Skip to main content

The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.

Event Notification Report for January 22, 1999

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           01/21/1999 - 01/22/1999

                              ** EVENT NUMBERS **

35261  35275  35286  35288  35289  35290  35291  35292  35293  35294  35295  35296 
35297  

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35261       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: HARRIS                   REGION:  2  |NOTIFICATION DATE: 01/14/1999|
|    UNIT:  [1] [] []                 STATE:  NC |NOTIFICATION TIME: 13:06[EST]|
|   RXTYPE: [1] W-3-LP                           |EVENT DATE:        01/14/1999|
+------------------------------------------------+EVENT TIME:        09:18[EST]|
| NRC NOTIFIED BY:  MARK PALMER                  |LAST UPDATE DATE:  01/21/1999|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |AL BELISLE           R2      |
|10 CFR SECTION:                                 |                             |
|ARPS 50.72(b)(2)(ii)     RPS ACTUATION          |                             |
|AESF 50.72(b)(2)(ii)     ESF ACTUATION          |                             |
|APRE 50.72(b)(2)(vi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     A/R        Y       100      Power Operation  |0        Hot Standby      |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AUTOMATIC REACTOR TRIP ON TRIP OF TWO OF THREE REACTOR COOLANT PUMPS AND     |
| LOSS OF TWO 6.9-kV BUSES                                                     |
|                                                                              |
| During relay calibration on the 'A' 6.9-kV non-safety bus, the bus was       |
| unexpectedly deenergized.  The 'C' 6.9-kV bus is a swing bus and was tied to |
| the 'A' 6.9-kV bus, which caused it to be deenergized also.  This caused the |
| loss of two of three reactor coolant pumps, and in turn, caused an automatic |
| reactor trip from 100% power.  All systems functioned as expected, all rods  |
| fully inserted, and auxiliary feedwater started on low steam generator level |
| as expected.  All safety systems are operable except the 'A' containment     |
| hydrogen analyzer which is out of service for planned maintenance.           |
|                                                                              |
| The exact cause of the loss of the 6.9-kV buses is currently under           |
| investigation.                                                               |
|                                                                              |
| The licensee notified the NRC Resident Inspector, the State of North         |
| Carolina, and the local county.                                              |
|                                                                              |
| ***Update on 01/21/99 at 1710 ET by Mark Ellington taken by MacKinnon***     |
|                                                                              |
| The licensee stated that they had not made an official notification to the   |
| state of North Carolina or the local counties but instead they had made      |
| courtesy calls to the state of North Carolina and the applicable counties    |
| notifying them of the reactor trip.                                          |
|                                                                              |
| The licensee also stated that 'A-SA" Containment  Hydrogen Recombiner was    |
| out of service instead of the "A" containment hydrogen analyzer.   R2DO      |
| (Chris Christensen) notified.                                                |
|                                                                              |
| The NRC resident inspector was notified of this update by the licensee.      |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Fuel Cycle Facility                              |Event Number:   35275       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PORTSMOUTH GASEOUS DIFFUSION PLANT   |NOTIFICATION DATE: 01/15/1999|
|   RXTYPE: URANIUM ENRICHMENT FACILITY          |NOTIFICATION TIME: 18:08[EST]|
| COMMENTS: 2 DEMOCRACY CENTER                   |EVENT DATE:        01/15/1999|
|           6903 ROCKLEDGE DRIVE                 |EVENT TIME:        14:10[EST]|
|           BETHESDA, MD 20817    (301)564-3200  |LAST UPDATE DATE:  01/21/1999|
|    CITY:  PIKETON                  REGION:  3  +-----------------------------+
|  COUNTY:  PIKE                      STATE:  OH |PERSON          ORGANIZATION |
|LICENSE#:  GDP-2                 AGREEMENT:  N  |JIM GAVULA           R3      |
|  DOCKET:  0707002                              |JOHN SURMEIER        NMSS    |
