The U.S. Nuclear Regulatory Commission is in the process of rescinding or revising guidance and policies posted on this webpage in accordance with Executive Order 14151 Ending Radical and Wasteful Government DEI Programs and Preferencing, and Executive Order 14168 Defending Women From Gender Ideology Extremism and Restoring Biological Truth to the Federal Government. In the interim, any previously issued diversity, equity, inclusion, or gender-related guidance on this webpage should be considered rescinded that is inconsistent with these Executive Orders.

Event Notification Report for October 12, 1999

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           10/08/1999 - 10/12/1999

                              ** EVENT NUMBERS **

36012  36209  36273  36274  36275  36276  36277  36278  36279  36280  36281  

!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36012       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: CLINTON                  REGION:  3  |NOTIFICATION DATE: 08/10/1999|
|    UNIT:  [1] [] []                 STATE:  IL |NOTIFICATION TIME: 14:23[EDT]|
|   RXTYPE: [1] GE-6                             |EVENT DATE:        08/10/1999|
+------------------------------------------------+EVENT TIME:        12:30[CDT]|
| NRC NOTIFIED BY:  ROBERT POWERS                |LAST UPDATE DATE:  10/08/1999|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |BRUCE BURGESS        R3      |
|10 CFR SECTION:                                 |                             |
|AOUT 50.72(b)(1)(ii)(B)  OUTSIDE DESIGN BASIS   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| EMERGENCY DIESEL GENERATOR DECLARED INOPERABLE DUE TO FUEL OIL LEAK          |
|                                                                              |
| "Abnormal readings from the lube oil analysis of the division 2 diesel       |
| generator lead to further testing of its lube oil. Gas chromatography        |
| analysis of the division 2 diesel generator lube oil showed a 5.7% fuel oil  |
| dilution. Vendor recommendations were to not operate the diesel with greater |
| than 5.0% fuel oil dilution. The division 2 diesel generator was tagged out  |
| for maintenance and declared inoperable on 8/9/99 at 1330 central time.      |
| During maintenance of the division 2 diesel generator it was discovered that |
| the 12th cylinder of the 16 cylinder engine fuel injector return line        |
| fitting was weeping fuel oil.                                                |
|                                                                              |
| "This notification is being made pursuant to 10CFR5072(b)(1)(ii)(B) as a     |
| condition outside of the design basis of the plant because of the discovery  |
| that the division 2 diesel generator has been incapable of performing its    |
| design function (intended safety function) for an extended period of time    |
| during operation."                                                           |
|                                                                              |
| The NRC resident inspector has been informed of this notification by the     |
| licensee.                                                                    |
|                                                                              |
| * * * RETRACTION 1803 10/8/1999 FROM ED TIEDEMANN TAKEN BY STRANSKY * * *    |
|                                                                              |
| "This report is to retract the notification of 8/10/1999, based on further   |
| evaluation by onsite engineering and licensing personnel, and offsite        |
| resources. The engineering evaluation performed for this event determined    |
| that the diesel generator would have fulfilled the design basis              |
| requirements, even with the effects of fuel dilution in the lube oil. "      |
|                                                                              |
| The NRC resident inspector has been informed of this retraction. Notified    |
| R3DO (Jacobson).                                                             |
+------------------------------------------------------------------------------+

!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36209       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: QUAD CITIES              REGION:  3  |NOTIFICATION DATE: 09/21/1999|
|    UNIT:  [1] [2] []                STATE:  IL |NOTIFICATION TIME: 20:41[EDT]|
|   RXTYPE: [1] GE-3,[2] GE-3                    |EVENT DATE:        09/10/1999|
+------------------------------------------------+EVENT TIME:        14:40[CDT]|
| NRC NOTIFIED BY:  DARYL CLARK                  |LAST UPDATE DATE:  10/08/1999|
|  HQ OPS OFFICER:  DICK JOLLIFFE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |ROGER LANKSBURY      R3      |
|10 CFR SECTION:                                 |                             |
|AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| -CONTROL ROOM EMERGENCY FILTRATION SYSTEM INOP DUE TO FAILING ITS            |
| SURVEILLANCE TEST-                                                           |
|                                                                              |
| At 1440 CDT on 09/10/99, while performing the Control Room Emergency         |
| Filtration (CREF) System monthly surveillance test, the system flow rate was |
| found to be 2317 scfm.  The required tech spec flow rate is 2000 scfm +/-    |
| 10%.  The licensee declared the CREF System inoperable per Tech Spec 3.8.D   |
