Skip to main content

Event Notification Report for December 01, 2013

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
11/30/2013 - 12/01/2013

EVENT NUMBERS
49592
Power Reactor
Event Number: 49592
Facility: HOPE CREEK
Region: 1     State: NJ
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: LINDSAY KOBERLEIN
HQ OPS Officer: HOWIE CROUCH
Notification Date: 12/01/2013
Notification Time: 10:02 [ET]
Event Date: 12/01/2013
Event Time: 06:13 [EST]
Last Update Date: 12/01/2013
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL
Person (Organization):
DAN SCHROEDER (R1DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 100 Power Operation 0 Hot Shutdown
Event Text
AUTOMATIC REACTOR SCRAM DUE TO MAIN TURBINE TRIP

"While operating at 100% power on 12/01/2013, at 0613 EST, the main turbine tripped on moisture separator hi level. The reactor scrammed along with the main turbine trip. All safety systems responded as designed and expected. There was no radiological release. There were no injuries."

During the scram, all rods inserted into the core. The plant is stable in mode 3 in its normal shutdown electrical line up. Decay heat is being removed via the turbine bypass valves dumping steam to the main condenser.

The licensee notified the NRC Resident Inspector and will be notifying Lower Alloways Creek township.