+------------------------------------------------+FRANK CONGEL         IRO     |
| NRC NOTIFIED BY:  RICHARD LARSON               |                             |
|  HQ OPS OFFICER:  STEVE SANDIN                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NBNL                     RESPONSE-BULLETIN      |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 4-HOUR NRC 91-01 BULLETIN NOTIFICATION INVOLVING ABANDONED EQUIPMENT IN THE  |
| X-326 PROCESS BUILDING                                                       |
|                                                                              |
| ON JANUARY 15, 1999, AT 1410 EST IT WAS DISCOVERED THAT THE X-326 PROCESS    |
| BUILDING NUCLEAR CRITICALITY APPROVALS (NCSAs)  DO NOT DESCRIBE THE          |
| OPERATION/CONTROLS FOR THE FOLLOWING ABANDONED IN PLACE EQUIPMENT:  PRODUCT  |
| PURIFICATION DISTILLATION TOWER, OLD EVACUATION JETS, OLD SO2 REACTOR, OLD   |
| PW BOOSTER CONNECTED TO CELL 25-7-15,  AND [AN] OLD FREON DEGRADER.          |
|                                                                              |
| "THIS IS REPORTABLE DUE TO NOT HAVING ANY NCSA IN PLACE FOR THIS ABANDONED   |
| EQUIPMENT.                                                                   |
|                                                                              |
| "THERE WAS NO LOSS OF HAZARDOUS/RADIOACTIVE MATERIAL OR                      |
| RADIOACTIVE/RADIOLOGICAL CONTAMINATION EXPOSURE AS A RESULT OF THIS EVENT."  |
|                                                                              |
| A PRIOR NRC NOTIFICATION (EVENT #33627) WAS MADE WHICH IDENTIFIED LEGACY     |
| EQUIPMENT IN THE X-326 PROCESS BUILDING, HOWEVER, THE ABOVE EQUIPMENT WAS    |
| INADVERTENTLY OMITTED.  THE EQUIPMENT IS IN GEOMETRICALLY FAVORABLE          |
| CONDITIONS AND CONTAINS URANIUM BELOW THE SAFE MASS LIMIT.  THIS CONDITION   |
| WAS DISCOVERED IN A REVIEW OF COMPLETED NCSAs.                               |
|                                                                              |
| THE LICENSEE WILL INFORM THE DOE SITE REPRESENTATIVE AND HAS INFORMED THE    |
| NRC RESIDENT INSPECTOR.                                                      |
|                                                                              |
| * * * UPDATE AT 1955 ON 1/18/99, BY LARSON, TAKEN BY WEAVER * * *            |
|                                                                              |
| "THIS IS REPORTABLE DUE TO NOT HAVING ANY NCSA IN PLACE FOR THIS ABANDONED   |
| EQUIPMENT.                                                                   |
|                                                                              |
| UPDATE: DUE TO THE PROBLEMS CONCERNING ABANDONED EQUIPMENT IN THE X-326      |
| BUILDING NOT COVERED BY NUCLEAR CRITICALITY SAFETY APPROVALS (NCSAs), A      |
| SEARCH PERFORMED IN THE X-705 & X-700 REVEALED ABANDONED EQUIPMENT THAT MAY  |
| NEED NCSAs. THE PLANT IS FOLLOWING IT'S PROCEDURE FOR ANOMALOUS NCSA         |
| CONDITIONS AND FURTHER EVALUATIONS ARE IN PROGRESS TO DETERMINE IF THIS      |
| ABANDONED EQUIPMENT MEETS THE FISSILE MATERIAL LIMITS. THE FISSILE MATERIAL  |
| LIMIT OF 15 GRAMS U235 BY PLANT PROCEDURES REQUIRES NCSAs."                  |
|                                                                              |
| THERE WAS NO LOSS OF HAZARDOUS/RADIOACTIVE MATERIAL OR                       |
| RADIOACTIVE/RADIOLOGICAL CONTAMINATION EXPOSURE AS A RESULT OF THIS EVENT.   |
|                                                                              |
| The licensee informed the NRC resident inspector.  The Operations Officer    |
| notified the RDO (Gavula); EO (Surmeier); IRO (Congel).                      |
|                                                                              |
| * * * UPDATE AT 1643 ON 1/20/99, BY HALCOMB, TAKEN BY WEAVER * * *           |
|                                                                              |
| DUE TO PROBLEMS CONCERNING ABANDONED EQUIPMENT IDENTIFIED IN THE X-326       |
| BUILDING NOT COVERED BY AN NCSA, A PLANT WIDE SEARCH WAS INITIATED TO        |
| IDENTIFY ALL EQUIPMENT WHICH MAY MEET THE FISSILE MATERIAL LIMITS AND WOULD  |
| REQUIRE AN ACTIVE NCSA. THIS SEARCH HAS IDENTIFIED THAT THE X-344, X-333,    |
| AND THE X-330 BUILDINGS CONTAIN ABANDONED EQUIPMENT THAT WILL REQUIRE AN     |
| NCSA.  ALL IDENTIFIED EQUIPMENT HAS BEEN BOUNDARIED OFF AND AN ANOMALOUS NCS |
| CONDITION REPORT COMPLETED.                                                  |
|                                                                              |
| THERE WAS NO LOSS OF HAZARDOUS/RADIOACTIVE MATERIAL OR                       |