| and entered a 7 day LCO.  This event is being reported to the NRC in         |
| accordance with 10CFR50.72 (b)(2)(iii)(D), a condition that prevented the    |
| fulfillment of a safety function.                                            |
|                                                                              |
| The licensee declared the CREF System operable 40 minutes later after        |
| adjusting the air flow.                                                      |
|                                                                              |
| The licensee is continuing to evaluate the reportability of this issue.      |
|                                                                              |
| The licensee informed the NRC Resident Inspector.                            |
|                                                                              |
| * * * RETRACTION 2158 10/8/1999 FROM LECHMAIER TAKEN BY STRANSKY * * *       |
|                                                                              |
| "This report is a retraction of the ENS call made on 9/21/99 concerning the  |
| Control Room Emergency Filtration System. We have completed our evaluation   |
| and have determined that the high flow rate condition found would not have   |
| prevented the system from performing its intended function. Therefore, this  |
| event is not reportable with respect to 10CFR50.72(b)(2)(iii).               |
|                                                                              |
| "The system damper that was previously repositioned on 9/1/99 was the cause  |
| of this high flow. This condition is prohibited by Technical Specifications  |
| (LCO exceeded) and is reportable in accordance with                          |
| 10CFR50.73(a)(2)(I)(B)."                                                     |
|                                                                              |
| The NRC resident inspector has been informed of this retraction by the       |
| licensee. Notified R3DO (Jacobson).                                          |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   36273       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  BRITISH NUCLEAR FUELS, PLC           |NOTIFICATION DATE: 10/08/1999|
|LICENSEE:  BRITISH NUCLEAR FUELS, PLC           |NOTIFICATION TIME: 08:14[EDT]|
|    CITY:                           REGION:     |EVENT DATE:        08/19/1999|
|  COUNTY:                            STATE:     |EVENT TIME:             [EST]|
|LICENSE#:                        AGREEMENT:  N  |LAST UPDATE DATE:  10/08/1999|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |JOHN KINNEMAN        R1      |
|                                                |BRIAN BONSER         R2      |
+------------------------------------------------+JOHN JACOBSON        R3      |
| NRC NOTIFIED BY:  EUR ING MIKE R A SMITH       |KRISS KENNEDY        R4      |
|  HQ OPS OFFICER:  LEIGH TROCINE                |KEVIN RAMSEY         NMSS    |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|CCCC 21.21               UNSPECIFIED PARAGRAPH  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 10 CFR PART 21 NOTIFICATION REGARDING THE POTENTIAL FOR A CYLINDER           |
| (MANUFACTURED BY STARVELEY'S LIMITED AND SUPPLIED BY BNFL TO USEC FOR        |
| ENRICHMENT) TO BE OVERFILLED BECAUSE THE CERTIFIED WATER CAPACITY STAMPED ON |
| THE CYLINDER IS LESS THAN THE SPECIFIED MINIMUM CAPACITY                     |
|                                                                              |
| The following text is a portion of a facsimile received from Eur Ing Mike R. |
| A. Smith, MRA Smith BSc CEng MIES, Head of Magnox and Hex Business, British  |
| Nuclear Fuels (BNFL), Fuel Business Group:                                   |
|                                                                              |
| "[10 CFR 21.21(4)(ii) - Identification of the facility, the activity, or the |
| basic component supplied for such facility or such activity within the U.S.  |
| which fails to comply or contains a defect:]  48Y Cylinder no. 1122/0690     |
| containing 12,155.5 kg of UF6 supplied to [United States Enrichment          |
| Corporation (USEC)] by BNFL Fuel for enrichment."                            |
|                                                                              |
| "[10 CFR 21.21(4)(iii) - Identification of the firm constructing the         |
| facility or supplying the basic component which fails to comply or contains  |
| a defect:]  Cylinder manufactured by Staveley's Limited, Manchester, England |
| in 1978.                                                                     |
|                                                                              |
| "[10 CFR 21.21(4)(iv) - Nature of the defect or failure to comply and the    |
| safety hazard which is created or could be created by such defect or failure |
| to comply:]  The certified water capacity stamped on the cylinder as part of |
| the name plate data is less than the minimum capacity specified in ANSI      |
| N14.1, Table 1, standard cylinder data for a 48Y cylinder.  [The] required   |
| minimum capacity [is] 142.7 ft�[, and the] actual certified water capacity   |
| [is] 4,019 kg; equivalent to 142.1 ft�.  The cylinder, in its current        |
| condition, represents no safety hazard since the actual contents of 2,155.5  |
| kg of UF6 still allows a cylinder ullage of 7.2%.  The cylinder has the      |
| potential to be overfilled if the normal maximum fill limit for a 48Y was    |
