Event Notification Report for January 18, 2014

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/17/2014 - 01/18/2014

Power Reactor
Event Number: 49740
Facility: SOUTH TEXAS
Region: 4     State: TX
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: PHIL STONE
HQ OPS Officer: DANIEL MILLS
Notification Date: 01/18/2014
Notification Time: 05:56 [ET]
Event Date: 01/18/2014
Event Time: 04:01 [CST]
Last Update Date: 01/18/2014
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED
Person (Organization):
RAY KELLAR (R4DO)
JENNIFER UHLE (NRR)
MARC DAPAS (R4RA)
SAMSON LEE (NRR)
JEFFERY GRANT (IRD)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
UNUSUAL EVENT DUE TO FIRE IN THE PROTECTED AREA

"At 0346 CST [the Unit 1 control room] received a fire alarm in the plant computer room. Upon investigation [the licensee] discovered [the plant computer] room with heavy smoke present and the halon system actuated. [Plant operators] entered '0P0P04-ZO-0008, Fire and Explosion'. Entered Unusual Event at 0401 CST. Fire brigade present at Unit 1 electrical auxiliary building. At 0412 CST the fire was declared to be under control with no visible signs of flame noticed by the fire brigade. Unusual Event based on HU2 (fire or explosion) in the (Protected Area or Switchyard) which affects normal plant operations."

At 0446 CST the fire was declared to be extinguished. No plant equipment or indications were affected.

The licensee has notified the NRC Resident Inspector, the State of Texas, and other local authorities.

Notified DHS SWO, FEMA Operations Center, NICC Watch Officer, and NuclearSSA via e-mail.

* * * UPDATE FROM TRIPP FRAHM TO DANIEL MILLS AT 0957 EST ON 1/18/14 * * *

"At 0957 EST, [on 1/18/14, the] Unusual Event [was] terminated. Fire damage assessment not complete. Working with site engineering, fire protection, and maintenance personnel to restore all fire detection and protection systems. Continuous fire watch being maintained. Priority is to restore fire detection and protection systems to affected area, followed by repairs to damaged equipment."

The licensee has notified the NRC Resident Inspector, the State of Texas, and other local authorities.

Notified R4DO (Keller), NRR (Uhle), R4RA (Dapas), NRR EO (Lee), and IRD MOC (Grant).

Notified DHS SWO, FEMA Operations Center, NICC Watch Officer, and NuclearSSA via e-mail.


Power Reactor
Event Number: 49741
Facility: MONTICELLO
Region: 3     State: MN
Unit: [1] [] []
RX Type: [1] GE-3
NRC Notified By: JACK EARSLEY
HQ OPS Officer: DANIEL MILLS
Notification Date: 01/18/2014
Notification Time: 07:45 [ET]
Event Date: 01/18/2014
Event Time: 03:38 [CST]
Last Update Date: 01/20/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
RICHARD SKOKOWSKI (R3DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 25 Power Operation 0 Hot Shutdown
Event Text
OFFSITE NOTIFICATION DUE TO DISCHARGE CANAL TEMPERATURE DROP

"At 0338 CST, Xcel Energy Environmental Services made a report to the State of Minnesota due to cooling water return to the Mississippi River via the plant's discharge canal dropping by more than 5 deg F per hour. The cause of the temperature drop was due to a required time limited reactor shut down. The reactor is currently shut down with all systems responding as expected.

"This notification is being made under 10 CFR 50.72(b)(2)(xi) based on a notification to another government agency.

"The NRC Resident Inspector has been notified"

* * * UPDATE FROM JON LAUDENBACH TO VINCE KLCO ON 1/20/14 AT 1259 EST * * *

"At 1130 EST on 1/20/2014, XCEL Energy Environmental Services made a report to the State of Minnesota (Minnesota Pollution Control Agency and the Minnesota Department of Natural Resources) due to the recorded total fish loss (207) as a result of the Monticello Plant's discharge canal temperature change per above.

"This is an update notification only and has no safety significance and no impact on the health and safety of the general public."

The licensee notified the NRC Resident Inspector.

Notified the R3DO (Skokowski).


Power Reactor
Event Number: 49742
Facility: HARRIS
Region: 2     State: NC
Unit: [1] [] []
RX Type: [1] W-3-LP
NRC Notified By: CARMINE MONTANA
HQ OPS Officer: DANIEL MILLS
Notification Date: 01/18/2014
Notification Time: 10:47 [ET]
Event Date: 01/18/2014
Event Time: 10:16 [EST]
Last Update Date: 01/18/2014
Emergency Class: ALERT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION 50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
MICHAEL F. KING (R2DO)
ERIC LEEDS (NRR)
VICTOR McCREE (R2RA)
JEFFERY GRANT (IRD)
ELIOT BRENNER (OPA)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 M/R Y 100 Power Operation 0 Hot Standby
Event Text
ALERT DECLARED DUE TO FIRE IN 480V BUS

"[At 1016 EST, an] Alert [was declared] based on EAL # HA 2.1 Fire or explosion resulting in either: visible damage to any table H-1 structure or system/component required for safe shutdown of the plant, or control room indication of degraded performance of any safe shutdown structure, system, or component within any table H-1 area.

