the requirements of 10 CFR |
| 50.72(a)(2)(ii)." |
| |
| "The chemical addition system pumps are currently out of service due to |
| maintenance being performed on the system, unrelated to the heat tracing. |
| The system in-service test is planned to be performed when the system is |
| returned to service. The chemical addition system in-service test performed |
| last November found the system performed as required at that time." |
| |
| "An analysis is planned to be performed to determine if the temperature of |
| the boric acid solution within the chemical addition system piping is at or |
| above the specified temperature." |
| |
| "Plans are underway to install, if necessary, additional insulation and, if |
| necessary heat tracing, to ensure the fluid temperature is maintained at the |
| correct temperature." |
| |
| "The potential outside design basis condition has been documented in CAP |
| T1999-0052 via the GPU Nuclear, Appendix B, corrective action program." |
| |
| The NRC resident inspector was notified of this event by the licensee. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 35301 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: INDIAN POINT REGION: 1 |NOTIFICATION DATE: 01/22/1999|
| UNIT: [2] [] [] STATE: NY |NOTIFICATION TIME: 12:43[EST]|
| RXTYPE: [2] W-4-LP,[3] W-4-LP |EVENT DATE: 01/22/1999|
+------------------------------------------------+EVENT TIME: 12:10[EST]|
| NRC NOTIFIED BY: DENNIS CORNAX |LAST UPDATE DATE: 01/22/1999|
| HQ OPS OFFICER: STEVE SANDIN +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |FRANK COSTELLO R1 |
|10 CFR SECTION: | |
|AOUT 50.72(b)(1)(ii)(B) OUTSIDE DESIGN BASIS | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2 N Y 99 Power Operation |99 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| SINGLE FAILURE COULD PREVENT COMPLETE CONTAINMENT ISOLATION DURING VENTING. |
| |
| The following text is a portion of a facsimile received from the licensee: |
| |
| "At approximately 12:10 hours on January 22, 1999, it was determined that |
| during containment pressure relief, the containment isolation function could |
| not be completely achieved if there [was] a containment isolation signal, |
| coupled with the single failure of containment isolation valve PCV-1190 to |
| close. The potential for this to occur exists since initiation of pressure |
| relief results in three-way solenoid valve SOV-1280 (a one-inch valve with |
| ports on [the] weld channel supply line between PCV-1190 and PCV-1191) |
| changing position to isolate [the] weld channel and vent the line between |
| the containment isolation valves (PCV-1190 and PCV-1191) to atmosphere. If |
| a postulated accident event were to occur that resulted in a containment |
| isolation signal, PCV-1190 must close before an interlock with SOV-1280 |
| would allow that valve to change position and supply weld channel gas |
| between the containment isolation valves. Thus, during the pressure relief, |
| a single failure of PCV-1190 to close on a containment isolation signal |
| could result in a one-inch vent path, which would be a monitored release |
| path and filtered by the [primary auxiliary building] exhaust system." |
| |
| "Immediate corrective action taken will administratively require the closure |
| of a manual valve ( PCV-1110-8) any time that PCV-1190 is in the open |
| position thereby precluding a pathway for [the] containment atmosphere to |
| communicate with the environment." |
| |
| This condition was discovered in response to an event reported by Indian |
| Point 3. (Refer to event #35298 for additional information.) The licensee |
| is continuing its evaluation to identify any other primary containment |
| isolation valves which may be affected. |
| |
| The licensee informed the NRC resident inspector. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Fuel Cycle Facility |Event Number: 35302 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PORTSMOUTH GASEOUS DIFFUSION PLANT |NOTIFICATION DATE: 01/22/1999|