| reached (12,501 kg of UF6 as specified in ANSI N14.1)."                      |
|                                                                              |
| "[10 CFR 21.21(4)(v) - The date on which the information of such defect or   |
| failure to comply was obtained:]  A memo was sent from USEC on 19 August     |
| 1999, informing BNFL Fuel that they had noted the certified water capacity   |
| was less than the ANSI-N14.1 minimum."                                       |
|                                                                              |
| "[10 CFR 21.21(4)(vi) - In the case of a basic component which contains a    |
| defect or fails to comply, the number and location of all such components in |
| use at, supplied for, or being supplied for one or more facilities or        |
| activities subject to the regulations in this part:]  Cylinder 1122/0690 is  |
| one of a batch of 108 cylinders purchased from Staveleys in 1978.  All other |
| 48Y Type Cylinders 1122/0600 to 1122/0707 inclusive, numbering 107, are      |
| located on licensed sites in the UK."                                        |
|                                                                              |
| "[10 CFR 21.21(4)(vii) - The corrective action which has been, is being, or  |
| will be taken; the name of the individual or organization responsible for    |
| the action; and the length of time that has been or will be taken to         |
| complete the action:]  Having established that cylinder 1122/0690 is safe to |
| feed; it is proposed to discuss with USEC the possibility of proceeding with |
| the feed to their diffusion plant, as planned.  Alternatively, should USEC   |
| be unwilling to proceed then concession will be sought to transfer the       |
| cylinder back to BNFL in the UK."                                            |
|                                                                              |
| "Once emptied, the cylinder will be removed from service to prevent any      |
| possibility of a re-occurrence."                                             |
|                                                                              |
| "The Head of Site at BNFL Springfields has commissioned a Working Party,     |
| which includes an independent senior engineer, independent senior operations |
| manager, and standards/surveillance engineers."                              |
|                                                                              |
| "The Working Party:                                                          |
| a)  Has already independently verified that there are no other under         |
| capacity cylinders located in the U.S.;                                      |
| b)  Will independently verify whether or not any other BNFL cylinders are    |
| under capacity;                                                              |
| c)  In the event that the independent verification does reveal any further   |
| such defective cylinders, will initiate appropriate action to remove such    |
| cylinders from service;                                                      |
| d)  Will monitor the implementation of any such actions through to           |
| completion;                                                                  |
| e)  [Has] already examined and modified BNFL's cylinder filling procedures   |
| to prevent an under capacity cylinder from being filled in the future;       |
| [and]                                                                        |
| f)  [Is] in the process of reviewing our cylinder purchase specification to  |
| prevent any further under capacity cylinders from being supplied."           |
|                                                                              |
| "[10 CFR 21.21(4)(viii) - Any advice related to the defect or failure to     |
| comply about the facility, activity, or basic component that has been, is    |
| being, or will be given to purchasers or licensees:]  The UK Nuclear         |
| Installations Inspectorate (NII) and Department of the Environment,          |
| Transport, and Regions (DETR) have been advised of this notification."       |
|                                                                              |
| (Call the NRC operations officer for contact information.)                   |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36274       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: NINE MILE POINT          REGION:  1  |NOTIFICATION DATE: 10/08/1999|
|    UNIT:  [1] [] []                 STATE:  NY |NOTIFICATION TIME: 09:44[EDT]|
|   RXTYPE: [1] GE-2,[2] GE-5                    |EVENT DATE:        10/08/1999|
+------------------------------------------------+EVENT TIME:        09:05[EDT]|
| NRC NOTIFIED BY:  THOMAS HOWARD                |LAST UPDATE DATE:  10/08/1999|
|  HQ OPS OFFICER:  LEIGH TROCINE                +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          UNU                   |JOHN KINNEMAN        R1      |
|10 CFR SECTION:                                 |TAD MARSH            NRR     |
|AAEC 50.72 (a) (1) (I)   EMERGENCY DECLARED     |CHARLES MILLER       IRO     |
|                                                |MIKE TSCHILTZ        EDO     |
|                                                |BURNICE CARR         FEMA    |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       24       Power Operation  |24       Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| DECLARATION OF UNUSUAL EVENT DUE TO THE POSSIBILITY THAT VARIOUS AREAS OF    |