| RADIOACTIVE/RADIOLOGICAL CONTAMINATION EXPOSURE AS A RESULT OF THIS EVENT.   |
|                                                                              |
| The licensee informed the NRC resident inspector.  The Operations Officer    |
| notified the RDO (Lanksbury); EO (BELL); IRO (Congel).                       |
|                                                                              |
| ***Update on 01/21/99 at 1847 ET by Sissler taken by MacKinnon***            |
|                                                                              |
| During ongoing plant search for abandoned equipment, additional equipment    |
| was discovered in the X-326 building which may meet the fissile material     |
| limits and would require an active NCSA.  The identified equipment has been  |
| boundaried off and an anomalous NCS condition report completed.              |
|                                                                              |
| The NRC resident inspector was notified of this event by the certificate     |
| holder. The Operations Officer notified R3DO (Lanksbury) and EO (Bell) .     |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35286       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: BRAIDWOOD                REGION:  3  |NOTIFICATION DATE: 01/20/1999|
|    UNIT:  [1] [] []                 STATE:  IL |NOTIFICATION TIME: 13:00[EST]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        01/20/1999|
+------------------------------------------------+EVENT TIME:        11:22[CST]|
| NRC NOTIFIED BY:  BOB NORK                     |LAST UPDATE DATE:  01/21/1999|
|  HQ OPS OFFICER:  DOUG WEAVER                  +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          UNU                   |ROGER LANKSBURY      R3      |
|10 CFR SECTION:                                 |ED GOODWIN           NRR     |
|AAEC 50.72(a)(1)(i)      EMERGENCY DECLARED     |ROSEMARY HOGAN       IRO     |
|                                                |CANUPP               FEMA    |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| UNUSUAL EVENT - LOSS OF APPROXIMATELY 50% OF CONTROL ROOM ANNUNCIATORS       |
|                                                                              |
| "Loss of redundant ANNUNCIATOR Power Supplies has rendered a substantial     |
| number of safety related annunciators inoperable.  This required a GSEP      |
| notification - Unusual Event, (MU-6 - Loss of Annunciators for >= 15         |
| minutes).  Backup indications are available and increased main control board |
| monitoring has been implemented."                                            |
|                                                                              |
| The licensee has notified the NRC resident inspector.                        |
|                                                                              |
| Event #35280 involved the same equipment.                                    |
|                                                                              |
| ***UPDATE on 01/21/99 at 1450 ET by Dave Kruck taken by MacKinnon****        |
|                                                                              |
| Unusual Event terminated at 1311 CT. The annunciator system is functional.   |
| The root cause for the failure had not been completed at the time of this    |
| event update notification.  Troubleshooting and repairs of the annunciator   |
| system are continuing.   R3DO (Lanksbury),  NRR EO (Dennig), & FEMA (Canupp) |
| notified.                                                                    |
|                                                                              |
| The NRC resident inspector was been notified of this event update by the     |
| licensee.                                                                    |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35288       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PEACH BOTTOM             REGION:  1  |NOTIFICATION DATE: 01/21/1999|
|    UNIT:  [2] [] []                 STATE:  PA |NOTIFICATION TIME: 09:00[EST]|
|   RXTYPE: [2] GE-4,[3] GE-4                    |EVENT DATE:        01/21/1999|
+------------------------------------------------+EVENT TIME:        05:02[EST]|
| NRC NOTIFIED BY:  TODD STRAYER                 |LAST UPDATE DATE:  01/21/1999|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |JOHN KINNEMAN        R1      |
|10 CFR SECTION:                                 |                             |
|AINC 50.72(b)(2)(iii)(C) POT UNCNTRL RAD REL    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| STANDBY GAS TREATMENT SYSTEM MAY NOT HAVE PERFORMED INTENDED FUNCTION DUE TO |