| RXTYPE: URANIUM ENRICHMENT FACILITY |NOTIFICATION TIME: 13:28[EST]|
| COMMENTS: 2 DEMOCRACY CENTER |EVENT DATE: 01/22/1999|
| 6903 ROCKLEDGE DRIVE |EVENT TIME: 09:30[EST]|
| BETHESDA, MD 20817 (301)564-3200 |LAST UPDATE DATE: 01/22/1999|
| CITY: PIKETON REGION: 3 +-----------------------------+
| COUNTY: PIKE STATE: OH |PERSON ORGANIZATION |
|LICENSE#: GDP-2 AGREEMENT: N |ROGER LANKSBURY R3 |
| DOCKET: 0707002 |DON COOL, NMSS EO |
+------------------------------------------------+FRANK CONGEL IRO |
| NRC NOTIFIED BY: KEITH WILLIAMSON | |
| HQ OPS OFFICER: JOHN MacKINNON | |
+------------------------------------------------+ |
|EMERGENCY CLASS: | |
|10 CFR SECTION: | |
|NBNL RESPONSE-BULLETIN | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| FAILURE TO IMPLEMENT AN NCSA IN BUILDING X-326 BECAUSE THERE WAS NO |
| PROCEDURE FOR OPERATION OF CALIBRATION BUGGIES |
| |
| This event was reported per NRC Bulletin 91-01 as a 4-hour notification. |
| |
| The following text is a portion of a facsimile received from Portsmouth: |
| |
| "On 01/22/1999 at 0930 hours during the on-going plant-wide search for |
| abandoned equipment, three (3) calibration buggies (all of different design) |
| were discovered in the X-326 [process building] building which may meet the |
| fissile material limits. All three (3) buggies meet the requirements of |
| NCSA-Plant069; but the NCSA was not implemented in the X-326 building |
| because there was not a procedure for operation of the calibration buggies. |
| The identified equipment has had a boundary set up around them, and the |
| anomalous NCS condition report is complete." |
| |
| "Spacing and geometry of the components on the buggies were controlled such |
| that the requirements of Plant069 were met." |
| |
| "The calibration buggies found do not violate the requirements of |
| NCSA-Plant069. The problem was the failure to flow down the requirements of |
| the NCSA into a procedure for the operation of the buggies. The problem was |
| in the implementation of the NCSA. The NCSA states that it is for use in |
| building X-326, but [it] was never implemented in that building." |
| |
| The NRC resident inspector was notified of this event by the certificate |
| holder. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 35303 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: LIMERICK REGION: 1 |NOTIFICATION DATE: 01/22/1999|
| UNIT: [] [2] [] STATE: PA |NOTIFICATION TIME: 14:53[EST]|
| RXTYPE: [1] GE-4,[2] GE-4 |EVENT DATE: 01/22/1999|
+------------------------------------------------+EVENT TIME: 14:00[EST]|
| NRC NOTIFIED BY: Glenn H. Stewart |LAST UPDATE DATE: 01/22/1999|
| HQ OPS OFFICER: JOHN MacKINNON +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |FRANK COSTELLO R1 |
|10 CFR SECTION: | |
|AOUT 50.72(b)(1)(ii)(B) OUTSIDE DESIGN BASIS | |
|NLTR LICENSEE 24 HR REPORT | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
| | |
|2 N Y 100 Power Operation |100 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| DISCOVERY THAT A FIRE INDUCED FAULT COULD IMPACT EQUIPMENT REQUIRED FOR SAFE |
| SHUTDOWN |
| |
| The following text is a portion of a facsimile received from the licensee: |
| |
| "On 01/21/99, at 1545 hours, an Engineering review determined that in the |
| event of a fire in Fire Area 64, 'Reactor Enclosure Cooling Water Equipment |
| Area,' a fire induced fault in the 480-VAC power cable to the 2B Reactor |
| Enclosure Cooling Water (RECW) pump motor could open the load center (LC) |
| breaker to its associated motor control center (MCC) which would impact |
| equipment required for safe shutdown in the event of a fire in that area. |
| At that time, it was believed that this situation could only occur if the 2B |
| RECW pump was operating at the time of the fire. The 2B RECW pump currently |
| is not operating. This condition is due to less than adequate circuit |
| breaker coordination which is limited to a small region on the time-current |