| THE PLANT ARE INACCESSIBLE DUE TO A HAZARDOUS ATMOSPHERE                     |
|                                                                              |
| The following text is a portion of a facsimile received from the licensee:   |
|                                                                              |
| "[At 0905 on 10/08/99, an] Unusual Event [was] declared due to Cardox fire   |
| system discharge ([carbon dioxide]) in [the Administration Building at       |
| 0815].  Various levels of the plant are being considered inaccessible until  |
| [oxygen] levels are verified [to be] satisfactory.  [Carbon dioxide] venting |
| is in progress.  [There is no] effect on plant operation at [the] present    |
| time[, and no effect is currently] anticipated."                             |
|                                                                              |
| "[The] preliminary cause of discharge of [carbon dioxide] appears to be a    |
| switch malfunction.  No fire was detected."                                  |
|                                                                              |
| The licensee stated that the Cardox fire system has both a 30-second siren   |
| and flashing red lights prior to the discharge of carbon dioxide in order to |
| allow personnel to evacuate the affected areas.  There were no injuries      |
| reported, and carbon dioxide venting is currently in progress.  The          |
| Administration Building and some adjacent areas of the turbine building were |
| affected.                                                                    |
|                                                                              |
| The licensee notified the NRC resident inspector as well as state and local  |
| agencies.  The licensee also plans to issue a media/press release.           |
|                                                                              |
| * * * UPDATE 1219 10/8/1999 FROM MATTESON TAKEN BY STRANSKY * * *            |
|                                                                              |
| The Unusual Event was terminated at 1210 EDT. The NRC resident inspector has |
| been informed. Notified R1DO (Kinneman), NRR (Marsh), IRO (Miller), FEMA     |
| (Carr).                                                                      |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36275       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SAINT LUCIE              REGION:  2  |NOTIFICATION DATE: 10/08/1999|
|    UNIT:  [1] [2] []                STATE:  FL |NOTIFICATION TIME: 13:17[EDT]|
|   RXTYPE: [1] CE,[2] CE                        |EVENT DATE:        10/08/1999|
+------------------------------------------------+EVENT TIME:        11:10[EDT]|
| NRC NOTIFIED BY:  CALVIN WARD                  |LAST UPDATE DATE:  10/08/1999|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |BRIAN BONSER         R2      |
|10 CFR SECTION:                                 |                             |
|APRE 50.72(b)(2)(vi)     OFFSITE NOTIFICATION   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Cold Shutdown    |0        Cold Shutdown    |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| OFFSITE NOTIFICATION REQUIRED BY NPDES PERMIT                                |
|                                                                              |
| The licensee contacted the Florida Department of Environmental Protection    |
| (DEP) regarding the discharge of effluent to the Atlantic Ocean. The site    |
| settling ponds were pumped down due to high water levels caused by recent    |
| rain. The site National Pollution Discharge Elimination System (NPDES)       |
| permit requires that the licensee contact the state DEP regarding this       |
| discharge. No release limits were exceeded. The NRC resident inspector has   |
| been informed of this notification by the licensee.                          |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36276       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SALEM                    REGION:  1  |NOTIFICATION DATE: 10/08/1999|
|    UNIT:  [1] [2] []                STATE:  NJ |NOTIFICATION TIME: 16:13[EDT]|
|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        10/08/1999|
+------------------------------------------------+EVENT TIME:        15:50[EDT]|
| NRC NOTIFIED BY:  RUSS GUMBERT                 |LAST UPDATE DATE:  10/08/1999|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |JOHN KINNEMAN        R1      |
|10 CFR SECTION:                                 |                             |
|ADEG 50.72(b)(1)(ii)     DEGRAD COND DURING OP  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Refueling        |0        Refueling        |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 10 CFR PART 50, APPENDIX R ISSUE REGARDING CABLE SEPARATION                  |
|                                                                              |
| The following is text of a (rather lengthy) facsimile submitted by the       |
| licensee:                                                                    |
|                                                                              |
| "1.  Description of Condition                                                |
|                                                                              |
| "During a review of the Salem Post-fire Safe Shutdown Analysis a concern was |
| identified with the cable routing of the pressurizer PORV and block valves.  |