| DAMPER PROBLEM                                                               |
|                                                                              |
| While preparing to replace the solenoid valve for Standby Gas Treatment      |
| (SBGT) System damper PO-20466 (reactor building supply to  SBGT), the damper |
| did not open when the control room hand switch was placed in the "open"      |
| position.  However, the damper did open when the pneumatic supply to the     |
| solenoid valve was isolated. This damper opens automatically upon a SBGT     |
| system initiation to provide a flow path from the Unit 2 reactor building.   |
| The SBGT system would still have had a flow path from the Unit 2 refuel      |
| floor and equipment cell exhaust areas upon an initiation.  In addition, the |
| Unit 2 refuel floor currently has direct communication with the Unit 2       |
| reactor building because the refuel floor equipment hatch is removed.        |
|                                                                              |
| The licensee reported this event because the failure of the damper to open   |
| could have prevented the SBGT system from performing its intended function.  |
| The licensee is performing calculations to determine whether the failure     |
| would have prevented the fulfillment of the safety function. The damper is   |
| currently open, and the pneumatic supply to the solenoid valve has been      |
| isolated. The licensee plans to continue activities to replace the solenoid  |
| valve.                                                                       |
|                                                                              |
| The NRC resident inspector has been informed of this notification by the     |
| licensee.                                                                    |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35289       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SOUTH TEXAS              REGION:  4  |NOTIFICATION DATE: 01/21/1999|
|    UNIT:  [] [2] []                 STATE:  TX |NOTIFICATION TIME: 09:50[EST]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        01/21/1999|
+------------------------------------------------+EVENT TIME:        06:07[CST]|
| NRC NOTIFIED BY:  TIM FRAWLEY                  |LAST UPDATE DATE:  01/21/1999|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |DALE POWERS          R4      |
|10 CFR SECTION:                                 |                             |
|ARPS 50.72(b)(2)(ii)     RPS ACTUATION          |                             |
|AESF 50.72(b)(2)(ii)     ESF ACTUATION          |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     A/R        Y       100      Power Operation  |0        Hot Standby      |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AUTOMATIC TURBINE/REACTOR TRIP DURING TROUBLESHOOTING                        |
|                                                                              |
| "During troubleshooting activities to isolate the source of a ground on a    |
| 480VAC load center, the power source to the main turbine trip interlocks was |
| inadvertently deenergized. As a result, the main turbine tripped, resulting  |
| in an automatic reactor trip - reactor power was above P9 (50% power). All   |
| equipment performed as expected; all control rods fully inserted, and the    |
| auxiliary feedwater system actuated automatically on low steam generator     |
| levels (expected to occur upon a reactor trip from high power levels)."      |
|                                                                              |
| The licensee also reported that several steam generator PORVs lifted         |
| following the trip; this is expected following a trip from this power level. |
| The NRC resident inspector has been informed of this event by the licensee.  |
|                                                                              |
| ***Update on 01/21/99 at 1700 ET by Frawley taken by MacKinnon***            |
|                                                                              |
| On investigation it was determined that no steam generator PORVs lifted      |
| following the reactor trip.                                                  |
| R4DO (Dale Powers) notified.                                                 |
|                                                                              |
| The NRC resident inspector will be notified of this update by the licensee.  |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35290       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PRAIRIE ISLAND           REGION:  3  |NOTIFICATION DATE: 01/21/1999|