"Fire in 480V bus 1D2. Reactor was manually tripped"

480 VAC safety related transformer fire in switchgear room. Plant reduced power and tripped the reactor manually. Reactor trip was uncomplicated. Fire was extinguished when the 480 VAC bus was de-energized.

The licensee has notified the NRC Resident Inspector, the State of North Carolina, and other local authorities.

Notified DHS SWO, DOE Ops Center, FEMA Operations Center, HHS Ops Center, NICC Watch Officer, USDA Ops Center, EPA EOC, and NuclearSSA via e-mail.

* * * UPDATE FROM JOEL DUHON TO JOHN SHOEMAKER AT 1602 EST ON 1/18/14 * * *

Harris Nuclear Plant secured from the Alert at 1551 EST, on 1/18/14. The plant is stable, the fire is out, the TSC and EOF have been secured and plant recovery has been transferred to the outage control center.

There were no personnel injuries or radiological releases.

Radiation monitor RM-*1TS-3653C (Technical Support Center Radiation Monitor) is out of service.

The licensee has notified the NRC Resident Inspector.

Notified the R2DO (King), R2RA (McCree), NRR (Leeds), IRD MOC (Grant), OPA (Brenner), NRR EO (Lee)

Notified DHS SWO, DOE Ops Center, FEMA Operations Center, HHS Ops Center, NICC Watch Officer, USDA Ops Center, EPA EOC, and NuclearSSA via e-mail.


Power Reactor
Event Number: 49743
Facility: COMANCHE PEAK
Region: 4     State: TX
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: DANNY BRADFORD
HQ OPS Officer: CHARLES TEAL
Notification Date: 01/18/2014
Notification Time: 12:18 [ET]
Event Date: 01/18/2014
Event Time: 08:40 [CST]
Last Update Date: 01/18/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
RAY KELLAR (R4DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 100 Power Operation 0 Hot Standby
Event Text
REACTOR TRIP DUE TO TURBINE TRIP

"At 0840 [CST], Comanche Peak NPP [CPNPP] Unit 1 turbine tripped causing a reactor trip. All rods inserted. No evolutions were in progress at time of trip. The cause of the trip is under investigation. A Generator Negative Sequence Current High Alarm was received immediately prior to turbine trip.

"Both Motor Driven Auxiliary Feed Water Pumps and the Turbine Driven Auxiliary Feed Water Pump started in response to Steam Generator Lo-Lo Levels.

"Currently, Unit 1 is being maintained in Hot Standby (Mode 3) in accordance with Integrated Plant Operating Procedure IPO-007A and the Emergency Response Guideline Procedure Network has been exited. Decay heat is being rejected to the Main Condenser via Steam Dump Valves (Turbine Bypass Valves).

"Normal plant response was observed and all systems actuated as expected. No radiological release is in progress.

"There was no impact to CPNPP Unit 2, and off-site power remains available."

The licensee has notified the NRC Resident Inspector.


Power Reactor
Event Number: 49744
Facility: FARLEY
Region: 2     State: AL
Unit: [] [2] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: RICK LULLING
HQ OPS Officer: CHARLES TEAL
Notification Date: 01/18/2014
Notification Time: 14:48 [ET]
Event Date: 01/18/2014
Event Time: 10:20 [CST]
Last Update Date: 01/20/2014
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
MICHAEL F. KING (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
UNIT 2 PYRO PANEL NON-FUNCTIONAL DUE TO UNKNOWN EQUIPMENT PROBLEMS

"At 10:20 [CST] on January 18, 2014, the Unit 2 Pyro Panel (fire/smoke detection panel) was declared non-functional due to an unknown equipment problem. Compensatory measures (e.g. continuous roving fire watches) have been established for all affected areas with the exception of the Unit 2 Containment Building. Containment fire watches have been established per the FSAR, which includes monitoring various temperatures, pressures, and other parameters for Containment, and systems associated with containment. However, this is not considered a satisfactory compensatory measure for maintaining effective assessment capability. Since a fire in Containment is an entry condition for the site's Emergency Plan, this is considered a loss of emergency assessment capability, and is being reported per 10CFR50.72(b)(3)(xiii).

"The NRC Senior Resident Inspector has been informed."


* * * UPDATE FROM RICK LULLING TO DANIEL MILLS AT 0700 EST ON 1/20/14 * * *

"At 0404 CST on 1/20/14 the Unit 2 Pyro panel was declared functional following the replacement of the fire indicating unit (FIU) and the power supply, and successful post maintenance testing. The emergency assessment capability for the site's Emergency Plan has been fully restored concerning a Containment fire."

The licensee notified the NRC Resident Inspector.

Notified R2DO (King).