| The cable for each PORV and its associated block valve is routed in the same |
| cable tray inside the containment. The pressurizer PORVs and block valves    |
| are considered a high/low pressure interface point for 10CFR50 Appendix R    |
| analysis. Therefore each PORV block valve combination is considered as       |
| redundant components that require proper separation in accordance with       |
| Section III.G.2 of Appendix R to prevent hot shorts, open circuits, or       |
| shorts to ground from causing spurious operation of these valves.            |
|                                                                              |
| "In the event of a postulated fire inside containment a block valve could    |
| lose power; since this valve is in the open position it would not be able to |
| be closed. A hot short could also cause the PORV to spuriously open. These   |
| two occurrences together would result in the loss of Reactor Coolant System  |
| (RCS) inventory control. This condition does not satisfy the 10CFR50         |
| Appendix R performance goal of inventory control for post-fire Safe Shutdown |
| (SSD).                                                                       |
|                                                                              |
| "A second similar concern exists with the PORVs and block valves for         |
| Alternate Shutdown (ASD) capability. ASD is implemented in the event of a    |
| fire in the Control Room, Relay Room or the ceiling of the 460V Switchgear   |
| room. A fire in the above areas could lead to the spurious operation of the  |
| PORVs. Operators implement the ASD methodology in accordance with procedures |
| S1(2).OP-AB.CR-0002. Spurious operation of the PORV could occur prior to the |
| operators reaching the step in the ASD to operate the local switch for the   |
| block valve and close the block valve. In the current procedure, it takes    |
| approximately 20 minutes to reach the step to operate the transfer switch    |
| for the block valve. Prior to closing the block valve, there would be a loss |
| of RCS inventory control due to the spurious operation of the PORV.          |
|                                                                              |
| "2.  Impact Statement                                                        |
|                                                                              |
| "For design basis accident mitigation (UFSAR Chapter 15), the PORV and block |
| valves are not impacted and remain operable. Currently, the PORV and block   |
| valve configuration does not meet the requirements of 10CFR50 Appendix R and |
| therefore is outside the design basis of the plant for Appendix R. This item |
| is reportable in accordance with 10CFR50.72.                                 |
|                                                                              |
| "The inadvertent opening of the PORV and block valve would result in RCS     |
| depressurization. For the block valve and PORV to open the following needs   |
| to occur:                                                                    |
|                                                                              |
| "*     an external or internal "hot short" of the PORV solenoid DC control   |
| circuitry which causes the energization of the solenoid, coincident with the |
| complete loss of the power supply cable to the PORV block valve, which       |
| prevents remote operation (closure) of the block valve, is a very low        |
| probability event.                                                           |
|                                                                              |
| "*     The control cables have external insulation, with an armored shield,  |
| with multiple individual insulated conductors within the shield. In order    |
| for the internal hot short to occur, the external fire would have to burn    |
| through the cable external jacket, and shielding, and then selectively       |
| affect specific DC conductors within the cable to enable conductors of the   |
| correct polarity to come in contact in such a manner to energize the         |
| solenoid valve and open the PORV. The same external fire would also have to  |
| damage the power supply to the block valve to preclude operation, as stated  |
| above.                                                                       |
|                                                                              |
| "*     In order for the external hot short to occur, another cable in the    |
| same raceway system, which is also of a shielded construction, would have to |
| have one of its internal conductors affected by the external fire affect the |
| conductors of the PORV control circuit, which is contained in its own        |
| shielded cable. This is an even more unlikely scenario.                      |
|                                                                              |
| "The probability of a fire, of a magnitude that would cause the above to     |
| occur inside containment is extremely low for the following reasons.         |
|                                                                              |
| "*     The main source of combustion inside containment is the oil in the    |
| RCP motor. However, the RCP motor is not in the vicinity of the affected     |
| cable trays. The RCP motor is equipped with detection and suppression        |
| system. An oil collection system is provided in the event of the leakage.    |