|    UNIT:  [1] [2] []                STATE:  MN |NOTIFICATION TIME: 13:59[EST]|
|   RXTYPE: [1] W-2-LP,[2] W-2-LP                |EVENT DATE:        01/21/1999|
+------------------------------------------------+EVENT TIME:        12:30[CST]|
| NRC NOTIFIED BY:  DOUG SMITH                   |LAST UPDATE DATE:  01/21/1999|
|  HQ OPS OFFICER:  STEVE SANDIN                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |ROGER LANKSBURY      R3      |
|10 CFR SECTION:                                 |                             |
|AOUT 50.72(b)(1)(ii)(B)  OUTSIDE DESIGN BASIS   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| LICENSEE DETERMINED THAT CERTAIN AUXILIARY BUILDING DOORS WOULD NOT RELIEVE  |
| PRESSURE AS DESIGNED FOLLOWING A HIGH ENERGY LINE BREAK (HELB).              |
|                                                                              |
| "The Prairie Island HELB analysis assumes that certain doors open to         |
| mitigate the pressure and temperature response. A calculation to             |
| reconstitute blow out pressure of the doors in the vent path was unable to   |
| verify doors would perform their HELB assumed function of opening to         |
| mitigate auxiliary building pressures. Latch pins on the stationary side of  |
| the doors do not allow the doors to swing open when required by the HELB     |
| event. Preliminary results from the calculation indicate damage would occur  |
| to other safety related structures. The doors will be unlatched to allow     |
| this pressure release to occur bringing the plant within the analysis.       |
| Category 1 doors 134, 184, 133, and 182 were declared inoperable per TS      |
| 3.6.E.1."                                                                    |
|                                                                              |
| Both units will remain in the  24-hour TS LCO until the latch pins are       |
| removed.  Hourly fire watches are assigned while the doors are unlatched.    |
| The licensee has long-term corrective actions under review.  This condition  |
| was discovered during an on-going design review.                             |
|                                                                              |
| The licensee informed the NRC Resident Inspector.                            |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35291       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: FT CALHOUN               REGION:  4  |NOTIFICATION DATE: 01/21/1999|
|    UNIT:  [1] [] []                 STATE:  NE |NOTIFICATION TIME: 14:00[EST]|
|   RXTYPE: [1] CE                               |EVENT DATE:        01/21/1999|
+------------------------------------------------+EVENT TIME:        10:10[CST]|
| NRC NOTIFIED BY:  DAVE BANNISTER               |LAST UPDATE DATE:  01/21/1999|
|  HQ OPS OFFICER:  JOHN MacKINNON               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:                                |DALE POWERS          R4      |
|10 CFR SECTION:                                 |BOB DENNIG,  NRR     EO      |
|NLCO                     TECH SPEC LCO A/S      |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 161kV incoming line declared inoperable.                                     |
|                                                                              |
| Report required by Technical Specification 2.7(2) c. as a result of          |
| declaring 161kV incoming line inoperable.  Declaring 161kV inoperable        |
| renders both house service transformers T1A3 and T1A4 inoperable (feed vital |
| onsite buses).  161kV is energized, and breakers 110 and 111 did not open,   |
| but cannot be brought back-in-house until lockout 86X/FT/161, which tripped, |
| is reset.                                                                    |
|                                                                              |
| A contractor performing modification work in the Fort Calhoun Station        |
| switchyard was trenching, and the trencher caught a cable buried             |
| approximately 4 inches underground.  This cable supplies 161kV fast transfer |
| secondary potential transformer alarm circuit.                               |
|                                                                              |
| All 4160 v  buses successfully fast transferred to the onsite 22kV power     |
| source, and Abnormal Operating Procedure AOP-31, "All 4160V Buses fed From   |
| 22kV," was entered.                                                          |
|                                                                              |
| A new cable is being run, and should be completely installed and tested by   |