| coordination curve for the LC breaker and the MCC breaker. On 01/22/99, at |
| 1400 hours, further investigation revealed that fire-induced damage to an |
| auto-start pressure switch in the control circuit for the 2B RECW pump |
| located in the affected fire area could create a hot short that would cause |
| the pump to auto-start resulting in the identified impact on safe shutdown |
| equipment. This represents a condition that is outside the design basis of |
| the plant and is reportable as a 1-hour notification in accordance with |
| 10CFR50.72(b)(1)(ii)(B). This condition is also considered a noncompliance |
| with the Fire Protection Program as described in the Limerick Generating |
| Station (LGS) Updated Final Safety Analysis Report (UFSAR), Section |
| 9A.6.1.1, and is reportable as a violation of LGS, Unit 2, Operating License |
| Condition 2.C.(3), 'Fire Protection.' Accordingly, this notification is |
| also being made within 24 hours as required by LGS, Unit 2, Operating |
| License Condition 2.E. This condition has existed since June 22, 1989, the |
| date of issuance of the Low Power Operating License for LGS, Unit 2. This |
| condition does not effect the operability of the 2B RECW pump or the |
| affected MCC based on the application of single failure criterion which |
| limits an electrical failure to a single division of safety-related power. |
| A fire watch has been established in the affected fire area as an |
| appropriate compensatory measure." |
| |
| The licensee notified the NRC resident inspector. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|General Information or Other |Event Number: 35304 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: INTEGRATED RESOURCES, INC. |NOTIFICATION DATE: 01/22/1999|
|LICENSEE: BARKER MICORFARADAS, INC |NOTIFICATION TIME: 15:20[EST]|
| CITY: Nebraska City REGION: 4 |EVENT DATE: 01/22/1999|
| COUNTY: STATE: NE |EVENT TIME: 14:20[CST]|
|LICENSE#: AGREEMENT: Y |LAST UPDATE DATE: 01/22/1999|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |DALE POWERS R4 |
| |FRANK COSTELLO R1 |
+------------------------------------------------+ROGER LANKSBURY R3 |
| NRC NOTIFIED BY: JOHN BROSEMER |VERN HODGE NRR |
| HQ OPS OFFICER: JOHN MacKINNON | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|CCCC 21.21 UNSPECIFIED PARAGRAPH | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| PRELIMINARY NOTIFICATION BY INTEGRATED RESOURCES OF 10-CFR-PART-21 |
| NOTIFICATION |
| |
| INTEGRATED RESOURCES, INC., CALLED TO MAKE A PRELIMINARY NOTIFICATION OF |
| INTENT TO ISSUE A 10-CFR-PART-21 NOTIFICATION ON THEMSELVES. DRESDEN |
| STATION SENT SQUARE ROOT CONVERTERS (DRESDEN STATION HAS ABOUT 100 OF THESE |
| SQUARE ROOT CONVERTERS) TO INTEGRATED RESOURCES, INC., FOR FAILURE ANALYSIS |
| BECAUSE AFTER ABOUT 5 YEARS OF USE, THESE SQUARE ROOT CONVERTERS START TO |
| FAIL. ALL THE SQUARE ROOT CONVERTERS ARE NON-SAFETY RELATED. NINE (9) OF |
| THE SQUARE ROOT CONVERTERS WERE TESTED. FAILURE ANALYSIS DETERMINED THAT |
| ALL FIVE (5) OF THE ALUMINUM ELECTROLYTIC CAPACITORY SPARGUE ELECTRIC CO. |
| (MODEL #TE1302 WITH MANUFACTURE DATE CODE OF 9322H) FAILED. ALL THE OTHER |
| SQUARE ROOT CONVERTERS' FAILURE POINT IS WHERE THE SQUARE ROOT CONVERTER |
| COULD NOT BE CALIBRATED PROPERLY. THE SQUARE ROOT CONVERTERS ARE BEING SENT |
| BACK TO THEIR MANUFACTURER (BARKER MICROFARADS, INC., LOCATED IN HILLSVILLE, |
| VA) TO DETERMINE THE FAILURE MECHANISM OF THE SQUARE ROOT CONVERTERS. |
| INTEGRATE RESOURCES, INC., STATED THAT THEY EXPECTED THE RESULTS OF THE |
| FAILURE MECHANISM OF THE SQUARE ROOT CONVERTS TO BE SENT TO THEM NEXT WEEK. |
| |
| |
| INTEGRATED RESOURCES, INC., SAID THAT NINE MILE POINT UNIT 1 HAS ONE |
| SAFETY-RELATED SQUARE ROOT CONVERTER AND ONE SAFETY-RELATED FUNCTION |
| GENERATOR AND THAT FITZPATRICK HAS TWO SAFETY-RELATED BASIC CONTROLLERS. |
| THESE TWO NUCLEAR POWER PLANTS WILL BE NOTIFIED OF THE POTENTIAL FAILURE OF |
