Part 21 Report - 1995-030
LICENSEE: COMMONWEALTH EDISON CO.
SITE: DRESDEN 2 3 EN NUMBER:28285
DOCKET: 05000237 05000249 EVENT DATE: 01-26-95
RX TYPE: BWR BWR EVENT TIME: 15:45
VENDORS: GE-3 GE-3 NOTIFY DATE: 01-26-95
EMERGENCY CLASS: N/A REGION: 3 STATE: IL TIME: 17:43
OPS OFFICER: TIM McGINTY
10 CFR SECTION: ADEG 50.72(b)(1)(ii) DEGRAD COND DURING OP
UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE
CODE CRIT PWR PWR
2 N Y 99 POWER OPERATION 99 POWER OPERATION
3 N Y 99 POWER OPERATION 99 POWER OPERATION
TIP SYSTEM ISOLATION VALVES WOULD RE-OPEN IF THE CONTROL SWITCHES
WERE IN THE OPEN POSITION WHEN A GROUP 2 ISOLATION SIGNAL WAS
RESET.
THE SYSTEM ENGINEERING DEPARTMENT REPORTED THAT A REVIEW OF THE
TRAVERSING IN-CORE PROBE (TIP) SYSTEM ISOLATION LOGIC PRINTS
INDICATED THAT DRESDEN STATION HAS THE SAME DESIGN DEFICIENCY
EXPERIENCED AT QUAD CITIES AND COOPER (SEE RELATED EVENT REPORTS
28281 & 28245, RESPECTIVELY). THIS DEFICIENCY WOULD ALLOW THE
TIP SYSTEM ISOLATION VALVES TO AUTO RE-OPEN UPON RESET OF A GROUP
2 PRIMARY CONTAINMENT ISOLATION IF THE CONTROL SWITCHES ARE NOT
LEFT IN THE "CLOSED" POSITION.
DRESDEN STATIONS UPDATED REVISED FSAR STATES THAT THE ISOLATION
LOGIC HAS BEEN MODIFIED TO PREVENT THE VALVES FROM AUTOMATICALLY
OPENING WHEN THE ISOLATION SIGNAL IS RESET. THE PRINT REVIEW
INDICATES THAT THE TIP SYSTEM ISOLATION VALVES WERE NOT INCLUDED
IN THIS MODIFICATION, AND ARE THEREFORE OUTSIDE THE DESIGN BASES.
ADMINISTRATIVE CONTROLS HAVE BEEN PLACED IN EFFECT TO ENSURE
THAT TIP SYSTEM ISOLATION VALVE CONTROL SWITCHES ARE IN THE
CLOSED POSITION, AND VALVES ARE VERIFIED CLOSED PRIOR TO RESET OF
ANY GROUP 2 PRIMARY CONTAINMENT ISOLATION. THE LICENSEE WILL BE
INVESTIGATING LONG-TERM CORRECTIVE ACTIONS, AND WILL INFORM THE
RESIDENT INSPECTOR.
Page Last Reviewed/Updated Wednesday, March 24, 2021