| mid-afternoon, allowing transfer back to 161kV.  A relay exists that might   |
| be able to be bypassed, which would allow 161kV to be brought back into the  |
| plant.                                                                       |
|                                                                              |
| All Emergency Diesel Generators are fully operable if needed and the non-Q   |
| Auxiliary Feedwater Pump is also fully operable.                             |
|                                                                              |
| The NRC resident inspector has been notified of this event by the licensee.  |
|                                                                              |
|                                                                              |
| ****Update on 01/21/99 at 1602 ET by Bannister taken by MacKinnon****        |
|                                                                              |
|                                                                              |
| The cable damaged in the Fort Calhoun switchyard has been replaced; the      |
| lockout relay, 86X/FT/161, has been reset; and the plant is now back in its  |
| normal electrical lineup with 161kV supplying both house service             |
| transformers T1A3 and T1A4 at 1440 CT. Technical Specification 2.7.(2) c.    |
| and Abnormal Operating Procedure APO-31 were exited. R4DO (D. Powers) & NRR  |
| EO (Dennig) notified.                                                        |
|                                                                              |
| The NRC resident inspector was notified of this event update by the          |
| licensee.                                                                    |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   35292       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  COMMONWEALTH OF MASS                 |NOTIFICATION DATE: 01/21/1999|
|LICENSEE:  AMERSHAM                             |NOTIFICATION TIME: 14:06[EST]|
|    CITY:  Burlington               REGION:  1  |EVENT DATE:        01/21/1999|
|  COUNTY:                            STATE:  MA |EVENT TIME:        11:00[EST]|
|LICENSE#:                        AGREEMENT:  Y  |LAST UPDATE DATE:  01/21/1999|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |JOHN KINNEMAN        R1      |
|                                                |FRED COMBS, NMSS     EO      |
+------------------------------------------------+EASTON, NMSS                 |
| NRC NOTIFIED BY:  R. FAIRFULL                  |                             |
|  HQ OPS OFFICER:  JOHN MacKINNON               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT                                                       |
|                                                                              |
| The following facsimile was received from Massachusetts:                     |
|                                                                              |
| "The Radiation Control Program was notified at approximately 11:00 a.m.      |
| today that a package exceeding transportation limits had been received by    |
| AEA Technology (formerly Amersham Corp.) this morning.                       |
|                                                                              |
| "The following facts were reported:                                          |
|                                                                              |
| 1. package was from their parent company in England                          |
| 2. max reading was 820 mr/hour; Transportation Index of 18                   |
| 3. package consisted of outer packaging, with styrofoam intermediate insert, |
| containing a lead pot                                                        |
| 4. lead pot contained three cesium sealed sources - total of 9 curies        |
| 5. sources were not braced within the pot                                    |
| 6. readings varied with package orientation range of 540-820 mr/hr           |
|                                                                              |
| "The Radiation Control Program dispatched an inspector to the AEA Technology |
| facility in Burlington Massachusetts this afternoon to investigate."         |
|                                                                              |
| See HOO log book for phone number.                                           |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35293       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CALVERT CLIFFS           REGION:  1  |NOTIFICATION DATE: 01/21/1999|
|    UNIT:  [1] [2] []                STATE:  MD |NOTIFICATION TIME: 16:51[EST]|