| THESE DEVICES. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Other Nuclear Material |Event Number: 35305 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: TEXAS DEPARTMENT OF HEALTH |NOTIFICATION DATE: 01/22/1999|
|LICENSEE: TECHNICAL WELDING |NOTIFICATION TIME: 16:00[EST]|
| CITY: PASADENA REGION: 4 |EVENT DATE: 01/21/1999|
| COUNTY: STATE: TX |EVENT TIME: [CST]|
|LICENSE#: L02187 AGREEMENT: Y |LAST UPDATE DATE: 01/22/1999|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |DALE POWERS R4 |
| | |
+------------------------------------------------+ |
| NRC NOTIFIED BY: HELEN WATKINS | |
| HQ OPS OFFICER: JOHN MacKINNON | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|NAGR AGREEMENT STATE | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| EXPOSURE GREATER THAN TEDE OF 5 REM (Refer to event #35306 for a similar |
| event.) |
| |
| THE FOLLOWING INFORMATION WAS RECEIVED VIA FACSIMILE TO THE NRC OPERATION |
| CENTER FROM THE TEXAS DEPARTMENT OF HEALTH BUREAU OF RADIATION CONTROL |
| (TDH-BRC) AS AN AGREEMENT STATE REPORT: |
| |
| "INCIDENT #7411 - TECHNICAL WELDING, PASADENA, TX, L02187, NOTIFIED TDH-BRC |
| OF A 5.5-R 1998 ANNUAL EXPOSURE TO A RADIOGRAPHER. 4.560 R WAS [RECEIVED] |
| DURING THE 12/98 MONITORING PERIOD. THE LICENSEE RECEIVED A VERBAL REPORT |
| FROM THE BADGE PROCESSOR ON 01/21/99. THE TDH-BRC IS INVESTIGATING." |
| |
| THERE WAS NO ADDITIONAL INFORMATION AVAILABLE ON THE FACSIMILE. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Other Nuclear Material |Event Number: 35306 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG: TEXAS DEPARTMENT OF HEALTH |NOTIFICATION DATE: 01/22/1999|
|LICENSEE: TECHNICAL WELDING |NOTIFICATION TIME: 16:00[EST]|
| CITY: PASADENA REGION: 4 |EVENT DATE: 01/20/1999|
| COUNTY: STATE: TX |EVENT TIME: [CST]|
|LICENSE#: L02187 AGREEMENT: Y |LAST UPDATE DATE: 01/22/1999|
| DOCKET: |+----------------------------+
| |PERSON ORGANIZATION |
| |DALE POWERS R4 |
| | |
+------------------------------------------------+ |
| NRC NOTIFIED BY: HELEN WATKINS | |
| HQ OPS OFFICER: JOHN MacKINNON | |
+------------------------------------------------+ |
|EMERGENCY CLASS: N/A | |
|10 CFR SECTION: | |
|NAGR AGREEMENT STATE | |
| | |
| | |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| EXPOSURE GREATER THAN TEDE OF 5 REM (Refer to event #35305 for a similar |
| event.) |
| |
| THE FOLLOWING INFORMATION WAS RECEIVED VIA FACSIMILE TO THE NRC OPERATION |
| CENTER FROM THE TEXAS DEPARTMENT OF HEALTH BUREAU OF RADIATION CONTROL |
| (TDH-BRC) AS AN AGREEMENT STATE REPORT: |
| |
| "INCIDENT #7410 - TECHNICAL WELDING, PASADENA, TX, L02187, NOTIFIED THE |
| TDH-BRC OF A 5.2-R 1998 ANNUAL EXPOSURE TO A RADIOGRAPHER. THE DOSE DURING |
| THE [3] MONTHS OF THE YEAR RESULTED FROM CALCULATED ASSESSMENTS. THE BADGES |
| WERE LOST. THE LICENSEE CONFIRMED THE OVEREXPOSURE ON 01/20/99. THE |
| TDH-BRC IS INVESTIGATING." |
| |
| THERE WAS NO ADDITIONAL INFORMATION AVAILABLE ON THE FACSIMILE. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 35307 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: RIVER BEND REGION: 4 |NOTIFICATION DATE: 01/22/1999|
| UNIT: [1] [] [] STATE: LA |NOTIFICATION TIME: 18:11[EST]|
| RXTYPE: [1] GE-6 |EVENT DATE: 01/22/1999|
+------------------------------------------------+EVENT TIME: 16:17[CST]|
| NRC NOTIFIED BY: RUSS GODWIN |LAST UPDATE DATE: 01/22/1999|
| HQ OPS OFFICER: JOHN MacKINNON +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |DALE POWERS R4 |
|10 CFR SECTION: | |
|AARC 50.72(b)(1)(v) OTHER ASMT/COMM INOP | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 95 Power Operation |95 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| EMERGENCY PAGING SYSTEM AND INTERNAL TELEPHONE SYSTEM ARE INOPERABLE. |
| |
| For unknown reason at this time, the emergency paging system and the plant's |
| internal telephone system became inoperable at 1617 EST. The emergency |
| paging system is used to call plant personnel to the plant in case there is |