|                                                                              |
| "*     The introduction of transient combustible materials into the          |
| containment is extremely remote due to limited containment access during     |
| operation.                                                                   |
|                                                                              |
| "*     The RCP motor oil level has a low-level alarm in the control room.    |
| Any inadvertent oil loss would be detected and corrected early. This reduces |
| the probability of lire due to the oil leakage.                              |
|                                                                              |
| "*     The cables in the affected cable tray are made up of                  |
| self-extinguishing cable material. This will minimize fire propagation along |
| the cables.                                                                  |
|                                                                              |
| "*     Containment volume is large. The probability of a plume to occur to   |
| affect the cable trays is extremely low.                                     |
|                                                                              |
| "*     A qualitative risk assessment shows that the probability of fire      |
| inside containment, in the area of concern, is extremely low.                |
|                                                                              |
| "3.  Cause of Occurrence                                                     |
|                                                                              |
| "The above concerns were not properly evaluated during development of the    |
| safe shutdown analysis.                                                      |
|                                                                              |
| "4.  Immediate Corrective Actions                                            |
|                                                                              |
| "*     Establish appropriate compensatory measures for the Alternate         |
| Shutdown Area in accordance with the fire protection program.                |
|                                                                              |
| "*     A containment loose debris inspection is performed following each     |
| containment entry during Modes 1-4.                                          |
|                                                                              |
| "*     Following any containment entry, a walkdown will be performed to      |
| ensure that there are no combustible loads in the vicinity of the affected   |
| cable trays.                                                                 |
|                                                                              |
| "*     Ensure operating shifts are alerted that spurious operation of the    |
| PORVs may be caused by a fire inside containment.                            |
|                                                                              |
| "*     Additional corrective actions are being evaluated and will be         |
| implemented as necessary.                                                    |
|                                                                              |
| "5.  Long Term Corrective Actions                                            |
|                                                                              |
| "*     Prior to startup from the next refueling outage, evaluate potential   |
| plant modifications and/or licensing/design basis changes. Actions will be   |
| implemented as required to address the PORV and block valve spurious         |
| operation concern."                                                          |
|                                                                              |
| The NRC resident inspector has been informed of this notification by the     |
| licensee.                                                                    |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36277       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: SURRY                    REGION:  2  |NOTIFICATION DATE: 10/09/1999|
|    UNIT:  [1] [2] []                STATE:  VA |NOTIFICATION TIME: 22:13[EDT]|
|   RXTYPE: [1] W-3-LP,[2] W-3-LP                |EVENT DATE:        10/09/1999|
+------------------------------------------------+EVENT TIME:        12:41[EDT]|
| NRC NOTIFIED BY:  LISA HILBERT-SEMMES          |LAST UPDATE DATE:  10/09/1999|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |BRIAN BONSER         R2      |
|10 CFR SECTION:                                 |JOHN ZWOLINSKI       NRR     |
|AESF 50.72(b)(2)(ii)     ESF ACTUATION          |CHARLES MILLER       IRO     |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|2     N          Y       100      Power Operation  |96       Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| EDGs START AND LOAD DUE TO LOSS OF ONE RESERVE STATION SERVICE TRANSFORMER   |
|                                                                              |
| "At 1241 hours, with Surry Power Station Unit 1 and Unit 2 at 100% reactor   |
| power, a loss of 'C' Reserve Station Service Transformer (RSST) occurred due |
| to a fire on one of the leads. The #1 Emergency Diesel Generator (EDG) auto  |
| started due to an undervoltage signal on the Unit 1 'H' emergency bus and    |
