Information Notice No. 88-75, Supplement 1: Disabling of Diesel Generator Output Circuit Breakers by Anti-Pump Circuitry
UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, D.C. 20555 April 17, 1989 Information Notice No. 88-75, SUPPLEMENT 1: DISABLING OF DIESEL GENERATOR OUTPUT CIRCUIT BREAKERS BY ANTI-PUMP CIRCUITRY Addressees: All holders of operating licenses or construction permits for nuclear power reactors. Purpose: This notice supplements information contained in Information Notice No. 88-75 concerning design problems with anti-pump circuitry used by circuit breakers with automatic closing logic. It is expected that recipients will review the information for applicability to their facilities and consider actions, as appropriate, to avoid similar problems. However, suggestions contained in this information notice do not constitute NRC requirements; therefore, no specific action or written response is required. Background: Information Notice No. 88-75 described two events at nuclear power reactors during which the capability to either automatically or manually (from the control room) close diesel generator output circuit breakers was lost because of design problems involving the breaker anti-pump circuitry. It was noted that anti-pump circuit problems could apply not only to diesel generator output breakers, but also to other safety-related breakers with automatic closing logic. Since issuance of Information Notice No. 88-75, design deficiencies have been reported involving the anti-pump circuitry for the auxiliary feedwater pump breakers, component cooling water pump breakers, and service water pump breakers at Zion Units 1 and 2. The anti-pump circuitry is designed to prevent cycling of the circuit breaker between the closed and tripped (open) positions when both automatic close and automatic trip signals exist concurrently. The anti-pump circuitry prevents repeated attempts to close the breaker under valid trip (fault) conditions. However, it was discovered that certain loss-of-power scenarios could result in concurrent automatic close and automatic trip signals that would cause the breaker to trip and lock out in the tripped position and would prevent reclosure (because of seal-in of the anti-pump circuit) although a valid standing closure signal is present and no fault condition exists. 8904110183 . IN 88-75, Supplement 1 April 17, 1989 Page 2 of 3 Description of Circumstances: On October 25, 1988, as a result of a review of tests performed to verify proper sequencing of emergency loads onto the emergency buses during a loss of offsite power, the engineering department at Zion Nuclear Power Station determined that the component cooling water (CCW) pumps and the auxiliary feedwater (AFW) pumps may not start on emergency power as designed following a loss of offsite power because of the design of the pump circuit breaker anti-pump circuitry. Further investigation revealed that a similar problem could occur with the service water (SW) pumps. Specifically, before the test, the train A CCW pump was in standby and the train B CCW pump was running. When power was removed from the emergency bus providing power to the train B CCW pump as part of the test, the pump stopped, creating a low-pressure condition in the discharge header, which in turn caused an automatic start signal for both the train A and B CCW pumps. Therefore, the circuit breaker for the train B CCW pump received an automatic trip signal (from the simulated loss of offsite power condition to allow proper sequencing) concurrent with an automatic close signal (from the initiation circuitry on low header pressure). This caused the anti-pump circuitry for the breaker to energize and seal in, preventing further breaker closure attempts, and left the pump deenergized with its breaker locked out by the anti-pump circuitry. When the low header pressure signal was cleared by automatic initiation of the train A CCW pump, the anti-pump circuitry for the train B pump reset (deenergized) and allowed the train B pump to start upon receipt of the loss of offsite power sequence timer signal. After reviewing the above test sequence and related circuit breaker traces, the licensee determined that during an actual loss of offsite power, in which power would be lost to all buses providing power to the CCW pumps, the breakers for each pump would have received start signals on low header pressure concurrent with undervoltage trip signals and would have been locked out as a result of the anti-pump feature, resulting in the loss of all CCW. This condition would not clear even after the emergency diesel generator attained full speed and voltage, and the sequenced breaker closure signals were generated. To start a CCW pump would require that the pump control switch be placed in the "AFTER-TRIP" position to reset (deenergize) the anti-pump circuit, thereby allowing subsequent breaker closure attempts. Further investigation revealed that the service water pump breakers could similarly be locked out on a standing low header pressure automatic closure signal coincident with a second level undervoltage trip signal. The licensee also concluded that a loss of offsite power condition, occurring at power, could result in a reactor/turbine trip accompanied by an immediate shrinking of steam generator inventory to below the low-low level setpoint for automatic initiation of auxiliary feedwater. In this case, the auxiliary feedwater pump breakers would receive concurrent close and trip signals, and the anti-pump circuitry would cause the same lockout condition as mentioned above (for the CCW and SW pumps), preventing automatic initiation of auxiliary feedwater. . IN 88-75, Supplement 1 April 17, 1989 Page 3 of 3 The Zion licensee modified the breaker control logic for the CCW and AFW pumps so that the automatic closure signals (CCW header low pressure and steam generator low-low level) are blocked following a loss of offsite power condition until the diesel generators attain full speed and voltage and are supplying power to the emergency buses, and the pump breakers have received automatic close signals via the load sequencer. Similarly, the SW pump breaker control logic was modified so that the closure signal on SW header low pressure is blocked until emergency bus voltage has been restored and the pump has been sequenced following a second level under-voltage condition. The circuit breaker anti-pump problem was not discovered during previous loss- of-power tests because the tests are performed on a bus-by-bus basis with the plant at hot shutdown. Redundant CCW and SW pumps powered from the bus not under test would maintain header pressure above the automatic initiation setpoint. Also, the magnitude of the steam generator level shrink at hot shutdown was not sufficient to cause an AFW pump automatic start signal on low-low level. Therefore, the anti-pump circuitry did not actuate because breaker close signals were not received concurrent with the breaker trip signals. This event demonstrates that when complete system integrated testing cannot be performed under actual conditions, it is important to carefully analyze all differences between plant conditions during testing and conditions expected to exist when the equipment under test is required to perform its safety function in order to verify the acceptability of the test. No specific action or written response is required by this information notice. If you have any questions about this matter, please contact one of the techni- cal contacts listed below or the Regional Administrator of the appropriate regional office. Charles E. Rossi, Director Division of Operational Events Assessment Office of Nuclear Reactor Regulation Technical Contacts: F. Burrows, NRR (301) 492-0833 R. Kendall, NRR (301) 492-3140 Attachment: List of Recently Issued NRC Information Notices . Attachment IN 88-75, Supplement 1 April 17, 1989 Page 1 of 1 LIST OF RECENTLY ISSUED NRC INFORMATION NOTICES _____________________________________________________________________________ Information Date of Notice No._____Subject_______________________Issuance_______Issued to________ 89-40 Unsatisfactory Operator Test 4/14/89 All holders of OLs Results and Their Effect on or CPs for nuclear the Requalification Program power reactors. 89-39 List of Parties Excluded 4/5/89 All holders of OLs from Federal Procurement or CPs for nuclear or Non-Procurement Programs power reactors. 89-38 Atmospheric Dump Valve 4/5/89 All holders of OLs Failures at Palo Verde or CPs for nuclear Units 1, 2, and 3 power reactors. 89-37 Proposed Amendments to 4/4/89 All U.S. NRC 40 CFR Part 61, Air licensees. Emission Standards for Radionuclides 89-36 Excessive Temperatures 4/4/89 All holders of OLs in Emergency Core Cooling or CPs for nuclear System Piping Located power reactors. Outside Containment 88-86, Operating with Multiple 3/31/89 All holders of OLs Supp. 1 Grounds in Direct Current or CPs for nuclear Distribution Systems power reactors. 89-35 Loss and Theft of Un- 3/30/89 All U.S. NRC secured Licensed Material byproduct, source and special nuclear material licensees. 89-34 Disposal of Americium 3/30/89 All holders of an Well-Logging Sources NRC specific license authorizing well- logging activities. 89-33 Potential Failure of 3/23/89 All holders of OLs Westinghouse Steam or CPs for PWRs. Generator Tube Mechanical Plugs _____________________________________________________________________________ OL = Operating License CP = Construction Permit
Page Last Reviewed/Updated Tuesday, March 09, 2021
Page Last Reviewed/Updated Tuesday, March 09, 2021