|   RXTYPE: [1] CE,[2] CE                        |EVENT DATE:        01/21/1999|
+------------------------------------------------+EVENT TIME:        15:45[EST]|
| NRC NOTIFIED BY:  UMPHREY                      |LAST UPDATE DATE:  01/21/1999|
|  HQ OPS OFFICER:  JOHN MacKINNON               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:                                |JOHN KINNEMAN        R1      |
|10 CFR SECTION:                                 |                             |
|AINC 50.72(b)(2)(iii)(C) POT UNCNTRL RAD REL    |                             |
|AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION    |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| PENETRATION ROOM VENTILATION SYSTEM MAY NOT PROVIDE ADEQUATE ACCIDENT        |
| MITIGATION WHILE MAINTENANCE IS PERFORMED ON SYSTEM.                         |
|                                                                              |
| Penetration room ventilation system does not provide adequate protection to  |
| control the release of radioactive material and mitigate the consequences of |
| an accident during the maintenance activities on the system due to system    |
| design.  At the present time the licensee is investigating corrective        |
| actions to be taken to corrective this problem.                              |
|                                                                              |
| The NRC resident inspector was notified of this event by the licensee.       |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Other Nuclear Material                           |Event Number:   35294       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  U.S. ARMY                            |NOTIFICATION DATE: 01/21/1999|
|LICENSEE:  U. S. ARMY                           |NOTIFICATION TIME: 16:57[EST]|
|    CITY:  ROCK ISLAND              REGION:  3  |EVENT DATE:        01/21/1999|
|  COUNTY:                            STATE:  IL |EVENT TIME:        14:00[CST]|
|LICENSE#:  12-00722-06           AGREEMENT:  Y  |LAST UPDATE DATE:  01/21/1999|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |ROGER LANKSBURY      R3      |
|                                                |MIKE BELL, NMSS      EO      |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  TIM MOHS                     |                             |
|  HQ OPS OFFICER:  JOHN MacKINNON               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:                                |                             |
|10 CFR SECTION:                                 |                             |
|IBAD 30.50(b)(1)(ii)     MATL >5X LOWEST LIMIT  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| U S ARMY  M137 telescope found to have tritium contamination.                |
|                                                                              |
| An M137 telescope was received at Fort Campbell, KY  on 12/21/98. The        |
| telescope outer cover was removed on 01/13/99 at which time it was found     |
| that at least one tritium vial inside the telescope was broken. Wipes taken  |
| of the telescope and the surrounding area were sent to Rock Island Arsenal,  |
| IL to be counted for tritium activity.  Today, (01/21/99), the results of    |
| the highest reading wipe was determined to be 6E06 DPM.  Nobody at this time |
| is known to have been contaminated, but bioassays of personnel who have come |
| into contact with the telescope are being or will be taken.  The telescope   |
| was shipped out of Galesburg, IL  to Macomb, IL, then from Macomb, IL to     |
| Springfield, IL. The telescope then passed through Ft. Drum, NY, and on to   |
| Fort Campbell, KY.                                                           |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35295       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: POINT BEACH              REGION:  3  |NOTIFICATION DATE: 01/21/1999|
|    UNIT:  [1] [] []                 STATE:  WI |NOTIFICATION TIME: 16:59[EST]|
|   RXTYPE: [1] W-2-LP,[2] W-2-LP                |EVENT DATE:        01/21/1999|
+------------------------------------------------+EVENT TIME:        15:00[CST]|
| NRC NOTIFIED BY:  RICK ROBBINS                 |LAST UPDATE DATE:  01/21/1999|
|  HQ OPS OFFICER:  JOHN MacKINNON               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |ROGER LANKSBURY      R3      |
|10 CFR SECTION:                                 |                             |
|AOUT 50.72(b)(1)(ii)(B)  OUTSIDE DESIGN BASIS   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| Material for deionized water supply valve changed                            |
|                                                                              |