| re-energized the Unit 1 'H' emergency bus. Also, the #3 EDG auto started due |
| to an undervoltage signal on the Unit 2 'J' emergency bus and re-energized   |
| the Unit 2 'J' emergency bus. The fire team reported that the fire was out   |
| at 1243. Unit 1 remained at 100% power. Unit 2 decreased to 96% power due to |
| a perturbation on the semi-vital bus when the 'J' emergency bus was          |
| de-energized then re-energized by the #3 EDG. The unit was returned to 100%  |
| power at 1400 when all unit conditions were verified stable. All equipment   |
| performed as expected during the event and there were no unexplained         |
| occurrences other than the loss of 'C' RSST which is under investigation.    |
|                                                                              |
| "No adverse radiological consequences resulted from this event. There were   |
| no radiation releases due to this event, nor were there any personnel        |
| injuries or contamination events.                                            |
|                                                                              |
| "Unit 1 is currently at 100% power and 845 MWe with #1 EDG supplying the 'H' |
| emergency bus.                                                               |
|                                                                              |
| "Unit 2 is currently at 100% power and 855 MWe with #3 EDG supplying the 'J' |
| emergency bus.                                                               |
|                                                                              |
| "This event was initially determined to be not reportable based on the EDG   |
| auto start signal being due to an undervoltage signal and not a valid ESF    |
| signal. Upon further review of Tech Specs and NUREG 1022, it was determined  |
| at 2015 that the EDG auto starts due to an under voltage signal were         |
| reportable as an ESF actuation."                                             |
|                                                                              |
| The NRC resident inspector has been informed of this event by the licensee.  |
|                                                                              |
| This is event is being reported in accordance with 10 CFR 50.72(b)(2)(ii).   |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Research Reactor                                 |Event Number:   36278       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: STATE UNIV OF NEW YORK AT BUFFALO    |NOTIFICATION DATE: 10/10/1999|
|   RXTYPE: 2000 KW PULSTAR                      |NOTIFICATION TIME: 11:48[EDT]|
| COMMENTS:                                      |EVENT DATE:        10/09/1999|
|                                                |EVENT TIME:        22:00[EDT]|
|                                                |LAST UPDATE DATE:  10/10/1999|
|    CITY:  BUFFALO                  REGION:  1  +-----------------------------+
|  COUNTY:  ERIE                      STATE:  NY |PERSON          ORGANIZATION |
|LICENSE#:  R-77                  AGREEMENT:  Y  |JOHN KINNEMAN        R1      |
|  DOCKET:  05000057                             |                             |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  MARK ADAMS                   |                             |
|  HQ OPS OFFICER:  BOB STRANSKY                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NINF                     INFORMATION ONLY       |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| COURTESY CALL DUE TO POWER OUTAGE                                            |
|                                                                              |
| The licensee reported that a transformer failure resulted in a power outage  |
| to the reactor facility. The emergency diesel generator started, but was     |
| manually stopped due to poor operating performance. Partial power has been   |
| restored from another building. The licensee anticipates that replacement of |
| the transformer could take from three to six weeks. This facility has been   |
| shut down since 1994. The only required equipment affected by the outage are |
| gaseous radiation monitors, which have an allowed outage time of 10 days.    |
|                                                                              |
| The caller made this report because of possible press interest in the event. |
| The local media monitors campus radio transmissions, and the caller          |
| speculated that transmissions regarding the event could be interpreted by    |
| the media as a serious event. The licensee may make a press release.         |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36279       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: FERMI                    REGION:  3  |NOTIFICATION DATE: 10/11/1999|
|    UNIT:  [2] [] []                 STATE:  MI |NOTIFICATION TIME: 13:07[EDT]|
|   RXTYPE: [2] GE-4                             |EVENT DATE:        10/11/1999|
+------------------------------------------------+EVENT TIME:        09:59[EDT]|
| NRC NOTIFIED BY:  COSEO                        |LAST UPDATE DATE:  10/11/1999|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |JOHN JACOBSON        R3      |
|10 CFR SECTION:                                 |                             |
|AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION    |                             |