| an emergency. The automatic telephone system is operable, and it can |
| automatically call plant personnel if they are needed. The licensee can |
| call offsite, and the ENS (emergency notification system) telephone system |
| is fully operable. The licensee said that they own the emergency paging |
| system, and they are presently troubleshooting the system. |
| |
| The NRC resident inspector will be notified of this event notification. |
| |
| *** UPDATE ON 01/22/99 AT 2001 EST FROM RICK TAKEN BY MacKINNON *** |
| |
| The emergency paging system and the plant's internal telephone system were |
| returned to service at 1840 CST. |
| |
| The NRC resident inspector was notified of this update by the licensee. The |
| R4DO (Powers) was notified by the NRC operations officer. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 35308 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: POINT BEACH REGION: 3 |NOTIFICATION DATE: 01/22/1999|
| UNIT: [1] [] [] STATE: WI |NOTIFICATION TIME: 19:10[EST]|
| RXTYPE: [1] W-2-LP,[2] W-2-LP |EVENT DATE: 01/22/1999|
+------------------------------------------------+EVENT TIME: 17:59[CST]|
| NRC NOTIFIED BY: RICK ROBBINS |LAST UPDATE DATE: 01/22/1999|
| HQ OPS OFFICER: JOHN MacKINNON +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |ROGER LANKSBURY R3 |
|10 CFR SECTION: |WILLIAM BATEMAN NRR |
|ASHU 50.72(b)(1)(i)(A) PLANT S/D REQD BY TS |FRANK CONGEL IRO |
|NLCO TECH SPEC LCO A/S | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 N Y 100 Power Operation |95 Power Operation |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| TECHNICAL SPECIFICATION SHUTDOWN DUE TO WESTINGHOUSE BREAKER CONCERNS |
| |
| Due to 4160-Volt Westinghouse 50-DH-350 breaker concerns on the Unit 1 |
| reactor coolant pumps, Technical Specification 15.3.5.-2.14.b and Technical |
| Specification 15.3.5-2.16, items a and b, were entered, and this requires |
| Unit 1 to be in a Hot Shutdown condition within 8 hours from 1600 CST. The |
| licensee said that this concern was part of a Ginna event sent out for |
| Westinghouse review. The licensee believes there is a laminated plate in |
| the shoot of the breaker that has a varnish which is holding the laminated |
| plates on. At this point, there is a concern about the operability of the |
| breakers. The laminated plates have been found to degrade over time, and |
| these plates can slide down and prevent the breakers from opening/closing. |
| Reactor coolant pumps, main feedwater pumps, and the '1A05' emergency bus |
| have the Westinghouse 50-DH-350 breakers. |
| |
| The only emergency operating piece of equipment out of service is the 'P38A' |
| (motor-driven auxiliary feedwater pump), which is out if service for |
| repairs. It should be back in service within the next 2 hours. The |
| electrical grid is stable, and since Unit 2 is in a refueling outage, it is |
| not affected by the breaker problem. |
| |
| The NRC resident inspector was informed of this event by the licensee. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 35309 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: NINE MILE POINT REGION: 1 |NOTIFICATION DATE: 01/22/1999|
| UNIT: [] [2] [] STATE: NY |NOTIFICATION TIME: 19:40[EST]|
| RXTYPE: [1] GE-2,[2] GE-5 |EVENT DATE: 01/20/1999|
+------------------------------------------------+EVENT TIME: 17:30[EST]|
| NRC NOTIFIED BY: ROY GREEN |LAST UPDATE DATE: 01/22/1999|
| HQ OPS OFFICER: JOHN MacKINNON +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |FRANK COSTELLO R1 |
|10 CFR SECTION: | |
|AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION | |
|NLCO TECH SPEC LCO A/S | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
| | |
|2 N Y 100 Power Operation |100 Power Operation |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| LATE NOTIFICATION ON REACTOR CORE ISOLATION COOLING (RCIC) BEING DECLARED |
| INOPERABLE ON 01/20/99 |
| |
| On 01/20/99 at 1730 EST, RCIC became inoperable as a result of two |