| During storeroom valve stock review, the licensee discovered that valve      |
| materials for a deionized water supply line containment isolation valve had  |
| changed.  Specifically, the diaphragm material had changed.  The design      |
| value for the original material was 200� F at 200 psi.  The new valve was    |
| rated at 150�  F at 300 psi.  This valve inside containment and another      |
| valve outside containment are normally closed during operation.  Further     |
| evaluations are underway.                                                    |
|                                                                              |
| Containment integrity has been verified by ensuring the valve outside        |
| containment is locked shut.                                                  |
|                                                                              |
| The NRC resident inspector will be notified of this event by the licensee.   |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35296       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: FITZPATRICK              REGION:  1  |NOTIFICATION DATE: 01/21/1999|
|    UNIT:  [1] [] []                 STATE:  NY |NOTIFICATION TIME: 18:17[EST]|
|   RXTYPE: [1] GE-4                             |EVENT DATE:        01/21/1999|
+------------------------------------------------+EVENT TIME:        14:00[EST]|
| NRC NOTIFIED BY:  ED HYNE                      |LAST UPDATE DATE:  01/21/1999|
|  HQ OPS OFFICER:  JOHN MacKINNON               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |JOHN KINNEMAN        R1      |
|10 CFR SECTION:                                 |                             |
|AINA 50.72(b)(2)(iii)(A) POT UNABLE TO SAFE SD  |                             |
|AINB 50.72(b)(2)(iii)(B) POT RHR INOP           |                             |
|AINC 50.72(b)(2)(iii)(C) POT UNCNTRL RAD REL    |                             |
|AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION    |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| Emergency diesel generators, while running unloaded, may have failed to      |
| energize emergency buses in the event of a unit trip with the 115 kV supply  |
| out of service.                                                              |
|                                                                              |
| A fire in the plant's hydrogen storage facility (event # 35275 on 01/14/99)  |
| resulted in a decision to remove the 115 kV reserve power supply from        |
| service to safely suppress the fire.  The Emergency diesel generators were   |
| started per plant surveillance procedure ST-9D to demonstrate operability as |
| required by Technical Specifications. A decision was made to allow the       |
| emergency diesel generators to run unloaded for a period of time with the    |
| 115 kV reserve power out of service but available.  A later review of the    |
| emergency diesel generator  protective scheme indicates the possibility that |
| one or more of the emergency diesel generators may have failed to energize   |
| the emergency buses in the event of a unit trip with the 115 kV supply out   |
| of service.  Further evaluation of this scenario is continuing to determine  |
| any necessary procedural changes.                                            |
|                                                                              |
| The NRC resident inspector has been notified of this event by the licensee.  |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35297       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: DIABLO CANYON            REGION:  4  |NOTIFICATION DATE: 01/22/1999|
|    UNIT:  [1] [2] []                STATE:  CA |NOTIFICATION TIME: 00:59[EST]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        01/21/1999|
+------------------------------------------------+EVENT TIME:        18:25[PST]|
| NRC NOTIFIED BY:  JOSEPHINE BROWN              |LAST UPDATE DATE:  01/22/1999|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |DALE POWERS          R4      |
|10 CFR SECTION:                                 |                             |
|NINF                     INFORMATION ONLY       |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| Courtesy call regarding safeguards system degradation related to computer.   |
| Compensatory measures were taken immediately upon discovery. Refer to the    |
| HOO Log for additional details. The NRC resident inspector will be informed  |
| of this notification by the licensee.                                        |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Thursday, March 25, 2021

Page Last Reviewed/Updated Thursday, March 25, 2021