[an error occurred while processing this directive]
United States Nuclear Regulatory Commission - Protecting People and the Environment



                                UNITED STATES
                        NUCLEAR REGULATORY COMMISSION
                    OFFICE OF NUCLEAR REACTOR REGULATION
                           WASHINGTON, D.C.  20555

                              December 18, 1992


NRC INFORMATION NOTICE 88-23, SUPPLEMENT 4:  POTENTIAL FOR GAS BINDING OF
                                             HIGH-PRESSURE SAFETY INJECTION
                                             PUMPS DURING A DESIGN BASIS
                                             ACCIDENT


Addressees

All holders of operating licenses or construction permits for nuclear power
reactors.

Purpose

The U.S. Nuclear Regulatory Commission (NRC) is issuing this information
notice supplement to alert addressees to problems that could result from the
transport and accumulation of gases in the piping of emergency core cooling
systems.  It is expected that recipients will review the information for
applicability to their facilities and consider actions, as appropriate, to
avoid similar problems.  However, suggestions contained in this information
notice are not NRC requirements; therefore, no specific action or written
response is required.  

Background

Each unit at the Surry Power Station has two low head safety injection (LHSI)
pumps which, during a design basis event, are initially aligned to take
suction from the refueling water storage tank (RWST) and to discharge into
cold legs of the reactor coolant system (RCS).  When a low level in the RWST
is reached, the LHSI pumps would automatically be realigned to take suction
from the containment sump and discharge to the high head safety injection
(HHSI) pumps ("piggyback" mode) through the recirculation mode transfer (RMT)
piping.  Two check valves in series are located in each of the three LHSI pump
discharge lines to the RCS cold legs.  These check valves are the pressure
boundary between the high pressure RCS and the low pressure LHSI system during
normal power operation.  Attachment 1 depicts the general layout for piping
and components of the Surry Units 1 and 2 LHSI and HHSI systems.

Description of Circumstances

While starting the LHSI pumps at Surry Unit 2 in July 1992, Virginia Power
(the licensee) observed pressure spikes, some greater than approximately 
2,760 kPa (400 psig), in the LHSI piping.  Upon investigating these pressure
spikes, the licensee discovered gas voids in the RMT piping.  Approximately
1.4 cubic meters (50 cubic feet) of gas (at standard temperature and pressure)
was vented from the RMT piping.  Another 0.9 cubic meters (32.5 cubic feet) of
gas was vented from the LHSI pump discharge to the cold leg piping.  Over the 

9212150017.

                                                      IN 88-23, Supplement 4
                                                      December 18, 1992
                                                      Page 2 of 3


next week an additional 0.7 cubic meters (26 cubic feet) of gas was vented
from the LHSI pump discharge to the RCS cold leg piping.  Attachment 1
identifies the locations from which gas was vented.

Samples of the vented gas were analyzed.  The samples contained varying
quantities of hydrogen, oxygen, and nitrogen.

The licensee believes that the principal source of the gas is from reactor
coolant that leaked past the RCS cold leg check valves into the LHSI piping. 
Once the reactor coolant leaks past the check valves it depressurizes from
approximately 15,400 kPa (2235 psig) to approximately 138 kPa (20 psig) and
cools from approximately 282 degrees Celsius (540 degrees Fahrenheit) to
various local temperatures.  Gases in the reactor coolant then come out of
solution and migrate to the high points of the LHSI system.

The licensee concluded that the system pressure spikes observed when starting
the LHSI pumps may have resulted from collapsing steam or gas voids within the
LHSI system.  The licensee concluded that steam voids could be present at
normal operating temperature.  The licensee conducted ultrasonic testing and
confirmed the presence of voids upstream of the RCS cold leg check valves in
the LHSI system piping.  Cold leg check valve leakage in Unit 2 is indicated
by the fact that the unlagged common discharge header for the LHSI pumps was
hot to the touch (approximately 49 degrees Celsius [120 degrees Fahrenheit]). 
In addition, leakage rates into the RWST of up to 1.13 liters per minute 
(0.3 gallons per minute) have been identified during normal power operation. 
The combined Unit 2 cold leg check valve seat leak rate measured in July 1992
was approximately 0.42 liters per minute (0.11 gallons per minute).  These
leakage rates are within the limits allowed by the Technical Specifications.

Upon discovery of the gas accumulation in the Unit 2 piping system, the
licensee began routine venting of portions of the system that may contain gas
pockets.  The licensee initially vented those sections of piping several times
a day until confident that rapid increase in gas accumulation was not
occurring.  The quantity of gas vented is recorded and trended, and the
venting frequency is adjusted as necessary based on the results.  This piping
is currently being vented weekly.  In addition, the licensee inspected and
subsequently identified gas in the Unit 1 RMT piping.  Comparable actions were
then taken on Unit 1.

The licensee also analyzed the possible effects of the accumulated gas on the
HHSI pumps for the specific circumstances identified and concluded that it
would not have significantly degraded pump performance.

Discussion

To address previous concerns with gas binding of high pressure safety
injection pumps, the licensee initially installed additional vents on the RMT
piping near the interfaces with the HHSI and LHSI systems.  The licensee also
evaluated possible gas intrusion into systems other than high pressure safety
injection and evaluated the effect of maintenance activities that could allow 
.                                                      IN 88-23, Supplement 4
                                                      December 18, 1992
                                                      Page 3 of 3


air to enter fluid systems.  However, for these actions the licensee focused
on the volume control tank as being the principal source of gas.  The licensee
did not consider RCS leakage through check valves as a potential source of
gas.

Additional discussion concerning potential gas intrusion into high-pressure
safety injection pumps is contained in NRC Information Notice (IN) 88-23, 
IN 88-23, Supplement 1, IN 88-23, Supplement 2, and IN 88-23, Supplement 3
dated May 12, 1988, January 5, 1989, January 31, 1990, and December 10, 1990,
respectively.  

Additional instances of gas intrusion have been identified since the issuance
of IN 88-23, Supplement 3.  For example: 

      TU Electric identified the presence of gas in portions of the suction
      piping for the centrifugal charging pumps at Comanche Peak Unit 1 in
      March 1991.  The licensee attributed the source of the gas to hydrogen
      coming out of solution in the centrifugal charging pump suction header
      and collecting in the associated vertical piping.  The licensee
      indicated that corrective actions to be taken to address this finding
      included the establishment of venting requirements.  Additional
      discussion concerning this event is contained in Licensee Event Report
      (LER) 50-445/91-012 dated April 25, 1991.  

      Water hammer because of air or gas intrusion is believed to have
      contributed to the loss of high head safety injection function
      identified at Shearon Harris in April 1991.  Additional discussion
      concerning this event is contained in IN 92-61 "Loss of High Head Safety
      Injection," and IN 92-61, Supplement 1, dated August 20, 1992, and
      November 6, 1992, respectively, and in LER 50-400/91-008-1 dated
      May 15, 1991.

This information notice requires no specific action or written response.  If
you have any questions about the information in this notice, please contact
the technical contact listed below or the appropriate Office of Nuclear
Reactor Regulation (NRR) project manager.


                                             ORIGINAL SIGNED BY


                                        Brian K. Grimes, Director
                                        Division of Operating Reactor Support
                                        Office of Nuclear Reactor Regulation

Technical contact:   S. Tingen, Region II
                     (804) 357-2101

Attachments:
1.  Surry, Units 1 and 2 HHSI and LHSI Systems
2.  List of Recently Issued NRC Information Notices
.
Page Last Reviewed/Updated Thursday, March 29, 2012