| inoperable primary containment isolation valves being closed to satisfy |
| Technical Specification 3.6.3. RCIC was declared inoperable per Technical |
| Specification 3.7.4 (14 days to restore to operable status). Initial |
| assessment conclude that an immediate report was not required. However, |
| upon additional review, it has been determined that a 4-hour report is |
| required in accordance with 10 CFR 50. 72 (b)(2)(iii)(D). RCIC was restored |
| to operable status on 01/22/99 at 1142 EST. The technical specifications |
| mentioned above were exited at the time. |
| |
| During the time period RCIC was out of service, all emergency core cooling |
| systems were fully operable. |
| |
| The NRC resident inspector was notified of this event by the licensee. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 35310 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: BRUNSWICK REGION: 2 |NOTIFICATION DATE: 01/23/1999|
| UNIT: [1] [] [] STATE: NC |NOTIFICATION TIME: 09:50[EST]|
| RXTYPE: [1] GE-4,[2] GE-4 |EVENT DATE: 01/23/1999|
+------------------------------------------------+EVENT TIME: 06:38[EST]|
| NRC NOTIFIED BY: DAVE JENKINS |LAST UPDATE DATE: 01/23/1999|
| HQ OPS OFFICER: LEIGH TROCINE +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |CHRIS CHRISTENSEN R2 |
|10 CFR SECTION: |BRIAN BONSER R2 |
|AESF 50.72(b)(2)(ii) ESF ACTUATION | |
| | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 M/R Y 25 Power Operation |0 Hot Shutdown |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| PRIMARY CONTAINMENT ISOLATIONS FOLLOWING A MANUAL REACTOR SCRAM FROM 25% |
| POWER DUE TO LOWERING TEMPERATURE IN THE BOTTOM HEAD REGION OF THE REACTOR |
| PRESSURE VESSEL DURING SINGLE REACTOR RECIRCULATION LOOP OPERATION |
| |
| The following text is a portion of a facsimile received from the licensee: |
| |
| "EVENT: On January 23, 1999, at 06:38, primary containment groups 2, 6, and |
| 8 isolations were received following a manual reactor scram. The reactor |
| scram was inserted on Unit 1 due to lowering temperature in the bottom head |
| region of the reactor pressure vessel during single reactor recirculation |
| loop operation. The cooldown was augmented by recirculation pump runback to |
| 28% demand (expected action at low power due to total feedwater flow) which |
| reduced circulation through the vessel. A technical specification shutdown |
| was not required due to bottom head temperature at the time of the reactor |
| scram. Following the manual reactor scram, reactor water level lowered to |
| 160 inches. This is below the Reactor Water Level Low Level One setpoint of |
| 166 inches. This is a normal level transient following a reactor scram and |
| was anticipated by the operating crew. Although these isolations were |
| anticipated by the operating crew, they were not explicitly discussed prior |
| to the reactor scram; therefore, this report is being made in accordance |
| with 10 CFR 50.72(b)(2)(ii). All required isolations occurred as a result |
| of the Reactor Water Level Low Level One initiation signal. Reactor water |
| level immediately swelled above the Low Level One setpoint. Group 2 |
| isolation valves include drywell equipment and floor drains, traversing |
| incore probe, residual heat removal (RHR) discharge isolation to radwaste, |
| and RHR process sampling valves. Group 6 isolation valves include |
| containment atmosphere control system and post-accident monitoring valves. |
| Group 8 isolation valves include RHR system shutdown cooling isolation |
| valves; these valves were closed prior to the isolation signal." |
| |
| "INITIAL SAFETY SIGNIFICANCE EVALUATION: Minimal. All systems responded as |
| designed from the Reactor Water Level Low Level One initiation signal." |
| |
| "CORRECTIVE ACTION(S): Isolations occurred as designed; no corrective |
| actions [are] required." |
| |
| The licensee stated that Technical Specification 3.4.9, Reactor Coolant |
