Information Notice No. 85-94: Potential for Loss of Minimum Flow Paths Leading to ECCS Pump Damage During a LOCA
SSINS No.: 6835 IN 85-94 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, DC 20555 December 13, 1985 Information Notice No. 85-94: POTENTIAL FOR LOSS OF MINIMUM FLOW PATHS LEADING TO ECCS PUMP DAMAGE DURING A LOCA Addressees: All nuclear power reactor facilities holding an operating license (OL) or a construction permit (CP). Purpose: This notice is provided to alert licensees of recent instances where it was discovered that minimum flow requirements might not or could not be met for some emergency core cooling system (ECCS) pumps under small-break loss-of coolant-accident (SBLOCA) conditions. It is suggested that recipients review this information for applicability to their facilities and consider actions, if appropriate, to preclude similar problems at their facilities. However, the suggestions contained in this notice do not constitute NRC requirements; therefore, no specific action or written response is required. Description of Circumstances: In three recent instances, it was discovered by licensee personnel or by NRC site resident inspectors that minimum flow paths for ECCS pumps were jeopar- dized by design errors or personnel errors. Brunswick Units 1 and 2: On or about May 23, 1984, while performing local leak fate testing of the primary containment penetrations, operations personnel at Brunswick Unit 2 observed that the minimum flow valve for the 2A core spray pump would not stay in the closed position following receipt of a "close" signal from the remote manual operator in the control room. (These valves do not receive a "close" signal upon actuation of the containment isolation system.) Figure 1 shows the location of the minimum flow valves. Engineering personnel determined that the control logic for the minimum flow valves was such that the valves would reopen after closure whenever a low flow condition was sensed in the core spray line, including conditions where the core spray system (CSS) pumps were not running. On June 1, an engineering review determined that the minimum flow valve control logic did not appear to meet design criteria for containment isola- tion. Based on this determination, the normally open minimum flow valves for the CSS trains for both units were declared inoperable. Operations personnel then complied with the plant technical specification action statement for inoperable primary containment isolation valves (PCIVs) by closing and deactivating the valves. At the time, Unit l was operating at power and Unit 2 was defueled. 8512120322 . IN 85-94 December 13, 1985 Page 2 of 4 The licensee established procedures intended to ensure effective operator action to minimize the potential for pump damage in the event of a CSS pump start. From subsequent discussions with the pump vendor, the plant operating staff learned that damage to the CSS pumps could occur in as little as 1 minute of operation at shutoff head without the minimum required flow. The plant staff reevaluated the situation and concluded that the risk of pump damage with the valves closed was unacceptable. After shutdown on June 12, the minimum flow valves were reopened and actuator power was restored. During the sub- sequent Unit 1 startup on June 13, administrative controls and special pro- cedures were implemented to ensure closure of the valves when required for containment isolation. The licensee's planned permanent corrective action is to modify the logic to allow remote isolation capability for the valves when their associated pumps are not running, so that minimum flow and containment isolation functions can both be ensured. Peach Bottom Unit 3: During an NRC inspection at Peach Bottom 3, from July 16 to August 31 1984, the site resident inspectors performed a review of the plant procedures and practices for ensuring minimum flow protection for the ECCS pumps. They determined that the minimum flow valves for separate trains of the residual heat removal (RHR) system had been closed on two different occasions while the reactor was at power. Figure 2 shows the locations of the minimum flow valves. The first event occurred on April 27, 1982, when the "D" RHR pump minimum flow valve was closed and deactivated for several hours. The second event occurred between June 22 and 25, 1984, when the "A" RHR pump minimum flow valve was closed and deactivated for approximately 3 days. In neither case could the inspectors determine why the minimum flow valves had been closed and deactivated. However, the inspectors believe t,hat the actions were taken to perform maintenance on the valves: or their motor operators. The inspectors also found that, in both cases, the licensee did not consider (or declare) the associated low pressure coolant injection (LPCI) system train to be inoperable while the minimum flow valve was closed. These events were brought to the attention of the licensee by the resident inspectors. To prevent recurrence, operations personnel were instructed not to deactivate any of the ECCS minimum flow valves when system operability is required. Additional corrective measures are still under review. Point Beach Units 1 and 2: On July 24, 1985, the licensee notified the NRC, pursuant to the provisions of 10 CFR 21, of a potential defect in the design of the control circuit for the safety injection (SI) pump recirculation flow path isolation valves. During a post-implementation review of the Emergency Operating Procedures, the licensee discovered that the failure of the power supply breaker in the remote control circuitry for either of the isolation