|NLCO                     TECH SPEC LCO A/S      |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|2     N          Y       97       Power Operation  |97       Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| VARIOUS SAFETY RELATED EQUIPMENT DECLARED INOPERABLE DUE TO LOSS OF COOLING  |
| TO THE BATTERY CHARGER ROOM .                                                |
|                                                                              |
| Following startup of the Division 2 Residual Heat Removal Service Water      |
| (RHRSW) pumps, it was observed that the Division 2 Emergency Equipment       |
| Service Water (EESW) pump was rotating backwards. Division 2 RHRSW flow was  |
| normal at greater than 9000 gpm. The Division 2 Ultimate Heat Sink (UHS)     |
| service water systems discharge into a common header that can be routed to   |
| the Division 2 UHS cooling tower fans or directly to the reservoir. This     |
| indicates that the Division 2 EESW pump discharge check valve is not fully   |
| closed. The Division 2 EESW pump control was placed in OFF/RESET (normally   |
| in AUTO) at 0959 hrs on 10/11/99. The pump discharge valve was closed to     |
| isolate the flow path and Division 2 EESW has been declared inoperable. This |
| results in Division 2 Emergency Equipment Cooling Water (EECW) being         |
| inoperable. Division 2 EECW provides cooling to the High Pressure Coolant    |
| Injection (HPCI) pump area cooler during accident conditions. Therefore, the |
| HPCI system was declared inoperable(14 day LCO) at 0959 on 10/11/99. HPCI    |
| remains in standby lineup ready for automatic initiation. The Div 2 EECW     |
| also provides cooling to the battery charger room. With the batteries        |
| inoperable they are in an 18 hr LCO.                                         |
|                                                                              |
| The check valve internals have been inspected and preliminary findings       |
| indicate that all parts are intact. The failure of the valve appears to be   |
| caused by a worn disc pin in the valve. Necessary repairs are in progress.   |
|                                                                              |
| The Resident Inspector was notified.                                         |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36280       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: POINT BEACH              REGION:  3  |NOTIFICATION DATE: 10/11/1999|
|    UNIT:  [1] [2] []                STATE:  WI |NOTIFICATION TIME: 16:56[EDT]|
|   RXTYPE: [1] W-2-LP,[2] W-2-LP                |EVENT DATE:        10/11/1999|
+------------------------------------------------+EVENT TIME:        15:14[CDT]|
| NRC NOTIFIED BY:  HASTINGS                     |LAST UPDATE DATE:  10/11/1999|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |JOHN JACOBSON        R3      |
|10 CFR SECTION:                                 |                             |
|AOUT 50.72(b)(1)(ii)(B)  OUTSIDE DESIGN BASIS   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|2     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| FIRE BARRIER WALL NOT MEETING THE LICENSEE'S REQUIRED APPENDIX "R" DESIGN    |
| BASIS.                                                                       |
|                                                                              |
| IT WAS DISCOVERED THAT A WALL SEGMENT SEPARATING THE CONTROL ROOM FROM THE   |
| CABLE SPREADING ROOM PROVIDES ONLY A 1.5 HOUR FIRE BARRIER INSTEAD OF THE 3  |
| HOUR FIRE BARRIER REQUIRED BY THE LICENSEE'S APPENDIX "R" DESIGN             |
| COMMITMENTS.  THIS PLACES THE WALL SEGMENT OUTSIDE APPENDIX "R" DESIGN       |
| BASIS.  HOURLY FIRE WATCHES ON BOTH SIDES OF THIS WALL WERE ALREADY IN PLACE |
| PRIOR TO THIS DISCOVERY AND WILL CONTINUE UNTIL THE PROBLEM IS RESOLVED.     |
|                                                                              |
| THE RESIDENT INSPECTOR WAS INFORMED.                                         |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   36281       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PALO VERDE               REGION:  4  |NOTIFICATION DATE: 10/11/1999|
|    UNIT:  [] [] [3]                 STATE:  AZ |NOTIFICATION TIME: 19:10[EDT]|
|   RXTYPE: [1] CE,[2] CE,[3] CE                 |EVENT DATE:        10/11/1999|
+------------------------------------------------+EVENT TIME:        08:40[MST]|
| NRC NOTIFIED BY:  STROUD                       |LAST UPDATE DATE:  10/11/1999|
|  HQ OPS OFFICER:  CHAUNCEY GOULD               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |KRISS KENNEDY        R4      |
|10 CFR SECTION:                                 |                             |
|HFIT 26.73               FITNESS FOR DUTY       |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|                                                   |                          |
|3     N          Y       100      Power Operation  |100      Power Operation  |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| CONTRABAND MATERIAL REPORTED AS A FITNESS-FOR-DUTY ISSUE                     |
|                                                                              |
| CONTRABAND MATERIAL FOUND IN THE VITAL AREA.   IMMEDIATE COMPENSATORY        |
| MEASURES TAKEN UPON DISCOVERY.  THE RESIDENT INSPECTOR WAS NOTIFIED.         |
|                                                                              |
| CONTACT THE HEADQUARTERS OPERATIONS OFFICER FOR ADDITIONAL DETAILS.          |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Thursday, March 25, 2021