Morning Report for August 8, 2001

                       Headquarters Daily Report

                         AUGUST 08, 2001

***************************************************************************
                    REPORT             NEGATIVE            NO INPUT
                    ATTACHED           INPUT RECEIVED      RECEIVED

HEADQUARTERS                           X
REGION I                               X
REGION II                              X
REGION III          X
REGION IV           X
PRIORITY ATTENTION REQUIRED  MORNING REPORT - REGION III  AUGUST  8, 2001

Licensee/Facility:                     Notification:

Wisconsin Public Service Corp.         MR Number: 3-01-0027
Kewaunee 1                             Date: 08/07/01
Kewaunee,Wisconsin                     E-mail from Resident Inspector
Dockets: 50-305
PWR/W-2-LP

Subject: MANAGEMENT CHANGES

Discussion:

The licensee announced that Kyle Hoops, currently the Plant Manager, will
begin an 18-month assignment at the Institute of Nuclear Power
Operations. Tom Taylor, currently the Assistant Plant Manager,
Operations, will replace Mr. Hoops. The change is effective January 2002.

Regional Action:

None.

Contact:  Roger Lanksbury            (630)829-9631
_
REGION IV  MORNING REPORT     PAGE  2          AUGUST  8, 2001

Licensee/Facility:                     Notification:

Pacific Gas & Electric Co.             MR Number: 4-01-0005
Diablo Canyon 1 2                      Date: 08/08/01
Avila Beach,California                 Licensee called HOO
Dockets: 50-275,50-323
PWR/W-4-LP,PWR/W-4-LP

Subject: ELECTRICAL FAULT CAUSED LOSS OF START-UP POWER (EVENT 38186)
Reportable Event Number: 38186

Discussion:

On Saturday, August 4, 2001, the licensee experienced an electrical fault
that caused the loss of startup transformer power to both units while
both units were operating at 100 percent power (reference Event Number
38186).  The loss of startup power resulted in loss of electrical power
to outbuildings and a precautionary start signal to the emergency diesel
generators.  All six emergency diesel generators started as designed for
this condition; none of them tied on to the emergency electrical buses
since offsite power was maintained through the 500 kV supply lines. Both
units remained at full power. This morning report is an update to that
event report.

Power to the Unit 2 startup transformer was restored on Sunday,
August 5, 2001.  Using a crosstie from the Unit 2 startup transformer,
startup power to Unit 1 was restored by midday on Monday, August 6.
During its investigation, the licensee found that a 230 kV/12 kV fused
disconnect switch on the outside wall of the turbine building in Unit 1
was badly damaged. In addition, during the event, the licensee lost power
to several buildings such as the administration building and the
simulator. The licensee knew that electrical power would not be restored
to administrative buildings by Monday and instructed nonessential
personnel not to report to work. Power was restored to the administrative
buildings early on Tuesday, August 7.

The licensee is investigating the causes for the event and is repairing
damaged equipment.

Regional Action:

The senior resident inspector will continue to follow up on licensee
activities in accordance with the baseline inspection program.

Contact:  Bill Jones                 (817)860-8147
_
 

Page Last Reviewed/Updated Wednesday, March 24, 2021