valves in the recirculation line constituted a single failure that could cause the loss of both SI pumps upon subsequent actuation of the pumps with reactor coolant system (RCS) pressure remaining above pump shutoff head for a short period. . IN 85-94 December 13, 1985 Page 3 of 4 The SI pumps have a common return pipe from their discharges to the refueling water storage tank (RWST) to provide a test flow path and a recirculation path for minimum flow when the RCS pressure exceeds pump shutoff head (see figure 3). There are two (one for each train) isolation valves in series on the return line. They are air-operated and fail closed when their control circuits lose electrical power or upon loss of air pressure, which is not supplied from a safety related system. The purpose of these valves is to Isolate the RWST (outside containment) from the containment sump during the recirculation phase of emergency core cooling following a LOCA. The valve position indication and the valve closed annunciation in the control room are powered from the same breaker as the valve control circuit. Therefore, the single failure of the breaker associated with either train would isolate the minimum flow path for both SI pumps, defeat the control room annunciation of the valve closure, and cause the loss of valve position indication. Because the valve position indication is not on a front panel, this condition could remain unnoticed for as much as a month (the surveillance interval). Subsequent start of the SI pumps could then result in the failure of both pumps within a short period unless RCS pressure dropped below the 1470 psi shutoff head. The licensee's short-term corrective action is to use the manual handwheel operators on the isolation valves to override the remote operators and maintain the valves in the open position in the event of loss of electrical power or air pressure. This' action defeats the interlock between the isolation valves in the RWST return line and the motor-operated containment sump isolation valves. The interlock is designed to close the recirculation line isolation valves when either of the containment sump isolation valves is not fully closed. To ensure that contaminated containment sump water will not be inadvertently pumped into the RWST during the recirculation phase of safety injection following a design-basis accident, the remote containment sump isolation valve controller switches have been fitted wi$h plastic covers and plaques explaining the requirement for manually closing the RWST return valves before the containment sump isolation valves are opened. The local operators have similar plaques and have been administratively "red locked" with plastic tab devices. Long-term options for permanent corrective actions are still under investigation. Discussion: These events all demonstrate failures of licensees to recognize in a timely manner that the operability of various ECCS pumps was jeopardized by loss or potential loss of recirculation flow paths. In the event of a LOCA which did not depressurize the RCS below the shutoff head of these pumps within a very short period, the pumps could become damaged and unavailable to perform their safety functions. The events at Brunswick and Peach Bottom illustrate that deficiencies exist in training and procedures with respect to the relationship between the availability of minimum flow paths and the operability of ECCS pumps. The events at Brunswick and Point Beach illustrate the difficulties in designing systems to meet multiple criteria. The minimum flow valve control logic at the . IN 85-94 December 13, 1985 Page 4 of 4 Brunswick plant was inadequate to meet its containment isolation function. The RWST return line control circuitry at the Point Beach plant was inadequate to ensure minimum flow through at least one SI pump in the event of a single failure. The importance of minimum flow recirculation systems to ECCS pump operability may not yet be fully reflected in design and operation because adequate attention has not been focused on the effects of SBLOCA sequences until relatively recently (i.e., following the Three Mile Island accident). It appears that the minimum flow system for the two SI trains at Point Beach was not designed to sustain a single failure. In addition, the Point Beach defect illustrates the problem with reliance upon administrative controls to ensure minimum flow through the ECCS pumps following a failure of the minimum flow path. Timely manual action in the control room can be compromised by a variety of difficulties. In the case of the defect reported by Point Beach, the same failure that could block the minimum flow path would also compromise control room indications needed by the operators. Other, more simple indication failures could also compromise the ability to detect mispositioned valves or inadequate flow. For this reason, administrative controls are poor substitutes for adequate design. No specific action or written response is required by this notice. If you have any questions regarding this matter, please contact the Regional Administrator of the appropriate NRC regional office or this office. Edward L. Jordan, Director Division of Emergency Preparedness and Engineering Response Office of Inspection and Enforcement Technical Contacts: S. M. Long, IE (301) 492-7159 E. J. Leeds, AEOD (301) 492-4445 Attachments: 1. Figure 1, BWR Low Pressure Core Spray 2. Figure 2, BWR Low Pressure 3. Figure 3, Diagram of Point Beach ECCS 4. List of Recently Issued IE information Notices
Page Last Reviewed/Updated Tuesday, March 09, 2021
Page Last Reviewed/Updated Tuesday, March 09, 2021