                              ** EVENT NUMBERS **

36472  36473  36474  

+------------------------------------------------------------------------------+
|Other Nuclear Material                           |Event Number:   36472       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  BEST FOODS                           |NOTIFICATION DATE: 11/29/1999|
|LICENSEE:  BEST FOODS                           |NOTIFICATION TIME: 15:27[EST]|
|    CITY:  BAYONNE                  REGION:  1  |EVENT DATE:        11/29/1999|
|  COUNTY:                            STATE:  NJ |EVENT TIME:             [EST]|
|LICENSE#:  1586-70GL             AGREEMENT:  N  |LAST UPDATE DATE:  11/29/1999|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |STEVEN DENNIS        R1      |
|                                                |JOSIE PICCONE        NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  JAMES LITTEN                 |                             |
|  HQ OPS OFFICER:  BOB STRANSKY                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|BAB2 20.2201(a)(1)(ii)   LOST/STOLEN LNM>10X    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| STOLEN PROCESS GAUGE                                                         |
|                                                                              |
| A representative of Best Foods called the NRC Operations Center to report    |
| the apparent theft of a process gauge. The device, a Filtec model CI-2GV     |
| case inspector (serial #75009), could not be located for its triennial       |
| leakage test. The gauge contains a 100 millicurie Am-241 source (source      |
| #3428). The gauge was last swipe tested in 1996. The gauge was a spare, and  |
| has been kept in a storage area with other spare parts. The caller was       |
| unsure whether a police report would be filed.                               |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36473       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: POINT BEACH              REGION:  3  |NOTIFICATION DATE: 11/29/1999|
|    UNIT:  [1] [2] []                STATE:  WI |NOTIFICATION TIME: 16:43[EST]|
|   RXTYPE: [1] W-2-LP,[2] W-2-LP                |EVENT DATE:        11/29/1999|
+------------------------------------------------+EVENT TIME:             [CST]|
| NRC NOTIFIED BY:  GOSPAREK                     |LAST UPDATE DATE:  11/29/1999|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |GEOFFREY WRIGHT      R3      |
|10 CFR SECTION:                                 |                             |
|DDDD 73.71               UNSPECIFIED PARAGRAPH  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Refueling        |0        Refueling        |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| SECURITY EVENT                                                               |
|                                                                              |
| Unescorted access granted inappropriately. Contact the NRC Operations Center |
| for additional details. The NRC resident inspector has been informed by the  |
| licensee.                                                                    |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36474       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: WOLF CREEK               REGION:  4  |NOTIFICATION DATE: 11/30/1999|
|    UNIT:  [1] [] []                 STATE:  KS |NOTIFICATION TIME: 06:12[EST]|
|   RXTYPE: [1] W-4-LP                           |EVENT DATE:        11/30/1999|
+------------------------------------------------+EVENT TIME:        04:59[CST]|
| NRC NOTIFIED BY:  DALE BERRY                   |LAST UPDATE DATE:  11/30/1999|
|  HQ OPS OFFICER:  DICK JOLLIFFE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |DALE POWERS          R4      |
|10 CFR SECTION:                                 |                             |
|ASHU 50.72(b)(1)(i)(A)   PLANT S/D REQD BY TS   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| -TS REQD PLANT S/D DUE TO FAILED ESFAS AFW ACTUATION LOGIC RELAY 48 VDC      |
| POWER SUPPLY-                                                                |
|                                                                              |
| THE LICENSEE DISCOVERED A FAILED 48 VDC POWER SUPPLY FOR THE BALANCE OF      |
| PLANT ENGINEERED SAFETY FEATURE ACTUATION SYSTEM (ESFAS) AUTOMATIC ACTUATION |
| LOGIC RELAYS FOR THE TRAIN 'A' AUXILIARY FEEDWATER (AFW) SYSTEM.  TECH SPEC  |
| 3.3.2, FUNCTION 6.C, ACTION 2, REQUIRES THE LICENSEE TO RESTORE THE POWER    |
| SUPPLY TO OPERABLE STATUS OR TO PLACE THE PLANT IN HOT STANDBY MODE IN 6     |
| HOURS AND HOT SHUTDOWN IN THE FOLLOWING 6 HOURS.                             |
|                                                                              |
| THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.                            |
+------------------------------------------------------------------------------+