| System Pressure and Temperature Limits - Normal Operation With the Core |
| Critical, specifies minimum temperatures while critical. If parameters go |
| outside these references limits, this technical specification requires the |
| parameters to be restored within 30 minutes. With temperature lowering in |
| the bottom head region, the licensee chose to manually scram the reactor to |
| restore the parameter before expiration of the 30-minute limiting condition |
| for operation. |
| |
| All rods fully inserted following the manual reactor scram. There were no |
| emergency core cooling actuations or safety injections, and none were |
| expected. None of the relief valves lifted. |
| |
| The unit is currently stable in Mode 3 (Hot Shutdown). Normal feedwater is |
| being used to supply water to the reactor vessel. The main steam isolation |
| valves are open, the turbine stop and control valves are closed, and the |
| condenser is available as a heat sink. All containment parameters appear to |
| be normal. Offsite power is available, and the emergency diesel generators |
| are operable if needed. |
| |
| NOTE: Prior to this event, the unit was operating at reduced power to |
| facilitate the performance of a recirculation |
| pump motor-generator set brush replacement. |
| |
| The licensee notified the NRC resident inspector. |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
|Power Reactor |Event Number: 35311 |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: BEAVER VALLEY REGION: 1 |NOTIFICATION DATE: 01/23/1999|
| UNIT: [1] [] [] STATE: PA |NOTIFICATION TIME: 12:43[EST]|
| RXTYPE: [1] W-3-LP,[2] W-3-LP |EVENT DATE: 01/23/1999|
+------------------------------------------------+EVENT TIME: 10:24[EST]|
| NRC NOTIFIED BY: TOM COTTER |LAST UPDATE DATE: 01/23/1999|
| HQ OPS OFFICER: JOHN MacKINNON +-----------------------------+
+------------------------------------------------+PERSON ORGANIZATION |
|EMERGENCY CLASS: N/A |FRANK COSTELLO R1 |
|10 CFR SECTION: | |
|ARPS 50.72(b)(2)(ii) RPS ACTUATION | |
|AESF 50.72(b)(2)(ii) ESF ACTUATION | |
| | |
| | |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1 M/R Y 73 Power Operation |0 Hot Standby |
| | |
| | |
+------------------------------------------------------------------------------+
EVENT TEXT
+------------------------------------------------------------------------------+
| DURING POWER REDUCTION, THE REACTOR WAS MANUALLY TRIPPED DUE TO LOW |
| CONDENSER VACUUM. |
| |
| Prior to this event, one of four condenser waterbox sections was removed |
| from service for tube cleaning, and reactor power was increased from 90% to |
| approximately 92% power. At 0916 EST, a low condenser vacuum alarm was |
| received at which time the licensee commenced a power reduction. During |
| power reduction, condenser parameters continued to degrade due to |
| circulating water system air intrusion from a leaking isolation valve. The |
| reactor was manually tripped from approximately 73% power due to the |
| degradation of the condenser system. All rods fully inserted into the |
| reactor core, and all systems operated as expected. Both the motor-driven |
| and turbine-driven auxiliary feedwater pumps automatically started on |
| low-low steam generator water level. None of the power-operated relief |
| valves on the primary or secondary side of the plant opened. Decay heat |
| from the primary system of the plant is being dumped to the main condenser. |
| (The main condenser can handle the decay heat loads.) Both the motor-driven |
| and turbine-driven feedwater pumps were secured after main feedwater was |
| restored to service. The electrical grid is stable, and all the emergency |
| core cooling systems are fully operable is needed. |
| |
| The NRC resident inspector was notified of this event by the licensee. |
+------------------------------------------------------------------------------+
Page Last Reviewed/Updated Thursday, March 25, 2021
Page Last Reviewed/Updated Thursday, March 25, 2021